| Date |
Text |
| 2007-06-08 11:06:29 | GAS REVISION DENIED |
| | REFERENCE: |
| | ** FBC-2004 FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATIONREQUIRED FOR GAS |
| | PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1.NOTE: THE SUBMITTED GAS REVISION DRAWINGS ARE NOT |
| | LEGIBLE AND ARE HARD TO READ. PLEASE CORRECT THIS ON |
| | THE RESUBMITTED GAS REVISION. |
| | PER FBC-2004 CHAPTER 1, SECTION 106.1.1:INFORMATION |
| | ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL |
| | BE OF SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE |
| | AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS, |
| | AS DETERMINED BY THE |
| | BUILDING OFFICIAL. |
| | |
| | 2. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | NOTE: THE SUBMITTED GAS REVISION DRAWINGS ARE NOT |
| | INDICATING CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF |
| | PIPE. PLEASE CORRECT THIS ON THE RESUBMITTED GAS |
| | REVISION. |
| | |
| | 3. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | NOTE: THE TOTAL DEVELOPED LENGTHS INDICATED ON THE |
| | DRAWINGS OF 85' ON THE 2 PSI, AND 35' ON THE 0.5 PSI |
| | CAN NOT BE VERIFIED UNTIL COMMENTS #1 AND #2 HAVE BEEN |
| | ADDRESSED. |
| | |
| | 4.PER FBC-2004 FUEL GAS SECTION 408.4 A SEDIMENT |
| | TRAP REQUIRED ON COOK LINE AND SHALL BE INSTALLED |
| | DOWNSTREAM OF THE EQUIPMENT SHUTOFF VALVE AS CLOSE TO |
| | THE INLET OF THE EQUIPMENT AS PRACTICAL. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |