Plan Review Notes
Plan Review Notes For Permit 06120362
Permit Number 06120362
Review Stop E
Sequence Number 1
Notes
Date Text
2007-01-05 07:39:51** UNSAT **
  
  
 1) NOTE: PLEASE SEE PLANS SHALL BEAR THE CORRECT
 ADDRESS AND UNIT NUMBER(S) ON TITLE BLOCKS ONCE ALL ARE
 CLEARED FROM THE ADDRESSING REVIEWER.
 PLEASE ALSO KNOW THAT IS HAS COME TO OUR ATTENTION THAT
 THE BUILDING POSSIBLY NOW HAS A CONDOMINIUM ASSESSMENT
 WHICH IN TURN MAY REQUIRE A UNITY OF TITLE.
 PLEASE SEE PLANS MENTIONS 106, ADDRESS IS 120 AND THE
 PERMIT APPLICATION IS
 PLEASE ALSO SEE POSSIBLE BUILDING REVIEW COMMENTS.
  
 2) NOTE: PLEASE SEE PLANS SHALL REFERENCE ALL CODES
 WHICH ARE CURRENTLY RELEVANT TO THE DESIGN OF SAID
 PLANS AND WHICH SHALL ALSO BE STATED ON PLANS. PLEASE
 KNOW THAT AS OF OCT 1ST, 2005 THE STATE OF FLORIDA
 ADOPTED THE 2004 FBC, HOWEVER THE PLANS STATE THE 2001
 FBC. PLEASE ALSO KNOW THAT AS OF DEC 8TH, 2006 THE
 STATE OF FLORIDA HAS NOW ADOPTED THE 2006 REVISIONS TO
 THE FLORIDA BUILDING CODE AND THE 2005 NEC, NFPA-70.
 PLEASE BE SURE TO SEE ALL OF THESE NEW SECTIONS WHICH
 ARE RELEVANT TO THE DESIGNS FOR THE SCOPE OF WORK BEING
 SHOWN AND PROPOSED.
 PLEASE ALSO SEE THAT THE FOLLOWING SHALL BE STATED ON
 THE PLANS AT A MINIMUM.
 2004 FBC W/2006 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
 PLEASE SEE MANY ITEMS BELOW ARE FROM THESE CODES AS
 REFERENCED.
  
 3) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF
 WORK SHALL INCLUDE ALL LABOR AND MATERIALS. PLEASE ALSO
 SEE BUILDING REVIEW COMMENTS AS BASED ON THE SCOPE OF
 WORK SHOWN THE APPLIED VALUE IS LOW.
 FBC 108.3
  
 4) NOTE: PLEASE CLARIFY IF THERE IS AN EQUIPMENT ROOM
 FOR ELEVATOR EQUIPMENT. PLEASE ALSO SEE 620.22, 23 AND
 24.
 IF THERE IS AN EQUIPMENT ROOM AND EMERGENCY BATTERY
 BACK UP LIGHT OF SOME KIND WILL BE REQUIRED.
 LS 101 7.8, 700.16 ETC
  
 5) NOTE:PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE DUE TO THE SCOPE OF WORK FOR CREATING THIS
 ONE NEW TENANT BUILD OUT SPACE AUTOMATED LIGHTING
 CONTROLS WILL BE REQUIRED. PLEASE SUBMIT SCHEDULING.
 PLEASE SEE IF INSTALLING A SYSTEM TO SEE REQUIREMENTS
 FOR MULTIPLE FLOORS. PLEASE SEE THAT IF USING ALL
 OCCUPANCY SENSOR TYPE DEVICES PLEASE STATE THE MAXIMUM
 TIMES, OR MAXIMUM TIMES ON ANY OVER RIDE DEVICES.
 PLEASE ALSO SEE 13-415.1.AB.1 AND 13-415.2.ABC.1 AND
 TABLES FOR USE ETC.
  
 6) NOTE: PLEASE PROVIDE PHOTO-METRICS FOR STAIRS.
 PLEASE SEE 7.8.1.3, AND 7.9.2.2 WHICH REQUIRES A
 MINIMUM OF 10FT CANDLES UNDER NORMAL AND 1FT CANDLE
 UNDER EMERGENCY.
 PLEASE SEE CONTROLS FOR LIGHTING SHALL ALSO BE
 INDICATED, AND ANY OVER RIDES DEVICES OR NIGHT LIGHTS.
  
