Plan Review Notes
Plan Review Notes For Permit 06120362
Permit Number 06120362
Review Stop P
Sequence Number 1
Notes
Date Text
2007-02-03 14:32:26DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
  
 1. SHT A-2 MORE INFORMATION REQUIRED. NOTE INDICATES A
 VENT WILL BE REMOVED. PLEASE INDICATE WHAT TYPE OF VENT
 WILL BE REMOVED.--NOTE INDICATES THAT THE ROOF
 DRAIN WILL NEED AN EXTENTION. IF OLD PAVERS WILL BE
 REMOVED FROM THE ROOF AND NEW PAVERS WILL BE INSTALLED,
 WILL THE NEW PAVERS BE THICKER THE THOSE REMOVED? THE
 ROOF SHOWS NO SECONDARY ROOF DRAINS. PLEASE INDICATE
 THE SQUARE FOOTAGE BEING DRAINED BY THIS ROOF DRAIN.
 INCLUDE 1/2 AREA OF ALL VERTICAL WALLS, AND THE AREA
 FROM THE ROOF ABOVE DRAINING ON TO THE ROOF AREA. (A
 DOWNSPOUT IS INDICATED). SHOW THE LOCATION OF ALL ROOF
 DRAINS AND SECONDARY ROOF DRAINS OR SCUPPERS IN ROOF
 AREA WHERE NEW TILE WORK WILL BE INSTALLED. SECTIONS
 106, 1107 AND ALL SUBSECTIONS& 106.1.1 1.
  
 2. IT IS INDICATED THAT A NEW ROOF WILL BE INSTALLED ON
 SHT A-5 FOR THE 8TH FLOOR. PLEASE INDICATE THE LOCATION
 OF THE ROOF DRAINS, PRIMARY AND SECONDARY. SUBMIT
 CALCULATIONS FOR THE PRIMARY AND SECONDARY ROOF DRAINS.
 INCLUDE 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS. SECTIONS 1106 & 1107 WITH ALL SUBSECTIONS.
  
 3. SHT M-1 INDICATES HOT & COLD WATER TO BE STUBED OUT
 FOR FUTURE USE. ALSO THIS SHEET SHOWS (4) 4" RAIN WATER
 LEADERSTO BE REUSED.A PLUMBING PERMIT WILL BE
 REQUIRED. SECTION 105.1.
  
 4. SEPARATE ROOF PERMIT WILL BE REQUIRED. SECTION
 105.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]