| 2007-06-08 12:46:52 | |
| | ** UNSAT 3RD REVIEW** |
| | |
| | ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEWS ALONG |
| | WITH A NEW NOTE BASED ON REVISED NOTES ON PLANS NEED TO |
| | BE ADDRESSED. |
| | |
| | 1) NOTE:PLEASE SEE PREVIOUS NOTES WHICH REQUESTED THE |
| | MINIMUM LEVELS FOR FBC ADA LEVELS TO BE STATED ON |
| | PLANS. AS NOTED PREVIOUSLY THIS COULD BE SHOWN ON PLANS |
| | AND LEGEND. IT IS KNOWN THESE FIRE ALARM AND ANY FIRE |
| | SPRINKLERS WILL BE UNDER SEPARATE PERMITS, HOWEVER THE |
| | BASE PLANS ARE REQUIRED TO SHOW THE *MINIMUM* |
| | REQUIREMENTS FOR THIS. |
| | PLEASE SEE 11-4.28.1 FOR LOCATIONS, 11-4.28.2 AND .3(4) |
| | FOR LEVELS. |
| | |
| | 2) NOTE: PLEASE SEE THE PREVIOUS SUBMITTED ENERGY |
| | CALCULATIONS HAD COMMENTS AS THEY NEEDED SOME |
| | COORDINATION WITH PLANS, HOWEVER THIS SUBMITTED PACKAGE |
| | DOES NOT CONTAIN ANY SUBMITTED ENERGY CALCULATIONS FOR |
| | REVIEW OF METHOD, COORDINATION ETC AS REQUIRED PER FBC |
| | 13-415.AB.1.1. |
| | PLEASE KNOW AS THESE WERE NOT SUBMITTED, NO REVIEW OF |
| | THESE ITEMS CAN BE DONE. |
| | |
| | 3) NOTE: PLEASE SEE THE REVISED NOTES ON E-1 NOW STATES |
| | IN *SPECIAL ENERGY EFFICIENT NOTES* , NOTE #5 THAT ALL |
| | INTERIOR LIGHTING IS GOING TO MEET 13-415.1.ABC.1.1, |
| | HOWEVER THE PLANS DO NOT SHOW THIS. THERE IS NOT SUCH |
| | DEVICES ON PLANS, NO CONTROLS, NO SCHEDULING, NO OVER |
| | RIDE TIMES ETC. |
| | PLEASE SEE CHAPTER 13 THIS SECTION AS STATED AND SEE |
| | PREVIOUS SUBMITTED PLANS FOR THIS SAME ITEM. |
| | |
| | ** EVEN IF PLANS ARE STAMPED BY THE STATE, IF THE PLANS |
| | DO NOT CORRELATE FOR CODE COMPLIANCE THEY CAN NOT BE |
| | ISSUED AND STAMPED. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |