| 2007-07-31 18:37:51 | *** UNSAT 4TH REVIEW *** |
| | |
| | 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED |
| | DO NOT CORRELATE WITH THE PLANS FOR THE METHOD OF |
| | CONTROL. PLEASE SEE THESE ARE STILL BEING ENTERED AS |
| | *MANUAL ON/OFF* WHEN THEY ARE AUTOMATED/OCCUPANCY TYPE |
| | DEVICES ON PLANS. |
| | PLEASE COORDINATE. 13-415.1.AB.1.1, 13-415.1.A, |
| | 13-415.2. |
| | PLEASE CLARIFY METHOD AND HOW THIS CAN BE USED FOR |
| | SCOPE OF WORK AS SHOWN. PLEASE CLARIFY LIGHTING POWER |
| | DENSITIES AS REQUESTED ON THE PREVIOUS THREE REVIEWS. |
| | THE RESPONSE LETTER DOES NOT ADDRESS OR MENTION THESE |
| | ITEMS??? |
| | PLEASE SEE THESE ARE TO BE SIGNED BY THE ENGINEER OF |
| | RECORD WITH SIGNATURE AS ON FILE AND RECOGNIZED BY THIS |
| | OFFICE. PLEASE SEE THESE ARE NOT THE SAME AS THE PLANS |
| | OR PREVIOUS SUBMITTED ENERGY CALCULATIONS. |
| | 13-103.1.1.1, FS471.025 |
| | |
| | 2) NOTE: PLEASE SEE THE PLANS HAVE NOT CHANGED FOR THE |
| | LOCATIONS OF DISCONNECTS. PLEASE SEE THE TRANSFORMER |
| | T1A WHICH IS BEING SHOWN IN SOME KIND OF CLOSET. THIS |
| | SAME CLOSET CONTAINS TWO SMALL RECTANGLES WHICH ARE NOT |
| | LABELED AS DISCONNECTS. AS THESE COULD NOT BE LOCATED |
| | AT ANY OTHER LOCATION ON PLANS, IT IS BEING ASSUMED |
| | THESE ARE THE SAME DISCONNECTS IN THIS SAME *CLOSET*. |
| | PLEASE SEE THESE DO NOT MEET 110.26, 240.24, 408.7 ETC |
| | AS PREVIOUSLY STATED IN PREVIOUS REVIEWS. |
| | ** ALL SERVICE EQUIPMENT NEW OR EXISTING WILL BE |
| | REQUIRED TO MEET THE MINIMUM REQUIRED BY CODE** |
| | |
| | **DOCUMENTATION HAS BEEN SENT TO THE CHIEF ELECTRICAL |
| | INSPECTOR FOR FIELD INSPECTION AND CORRECTION NOTICED |
| | TO BE ISSUED TO OWNER/JOBSITE AS/IF NEEDED. |
| | |
| | 3) NOTE: PLANS AND SUPPORTING DOCUMENTS ARE BEING |
| | RETAINED BY THIS OFFICE DUE TO REPEAT CODE COMPLIANT |
| | COMMENTS PER FS 553.80(2)(B). AT THIS TIME A FEE OF |
| | $9,732.00 MAY BE ASSESSED DUE TO THE REPEAT COMMENTS |
| | FOR CODE COMPLIANCE. THE CODE COMMENTS WILL GO UNDER |
| | PIER REVIEW. |
| | THE FEE IS REQUIRED UNDER FLORIDA STATUTESAND WILL BE |
| | DUE BEFORE NEXT RESUB OF PLANS MAY BE DONE. |
| | |