| 2007-03-10 14:07:19 | ** UNSAT 3RD REVIEW ** |
| | |
| | 1) NOTE: PLEASE SEE PLANS DO NOT INDICATE THE YEARS FOR |
| | THE NFPA-101 AND NFPA-72. SHOULD BE 2003 FOR 101 AND |
| | 2002 FOR 72. |
| | THIS WOULD HAVE BEEN REDLINED HOWEVER PLANS ARE COMING |
| | BACK FOR OTHER COMMENTS. |
| | |
| | 2) NOTE: PLEASE SEE THE SERVICE RISER AS THIS IS NOW |
| | NOTING THIS EXISTING 3-PHASE SERVICE FOR ONE OF THE |
| | METERS/MAINS WHICH ON PREVIOUS PLANS WAS BEING SHOWN AS |
| | AN EXISTING SINGLE PHASE METER AND MAIN? PLEASE CLARIFY |
| | THIS AS IT WAS THE UNDERSTANDING THAT A NEW 3-PHASE |
| | METER CAN, MAIN AND PANEL WAS BEING INSTALLED. PLEASE |
| | SEE THE PANEL *B* AS IT IS NOW BEING SHOWN AS 3-PHASE. |
| | PLEASE SEE BASED ON THE FEEDERS SHOWN FROM THE GUTTER, |
| | ONLY A SINGLE PHASE SERVICE IS BEING BROUGHT IN TO THE |
| | METER?? |
| | PLEASE CORRELATE. |
| | |
| | 3) NOTE: PLEASE CORRELATE ALL FIXTURES ON THE FIXTURE |
| | LEGEND WITH THE FIXTURES ON PLANS AND WATTAGES ON PLANS |
| | WITH THE NUMBER OF FIXTURES ON ENERGY CALCULATIONS AND |
| | THE WATTAGES INDICATED ON THE ENERGY CALCULATIONS. |
| | PLEASE SEE THE TRACK LIGHTING DOES NOT CORRELATE. |
| | PLEASE SEE THE WALL LIGHTING FIXTURES DO NOT |
| | CORRELATE. |
| | PLEASE SEE THE LIGHTING IN KITCHEN AREA (FRONT) DOES |
| | NOT CORRELATE. |
| | PLEASE SEE THE LIGHTING IN KITCHEN AREA (REAR) DOES NOT |
| | CORRELATE. |
| | PLEASE SEE THE LIGHTING IN OTHER AREAS, LIKE THE |
| | BATHROOMS, CLOSET, ETC WHICH DO NOT MATCH. |
| | PLEASE SEE THE TYPE OF FIXTURES NEED TO BE |
| | COORDINATED. |
| | PLEASE SEE 13-415.1.AB.1.1, 13-415.2 |
| | |
| | 4) NOTE: PLEASE SEE THE PLANS DO NOT INDICATE THE OVER |
| | RIDES AT THE POINT OF ENTRANCE INTO THE SPACES (EACH |
| | DOOR) TO TURN ON THE LIGHTING. PLEASE KNOW AS THIS IS |
| | REQUIRED IN 13-415.1.ABC.1.1, .1.2. |
| | PLEASE ALSO SEE THIS IS A LIFE SAFETY CODE ISSUE FOR |
| | EGRESS AND INGRESS IN AND OUT OF AREAS/SPACE. |
| | PLEASE SEE ONLY ONE LCP PAD WAS ADDED TO PLANS AND DID |
| | NOT LOCATE THIS AT THE POINT OF ENTRANCE NOR IS ONE |
| | LOCATED AT THE OTHER LOCATION/POINT OF ENTRANCE. |
| | |
| | 5) NOTE: PLEASE SEE THE LIGHTING CONTROL PANEL AND PANE |
| | SCHEDULE AS BOTH THE SIGN AND SHOW WINDOW ARE BEING |
| | SHOWN TO THE SAME LOCATION/CIRCUIT EVEN THOUGH THESE |
| | ARE TWO SEPARATE CIRCUITS. |
| | PLEASE CORRELATE AND ADJUST THE CIRCUITING FOR THE LCP |
| | AS NEEDED. |
| | FBC 106.1.2 |
| | |
| | 6) NOTE: PLEASE KNOW THAT ONE SET OF THE ELECTRICAL |
| | PLANS AND ENERGY CALCULATIONS HAVE NOW BEEN RETAINED BY |
| | THIS OFFICE FOR POSSIBLE REVIEW FROM THE FLORIDA BOARD |
| | OF PROFESSIONAL ENGINEERS. THIS IS THE RESPONSIBILITY |
| | OF THE ENGINEER OF RECORD. |
| | FS 471.025(2). |
| | |
| | 7) NOTE: PLEASE SEE FS 553.80(2)(B) AS SOME OF THESE |
| | ITEMS ARE REPEAT COMMENTS FROM THE SECOND REVIEW, IF |
| | PLANS COME BACK WITHOUT ANY OF THE CODE COMMENTS |
| | ADDRESSED, A FEE WILL BE ASSESSED FOR THE PLAN REVIEW |
| | POTION OF THE PERMIT FEE. THIS IS ONLY BEING GIVEN AS A |
| | NOTICE AT THIS TIME. |
| | |
| | ** AS STATED IN PREVIOUS REVIEWS, IF THERE ARE |
| | QUESTIONS OR COMMENT PLEASE CONTACT THIS |
| | OFFICE/REVIEWER TO GO OVER THESE NOTES. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |