| Date |
Text |
| 2007-03-11 10:10:08 | ** UNSAT 2ND REVIEW ** |
| | |
| | |
| | |
| | 222 LAKEVIEW |
| | 4THFLOOR BUILD-OUT/REMODEL\ |
| | |
| | ** PLEASE SEE SOME COMMENTS ARE THE SAME AND SOME ARE |
| | NEW DUE TO CHANGES IN PLANS. |
| | |
| | |
| | 1) NOTE: PLEASE SEE MISSING COMPLETE INFORMATION FOR A |
| | TITLE BLOCK FOR THE ARCHITECT OF RECORD AND FIRM. |
| | PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION NUMBER |
| | ALSO KNOW AS FIRM LICENSE NUMBER. |
| | PLEASE SEE MISSING THE PRINTED NAME AND LICENSE NUMBER |
| | FOR ARCHITECT. |
| | FLORIDA ADMINISTRATIVE CODE 61G1-16.004, FLORIDA |
| | STATUTES 481.219 |
| | **THIS IS NOT A COMMENT RELATED TO KAMM CONSULTING, |
| | HOWEVER TITLE BLOCKS ARE REQUIRED FOR ALL SHEETS PER |
| | ABOVE AND WHETHER OR NOT COMMENT IS MADE BY ANY OTHER |
| | TRADE. |
| | |
| | 2) NOTE: PERMIT APPLICATION HAS NOT BEEN ADJUSTED. |
| | PLEASE CLARIFY PERMIT APPLICATION HAS APPLIED FOR NEW |
| | TENANT BUILD OUT, HOWEVER PLANS DO NOT CORRELATE WITH |
| | THIS. |
| | |
| | 3) NOTE:PLEASE KNOW ANY NEW ROOM LIGHTING AND |
| | CONTROLS SHALL COMPLY WITH THIS SECTION. 13-415. |
| | PLEASE KNOW THE ENTIRE FLOOR DOES NOT HAVE BE BROUGHT |
| | UP TO CURRENT CODES, HOWEVER THE NEW ROOMS/LIGHTS AND |
| | CONTROLS WILL BE REQUIRED. THIS CAN BE DONE BY SINGLE |
| | DEVICES IN THESE ROOMS/AREAS. |
| | PLEASE ALSO KNOW THAT THE LIGHTING POWER DENSITIES FOR |
| | EACH OF THE NEW ROOMS SHALL COMPLY WITH THE MAXIMUM |
| | LIGHTING AS PERMITTED IN THE TABLES. PLEASE SEE MISSING |
| | LIGHTING CONTROL FOR ALL PER 13-415.1.ABC.1.1, .1.2, |
| | AND .1.3.NEW AREAS AND ROOMS. PLEASE SEE OVER RIDES |
| | DEVICES FOR THESE AREAS ALSO DEPENDING ON IF"SYSTEM" |
| | OR "DEVICES" ARECHOSEN. |
| | PLEASE SEE THE SYMBOL LEGEND FOR ALL DEVICES SHALL |
| | INDICATE ALL MAXIMUM TIMES FOR DEVICES. (30MINS FOR |
| | OCCUPANCY SENSOR TYPE AND 4HRS MAX FOR TIMER TYPE) |
| | PLEASE SEE ROOMS AND AREAS WHICH DO NOT INDICATE ANY OF |
| | THE DEVICES FOR AUTOMATED CONTROL. |
| | PLEASE SEE ALL AREAS CONTAIN FLOOR TO CEILING HEIGHT |
| | PARTITIONS SHALL CONTAIN DEVICE(S) FOR CONTROL. (PLEASE |
| | SEE STORAGE) |
| | PLEASE SEE 13-415.2, 13-415.2.ABC.1 FOR MISSING MAXIMUM |
| | PERMITTED LIGHTING POWER DENSITIES. |
| | |
| | 4) NOTE: PLEASE PLACE A NOTE ON PLANS/SHEET E2.1 TO |
| | CLOSET AREA TO BE BROUGHT UP TO CODE FOR MINIMUM |
| | CLEARANCES AS STATED IN THE SECTIONS OF THE CODE NOTED |
| | BELOW. PLEASE KNOW THIS WILL BE A CONDITION OF ISSUANCE |
| | AND PLEASE KNOW NO ROUGH ELECTRICAL INSPECTIONS WILL BE |
| | DONE UNTIL REVISIONS OR SEPARATE PERMIT IS SUBMITTED |
| | FOR CHANGES.ONCE NOTE IS ON PLANS, A HOLD WILL BE |
| | PLACED ON INSPECTIONS. |
| | PLEASE SEE THE PANELSHV, LV1 AND LV2 WHICH DO NOT |
| | SEEM TO MEET 110.26 FOR PANEL HV AND TRANSFORMER. |
| | PLEASE VERIFY THIS AND KNOW THAT IF THIS WALL IS |
| | ACTUALLY INSTALLED IN FRONT OF THE PANEL/EQUIPMENT AS |
| | SHOWN, THIS WILL BE REQUIRED TO MEET 110.26/450.9, |
| | 450.13 ETC |
| | |
| | 5) NOTE: PLEASE SEE PLANS HAVE BEEN REVISED TO SHOW THE |
| | TRANSFORMER "T1A" DIRECTLY IN A CLOSET WHEN PREVIOUSLY |
| | SHOWN IN THE MIDDLE OF THE CONFERENCE ROOM. PLEASE SEE |
| | PANELS *L* AND L1* DO NOT SEEM TO MEET THE TAP |
| | CONDUCTOR RULE FOR DISTANCE IN THE LENGTH OF |
| | CONDUCTORS. PLEASE SEE 240.21C. |
| | PLEASE ALSO SEE MINIMUM CLEARANCES REQUIRED FOR |
| | TRANSFORMER. |
| | THIS IS A FIRE/LIFE SAFETY HAZARD. |
| | PLEASE ALSO VERIFY LOCATION FOR TAPS ON A TRANSFORMER |
| | PER 240.21C. PLEASE ADJUST PLANS AND VERIFY THE ACTUAL |
| | INSTALLATION. |
| | |
| | |
| | 13) NOTE:** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDEDSHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS.PLEASE KNOW ONLY |
| | ONE SET OF THE OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-03-10 18:53:06 | 2007-03-10 18:53:06 |
| | IN ELEC FOR REVIEW |