2006-12-21 11:10:59 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} SHOW THE PHYSICAL LOCATION OF ALL SERVICE EQUIPMENT
 ON THE PLAN. 215.5. PER THE RISER DIAGRAM IT WOULD
 APPEAR THAT A 200 AMP DISCONNECT WOULD BE REQUIRED AT
 THE METER PER 230.70 (A) (1).
  
 2} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 3} PLEASE PROVIDE A PANEL SCHEDULE SO THAT
 BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT
 PROTECTION COMPLIANCE MAY BE REVIEWED PER 106.3.5.4 FBC
 AS AMENDED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.