Plan Review Notes
Plan Review Notes For Permit 06120299
Permit Number 06120299
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-01-04 17:26:38*****DENIED*****
  
  
  
 1.THE COMPLETE ADDRESS (1701 SO. FLAGLER DRIVE) OF
 WHERE THE SCOPE OF WORK WILL BE CONDUCTED SHALL BE IN
 THE TITLE BLOCK OF THE PLAN SHEETS.
  
 2.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO THE
 SAID PROPERTY OR VICINITY THEREOF (INCLUDING FIRE
 LANES).
  
 3.WHAT IS THE WIDTH OF THE SERVICE ENTRANCE GATE WHEN
 OPENED?FIRE DEPARTMENT ACCESS SHALL HAVE AN
 UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FEET.
  
 4.A GATE ENTRY SYSTEM SHALL BE REQUIRED FOR EMERGENCY
 REPONSE ACCESS.CONTACT THE FIRE PREVENTION BUREAU AT
 561-804-4724 FOR AN APPLICATION.
  
 5.IN THE EVENT OF A POWER OUTAGE, HOW WILL THE
 SERVICE ENTRANCE BE AFFECTED?
  
 6.HOW DO PATRONS OF THE POOL AREA EXIT THE AREA WITH
 THE INSTALLED MAGNETIC KEYCARDSYSTEM?
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722