| 2006-12-22 14:31:58 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | |
| | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING |
| | PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. SHEET A2 SANITARY RISER DIAGRAM DOES NOT REFLECT |
| | THE FLOOR PLAN, PLEASE REFERENCE THE ATTACHED CORRECTED |
| | SANITARY RISER DIAGRAM TO THE PLUMBING COMMENTS |
| | REFLECTING THE FLOOR PLAN THAT IS CODE COMPLIANT. |
| | |
| | 2. PER FBC-2004 PLUMBING THE FOLLOWING CORRECTIONS ARE |
| | REQUIRED FOR THE WASHING MACHINE. |
| | (A) 406.3 WASTE CONNECTIONS.THE TRAP AND |
| | FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES |
| | WASHER SHALL BE A MINIMUM OF 2 INCHES |
| | (51MM) IN DIAMETER. THE AUTOMATIC |
| | CLOTHES WASHER FIXTURE DRAIN SHALL |
| | CONNECT TO A BRANCH DRAIN OR DRAINAGE |
| | STACK A MINIMUM OF 3 INCHES (76MM) IN |
| | DIAMETER. |
| | (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY |
| | TRAPPED. STANDPIPES SHALL |
| | EXTEND A MINIMUM OF 18 INCHES (457MM) |
| | AND A MAXIMUM OF 42 INCHES (1066MM) |
| | ABOVE THE TRAP WEIR. ACCESS SHALL BE |
| | PROVIDED TO ALL STANDPIPES AND DRAINS |
| | FOR RODDING. PLEASE INDICATE THE STANPIPE ON THE |
| | RESUBMITTED DRAWINGS. |
| | (C) 708.9 ACCESS. ACCESS SHALL BE PROVIDED TO ALL |
| | CLEANOUTS, ON RESUBMITTED DRAWINGS PLEASE INDICATE |
| | CLEANOUT FOR WASHING MACHINE AT 4 FEET ABOVE FINNISH |
| | FLOOR (4' AFF). |
| | |
| | END OF COMMENTS: |
| | |