2007-11-13 09:09:36PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE COOLING LOAD CALCULATIONS ARE CALLING FOR 20,232
 TOTAL BTU'S AND THE TOTAL BTU,S LISTED ON THE
 MECHANICAL PLAN IS 27,200 (SEE ATTACHED ARI LISTING).
 THE MECHANICAL PLANS CAN ONLY CALL FOR 15% MORE TOTAL
 BTU'S THAN THE COOLING LOAD CAL'S, SEE FBC
 13-607.1.ABC.1.1. PLEASE CORRECT.
  
 2) THE MECHANICAL PLANS NEED THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN, AND
 CONTRACTOR INFORMATION IF APPLICABLE ON THEM, SEE
 W.P.B. AMEND. 106.1.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]