| 2007-02-08 12:08:16 | *****DENIED***** |
| | |
| | |
| | 1.THE COMPLETE AND/OR ACTUAL ADDRESS OF WHERE THE |
| | SCOPE OF WORK IS TO BE CONDUCTED SHALL BE IN THE TITLE |
| | BLOCK OF EACH SUBMITTED PLAN SHEET. |
| | |
| | 2.THE NFPA 101, 2003 EDITION AND THE FLORIDA FIRE |
| | PREVENTION CODE 2004 SHALL BE REFERENCED. |
| | |
| | 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, AND |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 4.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT |
| | INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO THE |
| | PROPERTY OR VICINITY THEREOF (INCLUDING FIRE LANES). |
| | |
| | 5.WHAT IS THE OCCUPANCY CLASSIFICATION FOR THIS |
| | STRUCTURE? |
| | |
| | 6.INDICATE THE NEAREST FIRE HYDRANT(S) IN THE |
| | VICINITY OF THE STRUCTURE.PLEASE BE ADVISED THAT IF |
| | THE DISTANCE IS GREATER THAN 500 FEET, AN ADDITIONAL |
| | HYDRANT MAY BE REQUIRED. |
| | |
| | 7.SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE EXTERIOR |
| | ELEVATION THAT FRONTS JEFFERSON ROAD.AS PER WEST PALM |
| | BEACH CODE, THE ADDRESS NUMBERS SHALL BE NO LESS THAN |
| | 6" IN HEIGHT NAND 1" IN WIDTH. |
| | |
| | 8.ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM AN AREA |
| | HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE |
| | PROVIDED WITH PANIC HARDWARE OR FIRE EXIT HARDWARE, |
| | UNLESS OTHERWISE THEY ARE DELAYED-EGRESS LOCKS OR |
| | ACCESS-CONTROLLED EGRESS LOCKS PERMITTED AND APPROVED |
| | BY THE AHJ. |
| | |
| | 9.SINCE THE STRUCTURE WILL HAVE A FIRE ALARM AND/OR |
| | FIRE SPRINKLER SYSTEM, A LAYOUT OF EACH OF THESE FIRE |
| | PROTECTION SYSTEMS WILL BE SUBMITTED FOR REVIEW. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. |
| | |
| | |