| 2007-11-28 11:21:51 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST |
| | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) INFORMATION ON MECHANICAL PLAN SHOW TOTAL COOLING AT |
| | 22,600 BTU'S FOR THIS 2.5 TON SYSTEM IS INCORRECT. SEE |
| | ATTACHED ARI CERTIFICATE FOR THAT SYSTEM SHOWS THE |
| | TOTAL COOLING IS 27,200 BTU'S. AS NOTED IN LAST REVIEW |
| | 11-13-07 NOTE #1. THE COOLING LOAD CALCULATIONS ARE |
| | CALLING FOR 20,232 TOTAL BTU'S AND THE CORRECT TOTAL |
| | BTU,S FOR THE SYSTEM LISTED ON THE MECHANICAL PLAN IS |
| | 27,200 (SEE ATTACHED ARI LISTING). THE MECHANICAL PLANS |
| | CAN ONLY CALL FOR 15% MORE TOTAL BTU'S THAN THE COOLING |
| | LOAD CAL'S, SEE FBC 13-607.1.ABC.1.1. PLEASE CORRECT. |
| | |
| | 2) TWO DIFFERENT SIZE MECHANICAL PLANS WERE SUBMITTED, |
| | PLEASE INDICATE WHICH PLAN IS FOR REFERENCE AND NOT TO |
| | BE USED. |
| | |
| | 3) BE ADVISED ONE COPY OF THE COOLING LOAD |
| | CALCULATIONS, ENERGY CAL'S. AND MECHANICAL PLANS HAVE |
| | BEEN RETAINED FOR OUR RECORDS, PLEASE PROVIDE TWO |
| | COPIES WHEN RE-SUBMITTING. |
| | |
| | 4) SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING FOUR |
| | TIMES THE FEE. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729 |
| | E-MAIL; [email protected] |