 7) NOTE: PLEASE SEE DOOR SWING AT THE BOTTOM OF THE NEW
 PROPOSED STAIRS MAY VERY WELL BE AN ISSUE WITH THE
 BUILDING AND FIRE REVIEW WHICH SEEMS TO IMPEDE WITH THE
 DIRECT PATH OF EGRESS FROM STAIRS.
 PLEASE SEE SECTIONS WHICH WILL BE STATED FROM OTHER
 REVIEWER(S). LS101 AND THE FBC
  
 8) NOTE: PLEASE INDICATE AND COMPLETE LOAD
 CALCULATIONS. THE INFORMATION AS SHOWN ON THE EXISTING
 AC-7 PANEL DOES NOT PROVIDE.
 PLEASE ALSO INCLUDE WHERE THIS PANEL IS BEING FED FROM.
 AS THIS BUILDING HAS BECOME A NEW "CONDO" PLEASE SHOW
 HOW THIS LEGAL OWNED UNIT HAS ITS OWN METER, MAIN
 DISCONNECT ETC.
 PANEL ONLY SHOWS THE NEW LOAD FOR THE NEW PANEL. LOAD
 ON THE EXISTING MDP AND NEW LOAD ADDED ETC.
 PLEASE KNOW AT THIS TIME REVIEW FOR MANY ITEMS FOR CODE
 COMPLIANCE CAN NOT BE DONE.
 220.3, 220.10, 220.11, 220.13, ALL CONTINUOUS AND
 LARGEST MOTOR LOADS SHALL BE SHOWN AT THE REQUIRED
 125%.215.3, 230.42 ETC.
 FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION.
  
 9) NOTE: PLEASE SEE FBC 2004 11-4.28.2, .3(4) FOR
 MINIMUM LEVELS FOR STROBES AND DB LEVELS ON HORN
 DEVICES.
 PLEASE SEE 75MIN CD ETC SHALL BE SHOWN ON PLANS FOR
 DEVICES BEING CONNECTED INTO ANY BUILDING FIRE ALARM
 SYSTEM.
 PLEASE KNOW THE BASED BUILD OUT WILL BE REQUIRED TO
 SHOW ANY FIRE SPRINKLER AND BASE FIRE ALARM DEVICES,
 EVEN THOUGH SEPARATE PERMITS, PLANS ARE REQUIRED FOR
 THESE ITEMS.
 PLEASE SEE NFPA-72, NFPA-1, AND FBC ADMIN SECTION
 106.3.5.1.1
 ** PLEASE SEE FIRE MARSHAL'S REVIEW COMMENT(S).
  
 10) NOTE: PLEASE SEE SOME SHEETS WHICH ARE NOT
 ELECTRICAL CONTAIN WHITE OUT. PLEASE KNOW THAT WHITE
 OUT AND HAND WRITTEN CHANGES IS NOT PERMITTED ON ANY
 PLANS, WHETHER OR NOT THEY ARE SIGNED, DATED AND SEALED
 BY AN ARCHITECT/ ENGINEER/CONTRACTORETC.
 FS 471, 481, FAC 61G15-23,61G1-16 FBC ADMIN SECTION
 106.1.2, 106.1.3, ETC.
  
 11) NOTE: PLEASE SHOW ALL EXISTING ELECTRICAL IN THE
 7TH FLOOR AREA FOR ELECTRICAL. PLEASE KNOW THE LIGHTING
 WILL BE REQUIRED TO MEET CHAPTER 13 OF THE FBC FOR
 CONTROLS AND PERFORMANCE CALCULATIONS AS THIS SPACE IS
 BEING INCLUDED INTO THE NEW SINGLE TENANT.
  
 12) NOTE: PLEASE SEE RISER AND PANEL SCHEDULE FOR NEW
 PANEL INDICATES THIS PANEL BEING A 100AMP PANEL AND YET
 42 CIRCUITS? PLEASE VERIFY THIS AS IS IT NOT KNOWN THAT
 A 100A PANEL IS AVAILABLE IN 42 CIRCUITS.
 PLEASE REVISE AND ADJUST AS NEEDED.
 FBC 106.1.2
  
 13) NOTE: PLEASE SEE MISSING THE CERTIFICATE OF
 AUTHORIZATION NUMBER FOR THE ENGINEERING FIRM FOR THE
 "S" SHEETS. FAC 61G15-23.002 FS 471.023 THIS IS
 REQUIRED WHETHER OR NOT COMMENT IS MADE BY THE OTHER
 TRADE(S).
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-01-05 06:57:252007-01-05 06:57:25
 NOTES IN PROGRESS
2007-01-03 07:49:19IN ELEC FOR REVIEW