| Date |
Text |
| 2007-02-16 15:32:52 | DENIED 2ND TIME |
| | REFERENCE: FBC-2004 PLUMBING; FBC-2004 CHAPTER 1, CITY |
| | OF WEST PALM BEACH AMENDMENTS; |
| | |
| | THE FOLLOWING CORRECTIONS ARE STILL REQUIRED FROM THE |
| | PREVIOUS PLUMBING PLAN REVIEW. |
| | NOTE: THIS REVIEW WILL FOLLOW THE SAME NUMERICAL ORDER |
| | AS THE PREVIOUS REVIEW WITH NEW ITEMS BEING NOTED AT |
| | THE END. |
| | AN (OK) BY THE NUMBER MEANS PREVIOUS COMMENT WAS |
| | ADDRESSED. |
| | |
| | 1. (OK) |
| | |
| | 2. (OK) |
| | |
| | 3. (OK) |
| | |
| | 4. A} (OK) |
| | |
| | B} (COMMENT NOT ADDRESSED) PER FBC-2004 PLUMBING, |
| | SECTION 708.3.5 TWO WAY CLEANOUT REQUIRED AT THE |
| | JUCTION OF THE BUILDING DRAIN AND THE BUILDING SEWER. |
| | PLEASE ADD THESE FOR THE RESUBMITTAL. |
| | NOTE: A SAMPLE POINT IS NOT CONSIDERED A TWO-WAY |
| | CLEANOUT. PLEASE REFERENCE THE ATTACHED DETAIL OF A |
| | SAMPLE POINT THATS APPROVED BY THE CITY AND CLEARLY |
| | INDICATE BOTH THE TWO-WAY CLEANOUT AND THE SAMPLE POINT |
| | ON THE RESUBMITTED PRINTS. |
| | |
| | 5. (OK) |
| | |
| | 6. (OK) |
| | |
| | 7. (OK) |
| | |
| | 8. (COMMENT NOT ADDRESSED) SHEET 3.0A WATER HEATER |
| | DETAIL SAFETY PAN: PLEASE INDICATE THE FOLLOWING PER |
| | FBC-2004 PLUMBING, SECTION 504.7.1, THE SAFETY PAN |
| | DRAIN SIZE AND PER SECTION 504.7.2 THE SAFETY PAN DRAIN |
| | TERMINATION ON THE RESUBMITTAL. |
| | |
| | 9. (OK) |
| | |
| | THE FOLLOWING ARE NEW ITEMS: NOTE, GAS PLAN REVIEW WILL |
| | NOW BE A SEPERATE PLAN REVIEW BECAUSE OF THE SUBMITTED |
| | DRAWINGS. |
| | |
| | 10. SHEET 3.0A PLUMBING PLAN DOES NOT REFLECT THE |
| | RESUBMITTED SANITARY RISER. PLEASE REFERENCE THE |
| | CORRECTED RED LINED SHEET AND PLEASE CORRELATE AND |
| | RESUBMIT. |
| | |
| | 11. SHEET 3.0A SAITARY RISER: PLEASE DELETE THE RED |
| | LINED PIPING FOR THE DD ON THE RESUBMITTAL. |
| | |
| | 12. SHEET 3.0A WATER RISER AND THE WATER HEATER |
| | DETAIL: PLEASE CORRELATE THE WATER HEATER P&T DRAIN |
| | LOCATION. WATER HEATER DETAIL INDICATES DRAIN TO |
| | EXTERIOR, AND WATER RISER INDICATES DRAIN TO MOP SINK. |
| | |
| | 13. SHEET 3.0A WATER RISER: PLEASE DELETE THE |
| | FOLLOWING "INSTALL APPROVED SHOCK ARRESTOR @ EA. |
| | FIXTURE GROUP" AND ADD IN ITS PLACE THE FOLLOWING " |
| | WATER HAMMER ARRESTORS TO BE INSTALLED PER FBC-2004 |
| | PLUMBING, SECTION 604.9." |
| | |
| | ******IMPORTANT INFORMATION |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |