| 2007-02-08 06:32:36 | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| | MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) BEFORE A PERMIT TO CONSTRUCT CAN BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY.THE PLANS MUST BE |
| | STAMPED AND THE RECEIPT ATTACHED TO THE APPLICATION. |
| | 233-5025 |
| | |
| | 3) SUBMIT ENERGY CALCULATIONS AS REQUIRED BY 2004 FBC |
| | CHAPTER 13. |
| | |
| | 4) ON SHEET A1 SPECIFY THE 2004 FLORIDA BUILDING CODE. |
| | CURRENT CODE IS NOT ACCEPTABLE. |
| | |
| | 5) R310.1 EMERGENCY ESCAPE AND RESCUE REQUIRED. |
| | BASEMENTS WITH HABITABLE SPACE AND EVERY SLEEPING ROOM |
| | SHALL HAVE AT LEAST ONE OPENABLE EMERGENCY ESCAPE AND |
| | RESCUE OPENING . |
| | R310.1.2 MINIMUM OPENING HEIGHT. |
| | THE MINIMUM NET CLEAR OPENING HEIGHT SHALL BE 24 INCHES |
| | (610 MM). |
| | R310.1.3 MINIMUM OPENING WIDTH. |
| | THE MINIMUM NET CLEAR OPENING WIDTH SHALL BE 20 INCHES |
| | (508 MM). THE WINDOW IN THE PROPOSED BED ROOM DOES NOT |
| | COMPLY. |
| | |
| | 6) SHOW COMPLIANCE WITH R320.7 PROTECTION AGAINST |
| | TERMITES AND DECAY. CONDENSATE LINES AND ROOF |
| | DOWNSPOUTS SHALL DISCHARGE AT LEAST 1 FOOT AWAY FROM |
| | THE STRUCTURE SIDEWALL, WHETHER BY UNDERGROUND PIPING, |
| | TAIL EXTENSIONS OR SPLASH BLOCKS. GUTTERS WITH DOWN |
| | SPOUTS ARE REQUIRED ON ALL BUILDINGS WITH EAVES OF LESS |
| | THAN 6 INCHES HORIZONTAL PROJECTION EXCEPT FOR GABLE |
| | END RAKES OR ON A ROOF ABOVE ANOTHER ROOF. |
| | |
| | 7) WALL SECTION 1/A3 SPECIFIES AN 18 " THICK FOOTING. |
| | THE SCHEDULE ON A4 SPECIFIES A 16" THICK FOOTER AT THIS |
| | LOCATION. PLEASE CORRECT. |
| | |
| | 8) THERE IS NO NO CONCRETE SLAB SPECIFIED ON THE |
| | FOUNDATION PLAN ON A4 FOR THE CARPORT ALTHOUGH THE LEFT |
| | ELEVATION ON A3 APPEARS TO INDICATE ONE. PLEASE |
| | CLARIFY. |
| | R309.4 CARPORTS. |
| | CARPORTS SHALL BE OPEN ON AT LEAST TWO SIDES. CARPORT |
| | FLOOR SURFACES SHALL BE OF APPROVED NONCOMBUSTIBLE |
| | MATERIAL. CARPORTS NOT OPEN ON AT LEAST TWO SIDES SHALL |
| | BE CONSIDERED A GARAGE AND SHALL COMPLY WITH THE |
| | PROVISIONS OF THIS SECTION FOR GARAGES. |
| | EXCEPTION: ASPHALT SURFACES SHALL BE PERMITTED AT |
| | GROUND LEVEL IN CARPORTS. |
| | THE AREA OF FLOOR USED FOR PARKING OF AUTOMOBILES OR |
| | OTHER VEHICLES SHALL BE SLOPED TO FACILITATE THE |
| | MOVEMENT OF LIQUIDS TO A DRAIN OR TOWARD THE MAIN |
| | VEHICLE ENTRY DOORWAY. |
| | |
| | 9) SPECIFY THE SLAB DETAIL INFORMATION FOR THE COVERED |
| | PATIO AND CARPORT ON THE FOUNDATION PLAN ON A4. SEE R |
| | 506. |
| | |
| | 10) PROVIDE A COLUMN SCHEDULE. SPECIFY THE STEEL COLUMN |
| | SIZE AND THICKNESS AND THE VERTICAL REINFORCING IN THE |
| | FILLED CELLS. |
| | |
| | 11) SPECIFY THE STEEL COLUMN BASES AND THE REQUIRED |
| | FASTENER TYPE, SIZE, EMBED DEPTH AND QUANITY. |
| | |
| | 12) SPECIFY THE BEAM ON SHEET A5 FOR THE COVERED |
| | PATIO. |
| | |
| | 13)WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 14)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SUBMIT THE FL COVERSHEET |
| | FOR ALL OF THE PRODUCTS. |
| | |
| | 15)SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES |
| | LISTED IN THE NOA WILL BE INSTALLED. SPECIFY THE |
| | FASTENING OPTION OPTION THAT WILL BE USED AND THE |
| | DESIGN PRESSURE. IF ENHANCED FASTENING IS REQUIRED FOR |
| | THE PERIMETER AND CORNER AREAS, SUBMIT RAS 117 |
| | CALCULATIONS. |
| | |
| | 16) THE NOA FOR THE TRACO SERIES 2100 HAS BEEN REVISED. |
| | SUBMIT THE NEW NOA. |
| | |
| | 17)THREE PRODUCT APPROVALS WERE SUBMITTED FOR THE NEW |
| | DOOR.PLEASE SUBMIT THE ONE FOR THE DOOR THAT WILL BE |
| | INSTALLED ONLY. |
| | |
| | 18) THE PLANS SPECIFY A GLAZED FRENCH DOOR WHICH WILL |
| | REQUIRE STORM PANELS IF IT IS NOT AN IMPACT RATED |
| | DOOR. |
| | |
| | 20) SUBMIT PRODUCT APPROVALS FOR THE STORM PANELS. |
| | SUBMIT 2 COPIES OF A KEY PLAN AND INSTALLATION SCHEDULE |
| | FOR THE STORM PANELS. SPECIFY THE OPENING SIZES, PANEL |
| | SPANS, FASTENER TYPE AND SPACING, CONNECTION TYPE, |
| | PRESSURES, ETC. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |