Plan Review Notes
Plan Review Notes For Permit 06120139
Permit Number 06120139
Review Stop G
Sequence Number 4
Notes
Date Text
2007-05-18 16:18:08DENIED REVISION
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 THE GAS REVISION PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. NOTE: THIS IS NOT A GAS SUBMITTAL, THIS IS A GAS
 REVISION AND ADDITIONAL FEES ARE DUE. THE APPROVED
 PERMITTED GAS DRAWINGS ON SHEET 3.0A, ARE SIGNED AND
 SEALED BY DESIGNPROFESSIONAL THOMAS TWOMEY P.E.
 #25626, AND ANY REVISIONS TO SAID DRAWINGS MUST BE
 SIGNED AND SEALED BY SAID DESIGN PROFESSIONAL PER
 CHAPTER 471, FLORIDA STATUTES.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721