| Date |
Text |
| 2007-01-05 07:39:51 | ** UNSAT ** |
| | |
| | |
| | 1) NOTE: PLEASE SEE PLANS SHALL BEAR THE CORRECT |
| | ADDRESS AND UNIT NUMBER(S) ON TITLE BLOCKS ONCE ALL ARE |
| | CLEARED FROM THE ADDRESSING REVIEWER. |
| | PLEASE ALSO KNOW THAT IS HAS COME TO OUR ATTENTION THAT |
| | THE BUILDING POSSIBLY NOW HAS A CONDOMINIUM ASSESSMENT |
| | WHICH IN TURN MAY REQUIRE A UNITY OF TITLE. |
| | PLEASE SEE PLANS MENTIONS 106, ADDRESS IS 120 AND THE |
| | PERMIT APPLICATION IS |
| | PLEASE ALSO SEE POSSIBLE BUILDING REVIEW COMMENTS. |
| | |
| | 2) NOTE: PLEASE SEE PLANS SHALL REFERENCE ALL CODES |
| | WHICH ARE CURRENTLY RELEVANT TO THE DESIGN OF SAID |
| | PLANS AND WHICH SHALL ALSO BE STATED ON PLANS. PLEASE |
| | KNOW THAT AS OF OCT 1ST, 2005 THE STATE OF FLORIDA |
| | ADOPTED THE 2004 FBC, HOWEVER THE PLANS STATE THE 2001 |
| | FBC. PLEASE ALSO KNOW THAT AS OF DEC 8TH, 2006 THE |
| | STATE OF FLORIDA HAS NOW ADOPTED THE 2006 REVISIONS TO |
| | THE FLORIDA BUILDING CODE AND THE 2005 NEC, NFPA-70. |
| | PLEASE BE SURE TO SEE ALL OF THESE NEW SECTIONS WHICH |
| | ARE RELEVANT TO THE DESIGNS FOR THE SCOPE OF WORK BEING |
| | SHOWN AND PROPOSED. |
| | PLEASE ALSO SEE THAT THE FOLLOWING SHALL BE STATED ON |
| | THE PLANS AT A MINIMUM. |
| | 2004 FBC W/2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | PLEASE SEE MANY ITEMS BELOW ARE FROM THESE CODES AS |
| | REFERENCED. |
| | |
| | 3) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF |
| | WORK SHALL INCLUDE ALL LABOR AND MATERIALS. PLEASE ALSO |
| | SEE BUILDING REVIEW COMMENTS AS BASED ON THE SCOPE OF |
| | WORK SHOWN THE APPLIED VALUE IS LOW. |
| | FBC 108.3 |
| | |
| | 4) NOTE: PLEASE CLARIFY IF THERE IS AN EQUIPMENT ROOM |
| | FOR ELEVATOR EQUIPMENT. PLEASE ALSO SEE 620.22, 23 AND |
| | 24. |
| | IF THERE IS AN EQUIPMENT ROOM AND EMERGENCY BATTERY |
| | BACK UP LIGHT OF SOME KIND WILL BE REQUIRED. |
| | LS 101 7.8, 700.16 ETC |
| | |
| | 5) NOTE:PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE SEE DUE TO THE SCOPE OF WORK FOR CREATING THIS |
| | ONE NEW TENANT BUILD OUT SPACE AUTOMATED LIGHTING |
| | CONTROLS WILL BE REQUIRED. PLEASE SUBMIT SCHEDULING. |
| | PLEASE SEE IF INSTALLING A SYSTEM TO SEE REQUIREMENTS |
| | FOR MULTIPLE FLOORS. PLEASE SEE THAT IF USING ALL |
| | OCCUPANCY SENSOR TYPE DEVICES PLEASE STATE THE MAXIMUM |
| | TIMES, OR MAXIMUM TIMES ON ANY OVER RIDE DEVICES. |
| | PLEASE ALSO SEE 13-415.1.AB.1 AND 13-415.2.ABC.1 AND |
| | TABLES FOR USE ETC. |
| | |
| | 6) NOTE: PLEASE PROVIDE PHOTO-METRICS FOR STAIRS. |
| | PLEASE SEE 7.8.1.3, AND 7.9.2.2 WHICH REQUIRES A |
| | MINIMUM OF 10FT CANDLES UNDER NORMAL AND 1FT CANDLE |
| | UNDER EMERGENCY. |
| | PLEASE SEE CONTROLS FOR LIGHTING SHALL ALSO BE |
| | INDICATED, AND ANY OVER RIDES DEVICES OR NIGHT LIGHTS. |
| | |
| | 7) NOTE: PLEASE SEE DOOR SWING AT THE BOTTOM OF THE NEW |
| | PROPOSED STAIRS MAY VERY WELL BE AN ISSUE WITH THE |
