| 2007-04-16 15:28:03 | 2007-04-16 15:28:03 |
| | *** NOTES ADDED. |
| | |
| | 1) NOTE; PLEASE SEE NOTE #1 FROM REVIEW DATED 3/31/07 |
| | HAS BEEN REMOVED AS THE ES-1 SHEET WAS LOCATED IN WITH |
| | THE CIVIL SHEETS. |
| | PLEASE BE SURE TO INSERT THE ES-1 SHEETS IN WITH THE |
| | ELECTRICAL PLANS. PLEASE SUBMIT STRUCTRUAL DETAIL FOR |
| | NEW CEILING HUNG TRANSFORMER. |
| | PLEASE CALRIFY THAT THE TRANSFORMER WILL NOT BE ABOVE |
| | ANY SUSPENDED CEILING ETC PER 450.13 |
| 2007-03-31 12:03:15 | |
| | |
| | *** UNSAT 2ND REVIEW ** |
| | |
| | ** PLEASE SEE SOME COMMENTS FORM PREVIOUS REVIEW ARE |
| | STILL IN NEED OF ADDRESSING AND SOME NEW COMMENTS BASED |
| | ON CHANGES ON PLANS. |
| | |
| | |
| | 1) NOTE: |
| | |
| | 2) NOTE: PLEASE SEE THE ENERGY CALCULATIONS DO NOT |
| | CORRELATE WITH THE ELECTRICAL PLANS SUBMITTED OR THE |
| | FIXTURES AS STATED ON LEGEND, WATTAGE ON FIXTURES, THE |
| | AMOUNT OF FIXTURES ETC. |
| | PLEASE COORDINATE THE USE, LIGHTING POWER DENSITIES AND |
| | METHOD OF CALCULATIONS BEING USED. |
| | PLEASE SEE THE INPUT DATA REPORT. |
| | PLEASE CLARIFY WHY PLANS CONTAIN NOTES FOR LIGHTING |
| | CONTROLS REQUIRED IF THE BUILDING IS OVER 5K SQ FT. IF |
| | THE BUILDING WHICH IS BEING SHOWN IS UNDER THE 5K, |
| | PLEASE DO NOT REFERENCE THESE CODE REQUIREMENTS UNLESS |
| | IT IS THE INTENTION AND DESIGN TO PROVIDE LIGHTING |
| | ENERGY EFFICIENT CONTROLS FOR AUTO-MATED SHUT OF |
| | LIGHTING. |
| | PLEASE SEE 13-415.1AB.1.1, 13-415.2 |
| | PLEASE ALSO SEE 13-103.1.1.1 AS THE ENERGY CALCULATIONS |
| | SHALL BE SIGNED, DATED AND SEALED BY THE RESPONSIBLE |
| | DESIGNERS. |
| | PLEASE SEE THE CALCULATIONS SUBMITTED ARE PHOTOCOPIES |
| | OF SIGNED SHEETS. |
| | |
| | 3) NOTE: PLEASE SEE THAT THE CODE SECTION REFLECTED FOR |
| | WIRING OF EMERGENCY/EXIT LIGHTS SHOULD BE 700.12E. |
| | PLEASE SEE THIS SEEMS TO HAVE BEEN A MISPRINT AND WOULD |
| | HAVE BEEN REDLINED IF THE PLANS WERE NOT COMING BACK |
| | FOR OTHER COMMENTS. |
| | PREVIOUS REVIEW NOTE: |
| | |
| | 4) NOTE: PLEASE SEE THAT MINIMUM STROBES AND HORN |
| | LEVELS SHALL BE STATED ON PLANS FOR FBC 11-4.28.2, |
| | .3(4). |
| | THIS COMMENT WAS MADE ON PREVIOUS REVIEW AND NOT |
| | MINIMUM LEVELS ARE STATED FOR ADA COMPLIANCE. THIS CAN |
| | BE DONE ON THE SYMBOL LEGEND. |
| | ** PLEASE KNOW EVEN THOUGH THE FIRE ALARM WILL BE UNDER |
| | A SEPARATE PERMIT THIS IS REQUIRED ON THE PLANS AT THIS |
| | TIME. |
| | ** PLEASE ALSO KNOW THE SECURITY SYSTEM AS SHOWN WILL |
| | ALSO BE UNDER A SEPARATE PERMIT. |
| | |
| | 5) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS IF |
| | THE SERVICE AS SHOWN IS BEING FED FROM AN EXISTING |
| | SERVICE. |
| | 220, 215.3, 230.42 |
| | PLEASE ALSO SEE THAT ALL CONTINUOUS LOADS SHALL BE |
| | SHOWN AT 125%. 215.3 AND 230.42. |
| | |
| | 6) NOTE: PLEASE SEE *F*,*S* AND *WM* SHEETS CONTAIN A |
| | RAISED SEAL OVER A PHOTO-COPIED SIGNATURE FOR THE |
| | ENGINEER * MR. ALBERT KWAN*. THIS HAS BEEN DONE ON A |
| | REPETITIVE BASIS BY THE SAID DESIGNER ON SEVERAL |
| | PROJECTS WHICH HAVE BEEN SUBMITTED TO THIS JURISDICTION |
| | AND ON SEVERAL OCCASIONS THE NOTES HAVE BEEN ISSUED TO |
| | THIS ENGINEER THAT AN *ORIGINAL SIGNATURE* IS REQUIRED |
| | UNDER FLORIDA STATUTES 471.025 AND FLORIDA |
| | ADMINISTRATIVE CODE 61G15-23.002. |
| | THE PREVIOUS SHEETS SUBMITTED WERE *PHOTO-COPIES* AND |
| | THE ONLY THING WHICH HAS CHANGED IS THE FACT THE |
| | PREVIOUS PLANS WITH THE PHOTO-COPIED SIGNATURE NOW HAS |
| | A RAISED SEAL OVER THE PHOTO-COPIED SIGNATURE. |
| | **PLEASE KNOW AT THIS TIME THESE SHEETS WILL BE |
| | RETAINED BY THIS OFFICE AND SENT TO THE FLORIDA BOARD |
| | OF PROFESSIONAL ENGINEERS FOR REVIEW. |
| | |
| | 7) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A |
| | NOTICE AT THIS TIME. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |