Plan Review Notes
Plan Review Notes For Permit 06120362
Permit Number 06120362
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-02-14 15:49:34*****DENIED*****
  
  
 01.THE ACTUAL ADDRESS OF WHERE THE SCOPE OF WORK IS
 GOING TO CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 02.THE 2003 NFPA 101 AND 2004 FLORIDA FIRE PREVENTION
 CODE SHALL BE REFERENCED.
  
 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 04.CONSTRUCTION AND / OR DEMOLITION OPERATIONS SHALL
 NOT INTERFERE OR HINDER WITH ACCESS TO OR EGRESS FROM
 THE FLOOR(S) OR BUILDING.
  
 05.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 06.PLEASE INDICATE IF THE FLOOR(S) OR THE BUILDING
 WILL BE OCCUPIED DURING THE SCOPE OF WORK.IF SO, THIS
 WILL BE PERMITTED ONLY WHERE REQUIRED MEANS OF EGRESS
 AND REQUIRED FIRE PROTECTION FEATURES ARE IN PLACE AND
 MAINTAINED, OR WHERE ALTERNATIVE LIFE SAFETY MEASURES
 ACCEPTABLE TO THE AHJ ARE IN PLACE.
  
 07. WHAT IS THE INTERIOR FINISH CLASSIFICATION FOR THE
 WALLS SND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS,
 AND IN ALL OTHER AREA?
  
 08.SINCE THE FIRE ALARM AND FIRE SPRINKLER SYSTEM
 WILL BE MODIFIED, SEPARATE PLANS AND PERMITS WILL BE
 REQUIRED.
  
 09.ALTHOUGH THIS ELEVATOR WILL SERVE ONLY TWO FLOORS,
 IT STILL SHALL CONFORM TO THE REQUIREMENTS OF ASME
 A17.1
  
 10.EMERGENCY LIGHTING WILL BE REQUIRED IN THE NEW
 STAIR AREA.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722