Plan Review Notes
Plan Review Notes For Permit 06120209
Permit Number 06120209
Review Stop M
Sequence Number 6
Notes
Date Text
2008-08-04 13:58:53PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLAN.
 *** DENIED ***
  
 1) THE COOLING LOAD CALCULATIONS ON FILE ARE CALLING
 FOR 20,232 TOTAL COOLING BTU'S, THE REVISED MECHANICAL
 PLAN EQUIPMENT SCHEDULE SHOWS 29,200 TOTAL COOLING
 BTU'S, THE PLANS CAN ONLY CALL FOR 15% MORE TOTAL
 COOLING BTU'S THAN THE COOLING LOAD CALCULATIONS, PER
 2004 FBC 13-607.1.ABC.1.1. A 2.5 TON A/C SYSTEM IS TO
 LARGE PER THE COOLING LOAD CAL'S. PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]