Plan Review Notes
Plan Review Notes For Permit 06120139
Permit Number 06120139
Review Stop G
Sequence Number 2
Notes
Date Text
2007-03-21 13:58:37DENIED 2ND TIME
 REFERENCE: FBC-2004 FUEL GAS; THE CITY OF WEST PALM
 BEACH GAS PERMIT APPLICATION REQUIREMENTS;
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1.**OK**
  
 2.**OK**
  
 3.**OK**
  
 4.**NO/OK**SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 NOTE: PLEASE INDICATE ON THE RESUBMITTED MANUFACTURER
 SHEETS THE MODEL NUMBER THAT CORRELATES WITH THE GAS
 LOAD CALCULATIONS ON SHEET 3.0A. SUBMITTALS MUST
 INDICATE A LISTINGS FROM A NATIONALLY RECOGNIZED
 TESTING LABORATORY (NRTL). THE FOLLOWING IS A LIST OF
 MANUFACTURER SHEETS THAT NEED CLARIFICATION.AN **OK**
 BY THE APPLIANCE MEANS THE SUBMITTAL IS ACCEPTABLE.
  
 A} WATER HEATER- SUBMITTAL **OK**, AN INDICATION OF
 WHICH MODEL NUMBER BEING USED IS REQUIRED.
  
 B} PIZZA- SUBMITTAL REQUIRED.
  
 C} PIZZA- SUBMITTAL REQUIRED.
  
 D} RANGE- 269,000 BTU RANGE, A LISTING (NRTL)
 REQUIRED.
  
 E} RANGE- 147,000 BTU RANGE, A LISTING (NRTL)
 REQUIRED. AN INDICATION OF WHICH MODEL NUMBER BEING
 USED IS REQUIRED. A CLEAR INDICATION THAT THE SUBMITTAL
 BTU'S CORRELATE WITH THE GAS LOAD CALCULATIONS ON SHEET
 3.0A.
  
 F} CONVECTION OVEN- SUBMITTAL **OK**, HOWEVER PLEASE
 REFERENCE THE NEW COMMENT IN RELATION TO THE CONVECTION
 OVEN.
  
 G} FRYER- SUBMITTAL **OK**.
  
 H} FRYER- SUBMITTAL **OK**.
  
 I} GRIDDLE- SUBMITTAL REQUIRED.
  
 J} MP REGULATOR- SUBMITTAL **OK**.
  
 K} EMERGENCY HOOD SHUT DOWN VALVE- SUBMITTAL **OK**.
  
 THE FOLLOWING ARE NEW COMMENTS:
  
 5. SHEET 3.0A GAS ISOMETRIC INDICATES 2 GAS
 CONNECTIONS WHICH WOULD MAKE IT A DOUBLE DECK
 CONVECTION OVEN WITH A TOTAL BTU LOAD OF 140,000. THE
 SUBMITTALS AND THE GAS LOAD CALCULATIONS ARE REFLECTING
 A SINGLE DECK COVECTION OVEN. IF THIS IS A SINGLE DECK
 COVECTION OVEN PLEASE DELETE ONE OF THE GAS CONNECTIONS
 ON THE GAS ISOMETRIC. IF THIS IS A DOUBLE DECK
 CONVECTION OVEN PLEASE CORRECT THE GAS LOAD
 CALCULATIONS ON SHEET 3.0A AND SUBMITTALS TO REFLECT
 THIS. PLEASE CLARIFY, CORRELATE, AND CORRECT ON THE
 RESUBMITTAL.
  
 6. SHEET 3.0A GAS ISOMETRIC: PLEASE DELETE THE 4'@ ON
 THE 2 PSI GAS PIPE BY THE SOV. THIS IS CONFUSING BEING
 THAT A BOLD 5' IS ALSO INDICATED FOR THE SAME
 CORRESPONDING CUT SECTION.
  
 7. SHEET 3.0A GAS ISOMETRIC GAS LOAD CALCULATIONS:
 PLEASE CORRECT THE 2 PSI LENGTH TO 60' AND THE 0.5 PSI
 LENGTH TO 31' ON THE RESUBMITTAL.
  
 8. SHEET 3.0A GAS ISOMETRIC: PLEASE CLEARLY INDICATE
 THE PIPE SIZE BETWEEN THE WATER HEATER AND PIZZA AS 2"
 ON THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved