Plan Review Notes
Plan Review Notes For Permit 06120209
Permit Number 06120209
Review Stop E
Sequence Number 2
Notes
Date Text
2007-07-03 08:20:08 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE DISCONNECT LOCATION ON THE RISER IS INCORRECT AN
 DISCONNECTS NOTHING. PLEASE REDRAW AND INDICATE THE
 CONDUIT AND WIRE SIZES. SEE 250.122 AND INSTALL THE
 EQUIPMENT GROUND PER SAME (AFTER THE DISCONNECT AND RUN
 TO PANEL).
  
 2} THERE IS ONLY ONE A/C SYSTEM ON THE PANEL SCHEDULE,
 TWO IN THE CALCULATIONS. PLEASE CORRELATE.
  
 3} THE ELECTRICAL PANEL LOCATION IN THE KITCHEN WOULD
 NOT COMPLY WITH THE 3' CLEARANCE REQUIREMENT OF 110.26,
 WITH RESPECT TO THE PENINSULAR.
  
 4}BATH CIRCUIT REQUIRED TO HAVE A 20 AMP CIRCUIT PER
 210.11(C) (3), INCLUDE IN THE PANEL SCHEDULE.
  
 5} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A) (1)
 AND 210.52 (A) (2), SEE DINING ROOM AND NEW BEDROOM.
 NOTE THE DINING ROOM MUST BE ON A SMALL APPLIANCE
 CIRCUIT PER 210.52(B)(1).
  
 6} THE ISLAND AND PENINSULAR RECEPTACLES MUST BE GFCI
 PROTECTED PER 210.8(A)(6), INDICATE ON PLAN..
  
 7}A RECEPTACLE IS REQUIRED FOR THE SERVICING OF THE
 CONDENSING UNITS PER 210.63. NONE IS INDICATED ON THE
 PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  