Plan Review Notes
Plan Review Notes For Permit 06120139
Permit Number 06120139
Review Stop E
Sequence Number 3
Notes
Date Text
2007-03-10 14:07:19** UNSAT 3RD REVIEW **
  
 1) NOTE: PLEASE SEE PLANS DO NOT INDICATE THE YEARS FOR
 THE NFPA-101 AND NFPA-72. SHOULD BE 2003 FOR 101 AND
 2002 FOR 72.
 THIS WOULD HAVE BEEN REDLINED HOWEVER PLANS ARE COMING
 BACK FOR OTHER COMMENTS.
  
 2) NOTE: PLEASE SEE THE SERVICE RISER AS THIS IS NOW
 NOTING THIS EXISTING 3-PHASE SERVICE FOR ONE OF THE
 METERS/MAINS WHICH ON PREVIOUS PLANS WAS BEING SHOWN AS
 AN EXISTING SINGLE PHASE METER AND MAIN? PLEASE CLARIFY
 THIS AS IT WAS THE UNDERSTANDING THAT A NEW 3-PHASE
 METER CAN, MAIN AND PANEL WAS BEING INSTALLED. PLEASE
 SEE THE PANEL *B* AS IT IS NOW BEING SHOWN AS 3-PHASE.
 PLEASE SEE BASED ON THE FEEDERS SHOWN FROM THE GUTTER,
 ONLY A SINGLE PHASE SERVICE IS BEING BROUGHT IN TO THE
 METER??
 PLEASE CORRELATE.
  
 3) NOTE: PLEASE CORRELATE ALL FIXTURES ON THE FIXTURE
 LEGEND WITH THE FIXTURES ON PLANS AND WATTAGES ON PLANS
 WITH THE NUMBER OF FIXTURES ON ENERGY CALCULATIONS AND
 THE WATTAGES INDICATED ON THE ENERGY CALCULATIONS.
 PLEASE SEE THE TRACK LIGHTING DOES NOT CORRELATE.
 PLEASE SEE THE WALL LIGHTING FIXTURES DO NOT
 CORRELATE.
 PLEASE SEE THE LIGHTING IN KITCHEN AREA (FRONT) DOES
 NOT CORRELATE.
 PLEASE SEE THE LIGHTING IN KITCHEN AREA (REAR) DOES NOT
 CORRELATE.
 PLEASE SEE THE LIGHTING IN OTHER AREAS, LIKE THE
 BATHROOMS, CLOSET, ETC WHICH DO NOT MATCH.
 PLEASE SEE THE TYPE OF FIXTURES NEED TO BE
 COORDINATED.
 PLEASE SEE 13-415.1.AB.1.1, 13-415.2
  
 4) NOTE: PLEASE SEE THE PLANS DO NOT INDICATE THE OVER
 RIDES AT THE POINT OF ENTRANCE INTO THE SPACES (EACH
 DOOR) TO TURN ON THE LIGHTING. PLEASE KNOW AS THIS IS
 REQUIRED IN 13-415.1.ABC.1.1, .1.2.
 PLEASE ALSO SEE THIS IS A LIFE SAFETY CODE ISSUE FOR
 EGRESS AND INGRESS IN AND OUT OF AREAS/SPACE.
 PLEASE SEE ONLY ONE LCP PAD WAS ADDED TO PLANS AND DID
 NOT LOCATE THIS AT THE POINT OF ENTRANCE NOR IS ONE
 LOCATED AT THE OTHER LOCATION/POINT OF ENTRANCE.
  
 5) NOTE: PLEASE SEE THE LIGHTING CONTROL PANEL AND PANE
 SCHEDULE AS BOTH THE SIGN AND SHOW WINDOW ARE BEING
 SHOWN TO THE SAME LOCATION/CIRCUIT EVEN THOUGH THESE
 ARE TWO SEPARATE CIRCUITS.
 PLEASE CORRELATE AND ADJUST THE CIRCUITING FOR THE LCP
 AS NEEDED.
 FBC 106.1.2
  
 6) NOTE: PLEASE KNOW THAT ONE SET OF THE ELECTRICAL
 PLANS AND ENERGY CALCULATIONS HAVE NOW BEEN RETAINED BY
 THIS OFFICE FOR POSSIBLE REVIEW FROM THE FLORIDA BOARD
 OF PROFESSIONAL ENGINEERS. THIS IS THE RESPONSIBILITY
 OF THE ENGINEER OF RECORD.
 FS 471.025(2).
  
 7) NOTE: PLEASE SEE FS 553.80(2)(B) AS SOME OF THESE
 ITEMS ARE REPEAT COMMENTS FROM THE SECOND REVIEW, IF
 PLANS COME BACK WITHOUT ANY OF THE CODE COMMENTS
 ADDRESSED, A FEE WILL BE ASSESSED FOR THE PLAN REVIEW
 POTION OF THE PERMIT FEE. THIS IS ONLY BEING GIVEN AS A
 NOTICE AT THIS TIME.
  
 ** AS STATED IN PREVIOUS REVIEWS, IF THERE ARE
 QUESTIONS OR COMMENT PLEASE CONTACT THIS
 OFFICE/REVIEWER TO GO OVER THESE NOTES.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]