| Date |
Text |
| 2007-02-07 19:19:41 | *****DENIED***** |
| | |
| | |
| | 1.THE COMPLETE ADDRESS OF WHERE THE SCOPE OF WORK |
| | WILL BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH |
| | SUBMITTED PLAN SHEET. |
| | |
| | 2.ON SHEET A0.00, MAKE THE FOLLOWING CHANGES TO THE |
| | CODE ANALYSIS SECTION:I.AUTHORITIES CONSTRUCTION |
| | SERVICES DEPARTMENT - CITY OF WEST PALM BEACH |
| | 561-805-6700;FIRE MARSHAL - MIKE CARSILLO |
| | 561-804-4724II. APPLICABLE BUILDING CODES |
| | ELIMINATE NFPA 2003 CODES W/FLORIDA AMENDMENTS, INSERT |
| | FLORIDA FIRE PREVENTION CODE 2004 |
| | |
| | 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD |
| | TO GENERAL DEMOLITION NOTES, SHEET AD1.03 |
| | |
| | 4.DO THE TENANT ENTRY DOORS (AS REFERRED TO ON SHEET |
| | A9.032) LEAD TO AN EXIT ACCESS CORRIDOR?IF SO, THESE |
| | DOORS SHALL BE FIRE RATED AS PER NFPA 80. |
| | |
| | 5.ON SHEET FA0.1, FIRE ALARM NOTE #17, DELETE |
| | SUPERVISORY SIGNAL ONLY - INSERT GENERAL FIRE ALARM |
| | |
| | 6.PROVIDE A LAYOUT OF THE FIRE SPRINKLER SYSTEM. WILL |
| | THEY NEED TO BE ALTERED OR MODIFIED DUE TO THE SCOPE OF |
| | WORK? |
| | |
| | 7.BUILDINGS OR PORTIONS OF BUILDINGS SHALL BE |
| | PERMITTED TO BE OCCUPIED DURING CONSTRUCTION, REPAIR, |
| | ALTERATIONS, OR ADDITIONS ONLY WHERE REQUIRED MEANS OF |
| | EGRESS AND REQUIRED FIRE PROTECTION |
| | FEATURES ARE IN PLACE AND CONTINUOUSLY MAINTAINED FOR |
| | THE PORTION OCCUPIED OR WHERE ALTERNATIVE LIFE SAFETY |
| | MEASURES ACCEPTABLE TO THE AUTHORITY HAVING |
| | JURISDICTION ARE IN PLACE. |
| | |
| | 8.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF |
| | NEW BUILDING MATERIALS & SUPPLIES SHALL NOT HINDER OR |
| | INTERFERE WITH ACCESS TO OR EXIT FROM FLOOR AND/OR |
| | BUILDING (INCLUDING FIRE LANES). |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |