| Date |
Text |
| 2007-02-12 11:02:02 | ** UNSAT 2ND REVIEW ** |
| | |
| | 1) NOTE: PLEASE BE SURE ALL PLANS STATE THE FOLLOWING |
| | MINIMUM CODES IN WHICH PLANS ARE DESIGNED AND PERMITTED |
| | UNDER. |
| | PLEASE KNOW THE FOLLOWING WILL BE REQUIRED FOR |
| | ELECTRICAL SHEETS. |
| | 2002 NFPA-70 |
| | THE PREVIOUS NOTE ONLY MENTIONED PERMIT APPLICATIONS |
| | SUBMITTED AFTER THE DECEMBER 8TH 2006 DATE WOULD BE |
| | UNDER THE NEW CODES. |
| | PLEASE SEE THE PLANS STATE THE 2006 REVISIONS TO THE |
| | 2004 FBC AND STATE THE 2005 NEC. |
| | PLEASE CORRECT. |
| | |
| | 2) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1, |
| | .1.2 AND .1.3 |
| | PLEASE INDICATE SCHEDULING, OVER RIDE DEVICES AT |
| | INGRESS/EGRESS, SEPARATE SPACES, TIMES ON ALL OVER RIDE |
| | DEVICES. |
| | PLEASE SEE 13-415.1.AB.1, 13-415.2, AND 13-415.2.ABC.1 |
| | ENERGY CALCULATIONS ARE MISSING AND PERFORMANCE |
| | CALCULATIONS. |
| | PLEASE SEE THE LOCATION OF OVER RIDES SHALL ALSO BE |
| | LOCATED AS REQUIRED AT THE POINT OF INGRESS/EGRESS TO |
| | THE SPACE. THIS CAN BE DONE BY WAY OF OCCUPANCY SENSORS |
| | OR OVER RIDES SWITCH DEVICES. |
| | PLEASE SEE NOT TIMES ARE STATED ON PLANS FOR ANY |
| | DEVICES, OR SCHEDULING. |
| | PLEASE SEE THE SYMBOL LEGEND FOR DEVICES DOES NOT |
| | CORRELATE WITH THE SYMBOLS ON PLANS AND DOES NOT |
| | INDICATE OVER RIDE CONTROL. |
| | PLEASE SEE THE FIXTURE LEGEND DOES NOT CORRELATE WITH |
| | THE ENERGY CALCULATIONS AND THE ENERGY CALCULATIONS DO |
| | NOT CORRELATE WITH FIXTURES ON PLANS. THE AMOUNT OF |
| | FIXTURES ON PLANS IS SUBSTANTIALLY MORE THAN THE AMOUNT |
| | OF FIXTURES IN THE ENERGY CALCULATIONS. |
| | PLEASE SEE SOME LIGHTING CIRCUITS ON PLANS ALONG WITH |
| | FIXTURES DO NOT SHOW CONTROL OR HOW THEY ARE BEING |
| | CONNECTED OR CONTROLLED WHICH WILL AFFECT THE LIGHTING |
| | CONTROL PANEL AS STATED. |
| | PLEASE ALSO SEE COMMENT WITH RESPECT TO CONTROL AND |
| | CIRCUITS ON PLANS. |
| | PLEASE PROVIDE A PANEL SCHEDULE FOR THE LIGHTING |
| | CONTROL PANEL FOR ALL LIGHTING BEING CONTROLLED BY THE |
| | LCP. |
| | * THIS WAS ON PREVIOUS REVIEW |
| | |
| | 3) NOTE: PLEASE CLARIFY LOAD FOR AHU, SHOWS 10KW AND |
| | 12KW. |
| | PLEASE SEE THE PANEL SCHEDULE SHOWS BOTH? PLEASE |
| | CLARIFY THIS. |
| | |
| | 4) NOTE: PLEASE PROVIDE ALL CIRCUITING ON PLANS AND |
| | CORRELATE WITH THE SUBMITTED PANEL SCHEDULE(S). PLEASE |
| | SEE SOME MISSING FOR LIGHTING, RECEPTS. |
| | PLEASE SEE THERE ARE SEVERAL FIXTURES WHICH DO NOT |
| | INDICATE ANY CIRCUITING, CONTROL ETC AS STATED IN NOTE |
| | #2 ABOVE. |
| | PLEASE CORRELATE WITH THE SUBMITTED PANEL SCHEDULES. |
| | FBC 106.1.2, 106.3.5.1.2,NEC 408.4, 310.16 ETC |
| | |
| | 5) NOTE: PLEASE SEE KITCHEN AREA WHICH WILL REQUIRE AN |
| | ADDITIONAL EMERGENCY LIGHTING FIXTURE FOR EGRESS. |
| | PLEASE SEE AREA REDLINED ON PLANS. |
| | LS 101 7.8, 7.9. |
| | PLEASE SEE 700.12 FOR CIRCUITING OF EMERGENCY LIGHT |
| | FOR NEW FIXTURE.. |
| | |
| | |
| | 6) NOTE: PLEASE SEE RISER WHICH HAS NOW BEEN REVISED |
| | SHOWS THE TWO METERS AND TWO MAINS FOR THE SAME |
| | TENANT?? THIS IS ONE TENANT AND THIS IS SHOWING MORE |
| | THAN ONE METER FOR THIS SINGLE SPACE. PLEASE SEE THAT |
| | ONLY ONE METER FOR TENANT SPACE IS PERMITTED. PLEASE |
| | SEE THIS METER CAN BE LARGER AND THEN EACH OF THE TWO |
| | MAINS AS SHOWN CAN BE TAPPED FROM THE LARGER SINGLE |
| | METER CAN. PLEASE CORRELATE RISER AND PANEL AS TWO |
| | DIFFERENT SIZES ARE SHOWN FOR PANEL *A*. |
| | PLEASE SEE BUILDING, ZONING FOR A SINGLE TENANT SERVED |
| | BY A SINGLE METER. |
| | PLEASE SEE 230.2. |
| | PLEASE PROVIDE MORE INFORMATION. FBC 106.1.2, |
| | 106.3.5.1.2 |
| | |
| | 7) NOTE: PLEASE SEE 210.8B3 FOR GFP PROTECTION FOR ALL |
| | 15/20A 120V RECEPTS IN KITCHEN/ KITCHEN AREAS. |
| | PLEASE SEE THESE WERE NOT CORRECTED. |
| | |
| | 8) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. |
| | THIS IS ONLY A NOTE GIVEN AT THIS TIME. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-02-11 19:21:15 | 2007-02-11 19:21:15 |
| | REVIEW TO CONTINUE ON 2/12 |