| 2007-10-12 16:50:51 | REVISION DENIED |
| | REFERENCE: |
| | ** FBC-2004 FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE (FAC). |
| | ** FLORIDA STATUTES (FS). |
| | |
| | 1. THE SUBMITTED REVISION IS CONFUSING IN THAT THE |
| | LANTERNS ARE STILL BEING INDICATED ON THE GAS ISOMETRIC |
| | RISER DIAGRAM. HOWEVER THERE IS A "NOTE: ISOLATE THE |
| | SUPPLY LINE, DISCONNECT THE TORCHES AND REMOVE THE |
| | SUPPLY FEED ABOVE GROUND @ EACH PILLAR LOCATION". THE |
| | REVISIED GAS ISOMETRIC SHOULD BE CORRELATED WITH THE |
| | NOTE. PER FBC-2004 CHAPTER 1, SECTION 106.1.1 |
| | INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL |
| | BE OF SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE |
| | AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS, |
| | AS DETERMINED BY THE |
| | BUILDING OFFICIAL. PLEASE CLEARLY CORRELATE THE GAS |
| | ISOMETRIC RISER DIAGRAM WITH THE NOTE ON THE NEXT |
| | REVISION SUBMITTAL. |
| | |
| | 2. IF THE LANTERNS ARE NOT GOING TO BE USED WHY NOT |
| | CAP GAS TIGHT AT THE TEE BY THE METER FEEDING THE |
| | LANTERNS AND REMOVE THE PIPING. PLEASE CLARIFY THIS. |
| | |
| | END OF COMMENTS: |
| | |