Plan Review Notes
Plan Review Notes For Permit 06120139
Permit Number 06120139
Review Stop E
Sequence Number 2
Notes
Date Text
2007-02-12 11:02:02** UNSAT 2ND REVIEW **
  
 1) NOTE: PLEASE BE SURE ALL PLANS STATE THE FOLLOWING
 MINIMUM CODES IN WHICH PLANS ARE DESIGNED AND PERMITTED
 UNDER.
 PLEASE KNOW THE FOLLOWING WILL BE REQUIRED FOR
 ELECTRICAL SHEETS.
 2002 NFPA-70
 THE PREVIOUS NOTE ONLY MENTIONED PERMIT APPLICATIONS
 SUBMITTED AFTER THE DECEMBER 8TH 2006 DATE WOULD BE
 UNDER THE NEW CODES.
 PLEASE SEE THE PLANS STATE THE 2006 REVISIONS TO THE
 2004 FBC AND STATE THE 2005 NEC.
 PLEASE CORRECT.
  
 2) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1,
 .1.2 AND .1.3
 PLEASE INDICATE SCHEDULING, OVER RIDE DEVICES AT
 INGRESS/EGRESS, SEPARATE SPACES, TIMES ON ALL OVER RIDE
 DEVICES.
 PLEASE SEE 13-415.1.AB.1, 13-415.2, AND 13-415.2.ABC.1
 ENERGY CALCULATIONS ARE MISSING AND PERFORMANCE
 CALCULATIONS.
 PLEASE SEE THE LOCATION OF OVER RIDES SHALL ALSO BE
 LOCATED AS REQUIRED AT THE POINT OF INGRESS/EGRESS TO
 THE SPACE. THIS CAN BE DONE BY WAY OF OCCUPANCY SENSORS
 OR OVER RIDES SWITCH DEVICES.
 PLEASE SEE NOT TIMES ARE STATED ON PLANS FOR ANY
 DEVICES, OR SCHEDULING.
 PLEASE SEE THE SYMBOL LEGEND FOR DEVICES DOES NOT
 CORRELATE WITH THE SYMBOLS ON PLANS AND DOES NOT
 INDICATE OVER RIDE CONTROL.
 PLEASE SEE THE FIXTURE LEGEND DOES NOT CORRELATE WITH
 THE ENERGY CALCULATIONS AND THE ENERGY CALCULATIONS DO
 NOT CORRELATE WITH FIXTURES ON PLANS. THE AMOUNT OF
 FIXTURES ON PLANS IS SUBSTANTIALLY MORE THAN THE AMOUNT
 OF FIXTURES IN THE ENERGY CALCULATIONS.
 PLEASE SEE SOME LIGHTING CIRCUITS ON PLANS ALONG WITH
 FIXTURES DO NOT SHOW CONTROL OR HOW THEY ARE BEING
 CONNECTED OR CONTROLLED WHICH WILL AFFECT THE LIGHTING
 CONTROL PANEL AS STATED.
 PLEASE ALSO SEE COMMENT WITH RESPECT TO CONTROL AND
 CIRCUITS ON PLANS.
 PLEASE PROVIDE A PANEL SCHEDULE FOR THE LIGHTING
 CONTROL PANEL FOR ALL LIGHTING BEING CONTROLLED BY THE
 LCP.
 * THIS WAS ON PREVIOUS REVIEW
  
 3) NOTE: PLEASE CLARIFY LOAD FOR AHU, SHOWS 10KW AND
 12KW.
 PLEASE SEE THE PANEL SCHEDULE SHOWS BOTH? PLEASE
 CLARIFY THIS.
  
 4) NOTE: PLEASE PROVIDE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE SUBMITTED PANEL SCHEDULE(S). PLEASE
 SEE SOME MISSING FOR LIGHTING, RECEPTS.
 PLEASE SEE THERE ARE SEVERAL FIXTURES WHICH DO NOT
 INDICATE ANY CIRCUITING, CONTROL ETC AS STATED IN NOTE
 #2 ABOVE.
 PLEASE CORRELATE WITH THE SUBMITTED PANEL SCHEDULES.
 FBC 106.1.2, 106.3.5.1.2,NEC 408.4, 310.16 ETC
  
 5) NOTE: PLEASE SEE KITCHEN AREA WHICH WILL REQUIRE AN
 ADDITIONAL EMERGENCY LIGHTING FIXTURE FOR EGRESS.
 PLEASE SEE AREA REDLINED ON PLANS.
 LS 101 7.8, 7.9.
 PLEASE SEE 700.12 FOR CIRCUITING OF EMERGENCY LIGHT
 FOR NEW FIXTURE..
  
  
 6) NOTE: PLEASE SEE RISER WHICH HAS NOW BEEN REVISED
 SHOWS THE TWO METERS AND TWO MAINS FOR THE SAME
 TENANT?? THIS IS ONE TENANT AND THIS IS SHOWING MORE
 THAN ONE METER FOR THIS SINGLE SPACE. PLEASE SEE THAT
 ONLY ONE METER FOR TENANT SPACE IS PERMITTED. PLEASE
 SEE THIS METER CAN BE LARGER AND THEN EACH OF THE TWO
 MAINS AS SHOWN CAN BE TAPPED FROM THE LARGER SINGLE
 METER CAN. PLEASE CORRELATE RISER AND PANEL AS TWO
 DIFFERENT SIZES ARE SHOWN FOR PANEL *A*.
 PLEASE SEE BUILDING, ZONING FOR A SINGLE TENANT SERVED
 BY A SINGLE METER.
 PLEASE SEE 230.2.
 PLEASE PROVIDE MORE INFORMATION. FBC 106.1.2,
 106.3.5.1.2
  
 7) NOTE: PLEASE SEE 210.8B3 FOR GFP PROTECTION FOR ALL
 15/20A 120V RECEPTS IN KITCHEN/ KITCHEN AREAS.
 PLEASE SEE THESE WERE NOT CORRECTED.
  
 8) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE.
 THIS IS ONLY A NOTE GIVEN AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-02-11 19:21:152007-02-11 19:21:15
 REVIEW TO CONTINUE ON 2/12


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved