| Plan Review Notes For Permit 06120299 |
| Permit Number |
06120299 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-01-04 17:26:38 | *****DENIED***** | | | | | | | | | | | | 1.THE COMPLETE ADDRESS (1701 SO. FLAGLER DRIVE) OF | | | WHERE THE SCOPE OF WORK WILL BE CONDUCTED SHALL BE IN | | | THE TITLE BLOCK OF THE PLAN SHEETS. | | | | | | 2.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT | | | INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO THE | | | SAID PROPERTY OR VICINITY THEREOF (INCLUDING FIRE | | | LANES). | | | | | | 3.WHAT IS THE WIDTH OF THE SERVICE ENTRANCE GATE WHEN | | | OPENED?FIRE DEPARTMENT ACCESS SHALL HAVE AN | | | UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FEET. | | | | | | 4.A GATE ENTRY SYSTEM SHALL BE REQUIRED FOR EMERGENCY | | | REPONSE ACCESS.CONTACT THE FIRE PREVENTION BUREAU AT | | | 561-804-4724 FOR AN APPLICATION. | | | | | | 5.IN THE EVENT OF A POWER OUTAGE, HOW WILL THE | | | SERVICE ENTRANCE BE AFFECTED? | | | | | | 6.HOW DO PATRONS OF THE POOL AREA EXIT THE AREA WITH | | | THE INSTALLED MAGNETIC KEYCARDSYSTEM? | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, | | | INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH | | | ITEM WAS ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|