| | BUILDING AND FIRE REVIEW WHICH SEEMS TO IMPEDE WITH THE |
| | DIRECT PATH OF EGRESS FROM STAIRS. |
| | PLEASE SEE SECTIONS WHICH WILL BE STATED FROM OTHER |
| | REVIEWER(S). LS101 AND THE FBC |
| | |
| | 8) NOTE: PLEASE INDICATE AND COMPLETE LOAD |
| | CALCULATIONS. THE INFORMATION AS SHOWN ON THE EXISTING |
| | AC-7 PANEL DOES NOT PROVIDE. |
| | PLEASE ALSO INCLUDE WHERE THIS PANEL IS BEING FED FROM. |
| | AS THIS BUILDING HAS BECOME A NEW "CONDO" PLEASE SHOW |
| | HOW THIS LEGAL OWNED UNIT HAS ITS OWN METER, MAIN |
| | DISCONNECT ETC. |
| | PANEL ONLY SHOWS THE NEW LOAD FOR THE NEW PANEL. LOAD |
| | ON THE EXISTING MDP AND NEW LOAD ADDED ETC. |
| | PLEASE KNOW AT THIS TIME REVIEW FOR MANY ITEMS FOR CODE |
| | COMPLIANCE CAN NOT BE DONE. |
| | 220.3, 220.10, 220.11, 220.13, ALL CONTINUOUS AND |
| | LARGEST MOTOR LOADS SHALL BE SHOWN AT THE REQUIRED |
| | 125%.215.3, 230.42 ETC. |
| | FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION. |
| | |
| | 9) NOTE: PLEASE SEE FBC 2004 11-4.28.2, .3(4) FOR |
| | MINIMUM LEVELS FOR STROBES AND DB LEVELS ON HORN |
| | DEVICES. |
| | PLEASE SEE 75MIN CD ETC SHALL BE SHOWN ON PLANS FOR |
| | DEVICES BEING CONNECTED INTO ANY BUILDING FIRE ALARM |
| | SYSTEM. |
| | PLEASE KNOW THE BASED BUILD OUT WILL BE REQUIRED TO |
| | SHOW ANY FIRE SPRINKLER AND BASE FIRE ALARM DEVICES, |
| | EVEN THOUGH SEPARATE PERMITS, PLANS ARE REQUIRED FOR |
| | THESE ITEMS. |
| | PLEASE SEE NFPA-72, NFPA-1, AND FBC ADMIN SECTION |
| | 106.3.5.1.1 |
| | ** PLEASE SEE FIRE MARSHAL'S REVIEW COMMENT(S). |
| | |
| | 10) NOTE: PLEASE SEE SOME SHEETS WHICH ARE NOT |
| | ELECTRICAL CONTAIN WHITE OUT. PLEASE KNOW THAT WHITE |
| | OUT AND HAND WRITTEN CHANGES IS NOT PERMITTED ON ANY |
| | PLANS, WHETHER OR NOT THEY ARE SIGNED, DATED AND SEALED |
| | BY AN ARCHITECT/ ENGINEER/CONTRACTORETC. |
| | FS 471, 481, FAC 61G15-23,61G1-16 FBC ADMIN SECTION |
| | 106.1.2, 106.1.3, ETC. |
| | |
| | 11) NOTE: PLEASE SHOW ALL EXISTING ELECTRICAL IN THE |
| | 7TH FLOOR AREA FOR ELECTRICAL. PLEASE KNOW THE LIGHTING |
| | WILL BE REQUIRED TO MEET CHAPTER 13 OF THE FBC FOR |
| | CONTROLS AND PERFORMANCE CALCULATIONS AS THIS SPACE IS |
| | BEING INCLUDED INTO THE NEW SINGLE TENANT. |
| | |
| | 12) NOTE: PLEASE SEE RISER AND PANEL SCHEDULE FOR NEW |
| | PANEL INDICATES THIS PANEL BEING A 100AMP PANEL AND YET |
| | 42 CIRCUITS? PLEASE VERIFY THIS AS IS IT NOT KNOWN THAT |
| | A 100A PANEL IS AVAILABLE IN 42 CIRCUITS. |
| | PLEASE REVISE AND ADJUST AS NEEDED. |
| | FBC 106.1.2 |
| | |
| | 13) NOTE: PLEASE SEE MISSING THE CERTIFICATE OF |
| | AUTHORIZATION NUMBER FOR THE ENGINEERING FIRM FOR THE |
| | "S" SHEETS. FAC 61G15-23.002 FS 471.023 THIS IS |
| | REQUIRED WHETHER OR NOT COMMENT IS MADE BY THE OTHER |
| | TRADE(S). |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-01-05 06:57:25 | 2007-01-05 06:57:25 |
| | NOTES IN PROGRESS |
| 2007-01-03 07:49:19 | IN ELEC FOR REVIEW |