| 2007-02-14 15:49:34 | *****DENIED***** |
| | |
| | |
| | 01.THE ACTUAL ADDRESS OF WHERE THE SCOPE OF WORK IS |
| | GOING TO CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH |
| | SUBMITTED PLAN SHEET. |
| | |
| | 02.THE 2003 NFPA 101 AND 2004 FLORIDA FIRE PREVENTION |
| | CODE SHALL BE REFERENCED. |
| | |
| | 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 04.CONSTRUCTION AND / OR DEMOLITION OPERATIONS SHALL |
| | NOT INTERFERE OR HINDER WITH ACCESS TO OR EGRESS FROM |
| | THE FLOOR(S) OR BUILDING. |
| | |
| | 05.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS |
| | SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT |
| | OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| | |
| | 06.PLEASE INDICATE IF THE FLOOR(S) OR THE BUILDING |
| | WILL BE OCCUPIED DURING THE SCOPE OF WORK.IF SO, THIS |
| | WILL BE PERMITTED ONLY WHERE REQUIRED MEANS OF EGRESS |
| | AND REQUIRED FIRE PROTECTION FEATURES ARE IN PLACE AND |
| | MAINTAINED, OR WHERE ALTERNATIVE LIFE SAFETY MEASURES |
| | ACCEPTABLE TO THE AHJ ARE IN PLACE. |
| | |
| | 07. WHAT IS THE INTERIOR FINISH CLASSIFICATION FOR THE |
| | WALLS SND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS, |
| | AND IN ALL OTHER AREA? |
| | |
| | 08.SINCE THE FIRE ALARM AND FIRE SPRINKLER SYSTEM |
| | WILL BE MODIFIED, SEPARATE PLANS AND PERMITS WILL BE |
| | REQUIRED. |
| | |
| | 09.ALTHOUGH THIS ELEVATOR WILL SERVE ONLY TWO FLOORS, |
| | IT STILL SHALL CONFORM TO THE REQUIREMENTS OF ASME |
| | A17.1 |
| | |
| | 10.EMERGENCY LIGHTING WILL BE REQUIRED IN THE NEW |
| | STAIR AREA. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |