| 2007-04-11 15:39:15 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION FOR THE REVISION |
| | ARE REQUIRED FOR GAS PLAN REVIEW TO MEET CODE |
| | COMPLIANCE: |
| | |
| | 1. PARTIAL REVISION OF THE GAS SYSTEM ARE UNACCEPTABLE |
| | PLEASE SUBMIT THE COMPLETE GAS SYSTEM ON THAT SHEET |
| | WITH THE NEW REVISION PER FBC-2004 CHAPTER 1, SECTION |
| | 106.1.1. |
| | |
| | 2. FBC-2004 CHAPTER 1,SECTION 106.3.4.2: |
| | THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| | THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| | NAME, AND ALSO DATE DRAWING. PLEASE DO |
| | THIS PRIOR TO RESUBMITTING. |
| | NOTE: THE SIGNATURE ON THE REVISION IS DIFFERENT THAN |
| | THE PERMITTED COPY AND IS IN PENCIL. IS THIS YOUR |
| | INTENT? SIGNATURE IN PENCIL IS UNACCEPTABLE PER |
| | FBC-2004 CHAPTER 1, SECTION 106.1.1. |
| | |
| | 3. PLEASE ADJUST THE TOTAL BTU'S ON THE REVISION TO |
| | REFLECT THE DIFFERENT BTU'S OF THE LANTERN. PERMITTED |
| | COPY INDICATES 2500BTU'S AND THE REVISION INDICATES |
| | 15000 BTU'S. ALSO DELETE THE POOL HEATER BTU'S FROM THE |
| | TOTAL BTU LOAD ON THE REVISION. |
| | |
| | 4. PLEASE INDICATE ALL CORRESPONDING LENGTHS OF THE |
| | CUT SECTIONS OF THE REVISED GALVANIZED PIPING ON THE |
| | RESUBMITTAL. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |