Plan Review Notes For Permit 06120246
Permit Number 06120246
Review Stop P
Sequence Number 1
Notes
Date Text
2007-01-03 09:20:32DENIED
 REFERENCE: FBC-2004 PLUMBING
  
 THE SUBMITTED PRINTS FOR PLUMBING ARE BEING RESUBMITTED
 FROM A PREVIOUS PLAN REVIEW FROM PERMIT #06040933 THAT
 WERE DENIED AND WERE NOT CORRECTED. THE FOLLOWING
 CORRECTIONS ARE STILL REQUIRED FOR PLUMBING PLAN REVIEW
 TO MEET CODE COMPLIANCE. PLEASE REFERENCE THE
 CORRECTIONS IN RED INK ON SHEET 5 FOR THE RESUBMITTAL:
  
 1. THE SANITARY ISOMETRIC RISER DIAGRAM DOESN'T
 REFLECT THE FLOOR PLAN. FLOOR PLAN ON SHEET 1 INDICATES
 A SHOWER, AND THE RISER DIAGRAM ON SHEET 5 INDICATES A
 TUB. ON THE RESUBMITTED DRAWINGS PLEASE CORRELATE IF
 THE FIXTURE IS GOING TO BE A TUB OR A SHOWER.
  
 2. ON SHEET 5 THE SANITARY RISER DIAGRAM INDICATES A
 3" TRAP FOR THE WATER CLOSET. THIS TRAP ISN'T REQUIRED
 BECAUSE THE WATER CLOSET HAS AN INTREGRAL TRAP. PER
 FBC-2004 PLUMBING, SECTION 1002.1 A FIXTURE SHALL NOT
 BE DOUBLE TRAPPED. PLEASE REMOVE THE TRAP FOR THE WATER
 CLOSET ON THE RESUBMITTAL.
  
 3. ON SHEET 5 SANITARY RISER DIAGRAM RUNNING TRAPS ARE
 INDICATED FOR THE LAV AND SHOWER OR TUB. RUNNING TRAPS
 ARE ILLEGAL PER FBC-2004 SECTION 1002.3. PLEASE REMOVE
 THE RUNING TRAPS FOR THE RESUBMITTAL.
  
 4. SHEET 5SANITARY RISER DIAGRAM, PER FBC-2004
 PLUMBING, SECTION708.3.4, A CLEANOUT SHALL BE
 PROVIDED AT THE BASE OF EACH WASTE OR SOIL STACK.
  
 **********IMPORTANT INFORMATION**********
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  