| 2007-02-08 09:44:29 | BUILDING PLAN REVIEW |
| | PERMIT:06120209 |
| | ADD:1325 9TH STREET |
| | CONT:JUSTINA A. MCCRAY |
| | TEL: (561)805-7255 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW1ST |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 3)THE EMERGENCY EGRESS WINDOWS SHALL REFER TO |
| | SECTION R310 OF THE 2004 RESIDENTIAL BUILDING CODE OR |
| | THE 2004 FBC. NOT THE 2001 FBC. |
| | |
| | 4)WPB AMENDMENTS 108.3*THE VALUE IS TO LOW. IF IN |
| | THE OPINION OF THE BUILDING OFFICIAL, THE CLAIMED |
| | VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| | TO BE UNDERESTIMATED ON THE APPLICATION, THE PERMIT |
| | SHALL BE DENIED. FOR PERMITTING PURPOSES, VALUATION OF |
| | BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE |
| | TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHNICAL, |
| | INTERIOR FINISH, NORMAL SITE WORK, ARCHITECTURAL AND |
| | DESIGN FEES EXCLUDING LAND.OUR VALUATION REFERENCE IS |
| | ICC (BVD) MARSHALL-SWIFT AND MEANS COST ANALYSIS |
| | SERVICES. |
| | |
| | 5)R807.1 ATTIC ACCESS. IN BUILDINGS WITH COMBUSTIBLE |
| | CEILING OR ROOF CONSTRUCTION, AN ATTIC ACCESS OPENING |
| | SHALL BE PROVIDED TO ATTIC AREAS THAT EXCEED 30 SQUARE |
| | FEET AND HAVE A VERTICAL HEIGHT OF 30 INCHES OR |
| | GREATER. |
| | THE ROUGH-FRAME OPENING SHALL NOT BE LESS THAN 22 |
| | INCHES BY 30 INCHES AND SHALL BE LOCATED IN A HALLWAY |
| | OR OTHER REDAILY ACCESSIBLE LOCATION. A 30-INCH MINIMUM |
| | UNOBSTRUCTED HEADROOM IN THE ATTIC SPACE SHALL BE |
| | PROVIDED AT SOME POINT ABOVE THE ACCESS OPENING. SEE |
| | SECTION M 1305.1.3 FOR ACCESS REQUIREMENTS WHERE |
| | MECHANICAL EQUIPMENT IS LOCATED IN ATTICS. |
| | |
| | 6)106.3.3* PRODUCT APPROVALS- 2004 |
| | THOSE PRODUCTS THAT ARE RGULATED BY DCA |
| | RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITTING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. PROVIDE THE PRODUCT APPROVALS |
| | FOR THE GLASS BLOCKS. |
| | |
| | 7)M1506.2EXHAUST AIR FROM BATHROOMS AND TIOLET |
| | ROOMS SHALL NOT BE RECIRCULATED WITHIN A RESIDENCE OR |
| | TO ANOTHER DWELLING UNIT. MECHANICAL EXHAUST CAPACITY |
| | FOR BATHROOMS AND TOILET ROOMS SHALL BE NO LESS THAN 50 |
| | CFM INTERMITTENT OR 20 CFM CONTINOUS. |
| | |
| | 8)R308.4 (5)GLAZING IN DOORS AND ENCLOSURES FOR HOT |
| | TUBS, WHIRLPOOLS, SAUNAS, STEAM ROOMS, BATHTUBS AND |
| | SHOWERS. GLAZING IN ANY PART OF A BUILDING WALL |
| | ENCLOSING THESE XOMPARTMENTS WHERE THE BOTTOM EXPOSED |
| | EDGE OF THE GLAZING IS LESS THAN 60 INCHES MEASURED |
| | VERTICALLY ABOVE THE STANDING OR WALKING SURFACE. |
| | |
| | 9)WPB AMENDMENTS 106.1.3*THE BUILDING OFFICIAL MAY |
| | ESTABLISH THROUGH DEPARTMENTAL POLICY, STANDARDS FOR |
| | PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE |
| | COMFORMITY TO ITS RECORD RETENTION PROGRAM,THIS |
| | POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE, |
| | CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS |
| | MANAGEMENT. THE SEAL ON THE DRAWINGS ARE ILLEGIBLE. |
| | 61G15-23.002A PROFESSIONAL ENGINER SHALL SIGN HIS |
| | NAME AND AFFIX HIS SEAL TO ALL PLANS, SEPCIFICATIONS, |
| | REPORTS, FINAL BID COCUMENTS OR OTHER DOCUMENTS |
| | PREPARED OR ISSUED BY SAID REGISTRANT AND BEING FILED |
| | FOR PUBLIC RECORD. |
| | |
| | 10)PROVIDE AN INTERIOR ELEVATION SHOWING ALL |
| | DIMENTIONS OF THE LIVING SPACE CEILING INCLUDED. HOW |
| | WILL THE EXISTING STRUCTURE BE SUPPORTED WHEN THE |
| | EXTERIOR WALL AT THE KITCHEN AREA IS REMOVED. SHOW IN |
| | DETAIL HOW THIS AREA WILL BE SUPPORTED. |
| | |
| | 11) |
| | ) 110.2* W. P. B. ADMINISTRATIVE |
| | CODE, INFORMATION THAT IS REQUIRED FOR |
| | RECORD KEEPING & FOR CERTIFICATE OF |
| | OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PERMIT WAS ISSUED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | ) NUMBER OF FLOORS |
| | ) NUMBER OF ROOMS |
| | ) NUMBER OF BEDROOMS |
| | ) SQ. FT. LIV SPACE/ FL |
| | ) SQ. FT. FOOTPRINT |
| | ) SQ. FT. UNDER ROOF (TOTAL) |
| | ) FLOOD ZONE |
| | ) FLOOD ELEVATION |
| | )L.O.M.R. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |