Plan Review Notes
Plan Review Notes For Permit 06120139
Permit Number 06120139
Review Stop P
Sequence Number 2
Notes
Date Text
2007-02-16 15:32:52DENIED 2ND TIME
 REFERENCE: FBC-2004 PLUMBING; FBC-2004 CHAPTER 1, CITY
 OF WEST PALM BEACH AMENDMENTS;
  
 THE FOLLOWING CORRECTIONS ARE STILL REQUIRED FROM THE
 PREVIOUS PLUMBING PLAN REVIEW.
 NOTE: THIS REVIEW WILL FOLLOW THE SAME NUMERICAL ORDER
 AS THE PREVIOUS REVIEW WITH NEW ITEMS BEING NOTED AT
 THE END.
 AN (OK) BY THE NUMBER MEANS PREVIOUS COMMENT WAS
 ADDRESSED.
  
 1. (OK)
  
 2. (OK)
  
 3. (OK)
  
 4. A} (OK)
  
 B} (COMMENT NOT ADDRESSED) PER FBC-2004 PLUMBING,
 SECTION 708.3.5 TWO WAY CLEANOUT REQUIRED AT THE
 JUCTION OF THE BUILDING DRAIN AND THE BUILDING SEWER.
 PLEASE ADD THESE FOR THE RESUBMITTAL.
 NOTE: A SAMPLE POINT IS NOT CONSIDERED A TWO-WAY
 CLEANOUT. PLEASE REFERENCE THE ATTACHED DETAIL OF A
 SAMPLE POINT THATS APPROVED BY THE CITY AND CLEARLY
 INDICATE BOTH THE TWO-WAY CLEANOUT AND THE SAMPLE POINT
 ON THE RESUBMITTED PRINTS.
  
 5. (OK)
  
 6. (OK)
  
 7. (OK)
  
 8. (COMMENT NOT ADDRESSED) SHEET 3.0A WATER HEATER
 DETAIL SAFETY PAN: PLEASE INDICATE THE FOLLOWING PER
 FBC-2004 PLUMBING, SECTION 504.7.1, THE SAFETY PAN
 DRAIN SIZE AND PER SECTION 504.7.2 THE SAFETY PAN DRAIN
 TERMINATION ON THE RESUBMITTAL.
  
 9. (OK)
  
 THE FOLLOWING ARE NEW ITEMS: NOTE, GAS PLAN REVIEW WILL
 NOW BE A SEPERATE PLAN REVIEW BECAUSE OF THE SUBMITTED
 DRAWINGS.
  
 10. SHEET 3.0A PLUMBING PLAN DOES NOT REFLECT THE
 RESUBMITTED SANITARY RISER. PLEASE REFERENCE THE
 CORRECTED RED LINED SHEET AND PLEASE CORRELATE AND
 RESUBMIT.
  
 11. SHEET 3.0A SAITARY RISER: PLEASE DELETE THE RED
 LINED PIPING FOR THE DD ON THE RESUBMITTAL.
  
 12. SHEET 3.0A WATER RISER AND THE WATER HEATER
 DETAIL: PLEASE CORRELATE THE WATER HEATER P&T DRAIN
 LOCATION. WATER HEATER DETAIL INDICATES DRAIN TO
 EXTERIOR, AND WATER RISER INDICATES DRAIN TO MOP SINK.
  
 13. SHEET 3.0A WATER RISER: PLEASE DELETE THE
 FOLLOWING "INSTALL APPROVED SHOCK ARRESTOR @ EA.
 FIXTURE GROUP" AND ADD IN ITS PLACE THE FOLLOWING "
 WATER HAMMER ARRESTORS TO BE INSTALLED PER FBC-2004
 PLUMBING, SECTION 604.9."
  
 ******IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  