| Plan Review Notes For Permit 06120209 |
| Permit Number |
06120209 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-07-03 08:20:08 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} THE DISCONNECT LOCATION ON THE RISER IS INCORRECT AN | | | DISCONNECTS NOTHING. PLEASE REDRAW AND INDICATE THE | | | CONDUIT AND WIRE SIZES. SEE 250.122 AND INSTALL THE | | | EQUIPMENT GROUND PER SAME (AFTER THE DISCONNECT AND RUN | | | TO PANEL). | | | | | | 2} THERE IS ONLY ONE A/C SYSTEM ON THE PANEL SCHEDULE, | | | TWO IN THE CALCULATIONS. PLEASE CORRELATE. | | | | | | 3} THE ELECTRICAL PANEL LOCATION IN THE KITCHEN WOULD | | | NOT COMPLY WITH THE 3' CLEARANCE REQUIREMENT OF 110.26, | | | WITH RESPECT TO THE PENINSULAR. | | | | | | 4}BATH CIRCUIT REQUIRED TO HAVE A 20 AMP CIRCUIT PER | | | 210.11(C) (3), INCLUDE IN THE PANEL SCHEDULE. | | | | | | 5} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A) (1) | | | AND 210.52 (A) (2), SEE DINING ROOM AND NEW BEDROOM. | | | NOTE THE DINING ROOM MUST BE ON A SMALL APPLIANCE | | | CIRCUIT PER 210.52(B)(1). | | | | | | 6} THE ISLAND AND PENINSULAR RECEPTACLES MUST BE GFCI | | | PROTECTED PER 210.8(A)(6), INDICATE ON PLAN.. | | | | | | 7}A RECEPTACLE IS REQUIRED FOR THE SERVICING OF THE | | | CONDENSING UNITS PER 210.63. NONE IS INDICATED ON THE | | | PLAN. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | |
|