Plan Review Notes
Plan Review Notes For Permit 06120149
Permit Number 06120149
Review Stop B
Sequence Number 1
Notes
Date Text
2007-02-08 06:32:36DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE APPLICATION.
 233-5025
  
 3) SUBMIT ENERGY CALCULATIONS AS REQUIRED BY 2004 FBC
 CHAPTER 13.
  
 4) ON SHEET A1 SPECIFY THE 2004 FLORIDA BUILDING CODE.
 CURRENT CODE IS NOT ACCEPTABLE.
  
 5) R310.1 EMERGENCY ESCAPE AND RESCUE REQUIRED.
 BASEMENTS WITH HABITABLE SPACE AND EVERY SLEEPING ROOM
 SHALL HAVE AT LEAST ONE OPENABLE EMERGENCY ESCAPE AND
 RESCUE OPENING .
 R310.1.2 MINIMUM OPENING HEIGHT.
 THE MINIMUM NET CLEAR OPENING HEIGHT SHALL BE 24 INCHES
 (610 MM).
 R310.1.3 MINIMUM OPENING WIDTH.
 THE MINIMUM NET CLEAR OPENING WIDTH SHALL BE 20 INCHES
 (508 MM). THE WINDOW IN THE PROPOSED BED ROOM DOES NOT
 COMPLY.
  
 6) SHOW COMPLIANCE WITH R320.7 PROTECTION AGAINST
 TERMITES AND DECAY. CONDENSATE LINES AND ROOF
 DOWNSPOUTS SHALL DISCHARGE AT LEAST 1 FOOT AWAY FROM
 THE STRUCTURE SIDEWALL, WHETHER BY UNDERGROUND PIPING,
 TAIL EXTENSIONS OR SPLASH BLOCKS. GUTTERS WITH DOWN
 SPOUTS ARE REQUIRED ON ALL BUILDINGS WITH EAVES OF LESS
 THAN 6 INCHES HORIZONTAL PROJECTION EXCEPT FOR GABLE
 END RAKES OR ON A ROOF ABOVE ANOTHER ROOF.
  
 7) WALL SECTION 1/A3 SPECIFIES AN 18 " THICK FOOTING.
 THE SCHEDULE ON A4 SPECIFIES A 16" THICK FOOTER AT THIS
 LOCATION. PLEASE CORRECT.
  
 8) THERE IS NO NO CONCRETE SLAB SPECIFIED ON THE
 FOUNDATION PLAN ON A4 FOR THE CARPORT ALTHOUGH THE LEFT
 ELEVATION ON A3 APPEARS TO INDICATE ONE. PLEASE
 CLARIFY.
 R309.4 CARPORTS.
 CARPORTS SHALL BE OPEN ON AT LEAST TWO SIDES. CARPORT
 FLOOR SURFACES SHALL BE OF APPROVED NONCOMBUSTIBLE
 MATERIAL. CARPORTS NOT OPEN ON AT LEAST TWO SIDES SHALL
 BE CONSIDERED A GARAGE AND SHALL COMPLY WITH THE
 PROVISIONS OF THIS SECTION FOR GARAGES.
 EXCEPTION: ASPHALT SURFACES SHALL BE PERMITTED AT
 GROUND LEVEL IN CARPORTS.
 THE AREA OF FLOOR USED FOR PARKING OF AUTOMOBILES OR
 OTHER VEHICLES SHALL BE SLOPED TO FACILITATE THE
 MOVEMENT OF LIQUIDS TO A DRAIN OR TOWARD THE MAIN
 VEHICLE ENTRY DOORWAY.
  
 9) SPECIFY THE SLAB DETAIL INFORMATION FOR THE COVERED
 PATIO AND CARPORT ON THE FOUNDATION PLAN ON A4. SEE R
 506.
  
 10) PROVIDE A COLUMN SCHEDULE. SPECIFY THE STEEL COLUMN
 SIZE AND THICKNESS AND THE VERTICAL REINFORCING IN THE
 FILLED CELLS.
  
 11) SPECIFY THE STEEL COLUMN BASES AND THE REQUIRED
 FASTENER TYPE, SIZE, EMBED DEPTH AND QUANITY.
  
 12) SPECIFY THE BEAM ON SHEET A5 FOR THE COVERED
 PATIO.
  
 13)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 14)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SUBMIT THE FL COVERSHEET
 FOR ALL OF THE PRODUCTS.
  
 15)SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES
 LISTED IN THE NOA WILL BE INSTALLED. SPECIFY THE
 FASTENING OPTION OPTION THAT WILL BE USED AND THE
 DESIGN PRESSURE. IF ENHANCED FASTENING IS REQUIRED FOR
 THE PERIMETER AND CORNER AREAS, SUBMIT RAS 117
 CALCULATIONS.
  
 16) THE NOA FOR THE TRACO SERIES 2100 HAS BEEN REVISED.
 SUBMIT THE NEW NOA.
  
 17)THREE PRODUCT APPROVALS WERE SUBMITTED FOR THE NEW
 DOOR.PLEASE SUBMIT THE ONE FOR THE DOOR THAT WILL BE
 INSTALLED ONLY.
  
 18) THE PLANS SPECIFY A GLAZED FRENCH DOOR WHICH WILL
 REQUIRE STORM PANELS IF IT IS NOT AN IMPACT RATED
 DOOR.
  
 20) SUBMIT PRODUCT APPROVALS FOR THE STORM PANELS.
 SUBMIT 2 COPIES OF A KEY PLAN AND INSTALLATION SCHEDULE
 FOR THE STORM PANELS. SPECIFY THE OPENING SIZES, PANEL
 SPANS, FASTENER TYPE AND SPACING, CONNECTION TYPE,
 PRESSURES, ETC.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  