| Date |
Text |
| 2007-03-21 11:24:16 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS, |
| | SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING |
| | REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT |
| | MADE ON PREVIOUS REVIEWS. |
| | |
| | ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM |
| | PREVIOUS REVIEW WITH A NO, OK OR A NO/OK. |
| | THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE |
| | PREVIOUS REVIEW NOTES. |
| | |
| | A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR |
| | FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS |
| | ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER |
| | EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT. |
| | |
| | AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL |
| | COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS. |
| | |
| | A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN |
| | ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW |
| | COMMENT MAY HAVE BEEN FULLY ADDRESSED. |
| | |
| | ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF |
| | THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH. |
| | |
| | 1.**OK** |
| | |
| | 2.**OK** |
| | |
| | 3.**OK** |
| | |
| | 4 A}**OK**, AND B}**OK** |
| | |
| | 5.**OK** |
| | |
| | 6.**OK** |
| | |
| | 7.**OK** |
| | |
| | 8.**OK** |
| | |
| | 9.**OK** |
| | |
| | 10.**OK** |
| | |
| | 11.**OK** |
| | |
| | 12.**NO/OK** SHEET 3.0A ISOMETRIC WATER RISER AND THE |
| | WATER HEATER DETAIL: PLEASE CORRELATE THE WATER HEATER |
| | P&T VALVE AND HEATER PAN DRAIN LOCATION. |
| | NOTE: THE RESUBMITTED WATER HEATER DETAIL INDICATES P&T |
| | TO SAFE PAN, SAFE PAN TO MOP SINK. THE ISOMTRIC WATER |
| | RISER INDICATES P&T VALVE TO MOP SINK. PLEASE CORRELATE |
| | THE ISOMETRIC WATER RISER WITH THE WATER HEATER DETAIL |
| | ON THE RESUBMITTAL. |
| | |
| | 13.**OK** |
| | |
| | THE FOLLOWING ARE NEW COMMENTS: |
| | |
| | 14. SHEET 3.0A ISOMETRIC SANITARY RISER DIAGRAM |
| | INDICATING A TRAPZILLA AT325. I BELIEVE THAT MODLE |
| | NUMBER IS INCORRECT, I BELIEVE THE CORRECT MODEL NUMBER |
| | IS TZ-325 PLEASE CLARIFY ON THE RESUBMITTAL. PLEASE |
| | KNOW THAT THIS GREASE TRAP NEEDS APPROVAL FROM |
| | ENVIRONMENTAL COMPLIANCE. |
| | NOTE: PER ARTICLE LLL. SEWERS AND SEWEAGE DISPOSAL. |
| | PLEASE CONTACT THE FOLLOWING. |
| | |
| | ENVIRONMENTAL COMPLIANCE MANAGER: |
| | LYNN MASSON |
| | PHONE= (561) 822-2271 |
| | FAX= (561) 822-2279 |
| | E-MAIL= [email protected] |
| | |
| | 15. SHEET 3.0A PLUMBING FLOOR PLAN: PLEASE DELETE THE |
| | FOLLOWING "2 WAY FCO SAMPLE POINT" AND "TIE TO EXISTING |
| | 4" SANITARY" ON THE RESUBMITTAL. |
| | |
| | 16. SHEET 3.0A SANITARY ISOMETRIC RISER DIAGRAM: |
| | TWO-WAY CLEANOUT REQUIRED ON BOTH THE INLET AND THE |
| | OUTLET OF THE GREASE TRAP PER THE CITY OF WEST PALM |
| | BEACH STANDARD GREASE TRAP DETAIL. PLEASE REFERENCE THE |
| | ATTACHED COPY OF THIS DETAIL TO THE PLUMBING COMMENTS. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |
| | |