| Plan Review Notes For Permit 06120355 |
| Permit Number |
06120355 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-01-09 10:33:22 | *** DENIED *** | | | 1) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC | | | 13-101.1.1. | | | | | | 2) PLEASE SUBMIT DETAILED MANUFACTURER'S | | | SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR A/C | | | SYSTEMS, A/C EQUIPMENT LISTING IS CALLING FOR 10.5 SEER | | | EQUIPMENT BUT THE MINIMUM IS 13 SEER, PER 2004/ 06 REV. | | | FBC 13-607.1.ABC.3.2.1. | | | | | | 3) SEE PLANS PAGE M-1 A/C UNIT MOUNTING DETAIL, | | | CONDENSER DRAIN NEEDS TO DISCHARGE A MINIMUM OF 12" | | | FROM THE BUILDING, PER 2004 FBC 1503.6. | | | | | | 4) SEE PLANS PAGE M-1 RETURN AIR TRANSFER DUCTS, 10" | | | FROM ROOM 102 TO 103 NEEDS TO BE 14", 10" FROM ROOM 112 | | | TO 107 NEEDS TO BE 14", AND 10" FROM ROOM 107 TO 109 | | | NEEDS TO BE 18", | | | BALANCED RETURN AIR MAY BE ACHIEVED BY. | | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY | | | INCREASING THE RETURN TRANSFER ONE AND | | | ONE HALF TIMES THE CROSS SECTIONAL AREA | | | (SQUARE INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM OR SPACE IT'S SERVING | | | AND THE DOOR HAVING AT LEAST AN | | | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE | | | PROPER RETURN AIR BALANCE.. PER 2004 FBC/R M1602.4 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|