| 2007-03-19 08:07:29 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | FROM PREVIOUS REVIEW: |
| | (COMMENT NUMBERS TO REMAIN THE SAME) |
| | |
| | 1. OK |
| | 2. OK |
| | |
| | 3. ALL ARCHITECTURAL SHEETS. THE TITLE BLOCK MUST, AT A |
| | MINIMUM, CONTAIN THE FOLLOWING:THE FIRM LICENSE |
| | NUMBER & THE PRINTED NAME OF THE PERSON SEALING THE |
| | DOCUMENT. FAC 61G1-16.004(2)(6) & FS 481.219, |
| | 481.2055. |
| | ****NO RESPONSE, THE PRINTED NAME HAS BEEN INDICATED, |
| | BUT THE CA# AS INDICATED ON THE PLANS IS SHOWN AS |
| | ANOTHER BUSINESS NAME IN THE STATE DBPR WEBSITE. SEE |
| | ATTACHED SHEET. |
| | |
| | 4. OK |
| | 5. OK |
| | |
| | 6. SHTS A1.04 & A7.041 DETAIL 1. THE BREAK ROOMSINK |
| | SHALL COMPLY WITH SECTION 11-4.24 AND ALL SUBSECTIONS. |
| | SHOW THE FOLLOWING: |
| | A. OK |
| | B. 11-4.24.4 SINK DEPTH |
| | C. 11-4.24.5 CLEAR FLOOR SPACE. FORWARD APPROACH |
| | EXTENDING A MAXIMUM 19" UNDERNEATH THE SINK IS |
| | REQUIRED. CABINET DOORS ARE NOT APPROVED. |
| | D. 11-4.24.6 EXPOSED PIPES & SURFACES |
| | E. 11-4.24.7 FAUCETS |
| | ****NO RESPONSE, THE SINK DEPTH IS NOT SHOWN. THE |
| | CABINET DOORS ARE STILL SHOWN ON ELEVATION 1 SHT |
| | A-7.041. EXPOSED PIPES & SURFACES NOT ADDRESSED. |
| | INDICATE FAUCET TYPE. (INDICATING ADA COMPLIANT FAUCET |
| | IS NOT ENOUTH INFORMATION). |
| | |
| | 7. SHOW THE FIXTURES REQUIRED BY SECTION 1004.1.3 |
| | (BLDG) & 403.1 MINIMUM FACILITIES. INDICATE ON THE |
| | FLOOR PLAN THE DRINKING FOUNTAINS. SECTION 106.1.1. |
| | ****NO RESPONSE. NOT ADDRESSED. |
| | |