| Notes |
| Date |
Text |
| 2007-11-15 15:48:47 | BUILDING PLAN REVIEW | | | PERMIT:06120209 | | | ADD:1325 9TH STREET | | | CONT:JUSTINA A. MCCRAY | | | TEL: (561)805-7255 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW 3RD | | | ACTION: DENIED | | | | | | 1)OK | | | 2)OK | | | 3)OK | | | 4)OK | | | 5)OK | | | | | | 6)NOTED: INDICATE WHICH ITEMS OR SYSTEMS WILL BE USED | | | FROM EACH PRODUCT APPROVAL, INCLUDING THE FASTENER | | | SPACING OR THE STORM PANELS. | | | | | | 7)OK | | | 8)OK | | | 9)OK | | | 10)OK | | | 11) OK | | | | | | NEW*************** | | | | | | 12)R802.1.6TRUSS DESIGN DRAWINGS PREPARED IN | | | CONFORMANCE WITH SEC. R802.1.6.1 SHALL BE PROVIDED TO | | | THE BUILDING OFFICIAL AND APPROVED PRIOR TO | | | INSTALLATION. | | | | | | A) INDICATE THE TYPE OF INSULATION AT THE EXTERIOR | | | WALLS. THE DRAWINGS SHOW R-19 INSULATION FOR THE ATTIC | | | AND THE ENERGY CALCULATIONS SHOW R-30 WHIC IS IT? | | | CLARIFY. | | | B)THE DRAWINGS CALL FOR 2500PSI CONCRETE FOOTINGS AND | | | THE SOIL REPORT CALLS FOR 200PSI. CLARIFY. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 | | | | | | |
|