Plan Review Notes
Plan Review Notes For Permit 06120139
Permit Number 06120139
Review Stop P
Sequence Number 1
Notes
Date Text
2007-01-12 15:09:50DENIED
 REFERENCE: FBC-2004 PLUMBING, FBC-2004 CHAPTER 1, AND
 FBC-2004 CHAPTER 11
  
 NOTE: SEPERATE PLUMBING AND GAS PERMITS REQUIRED FOR
 THIS JOB
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW:
  
 1. THE TWO COPIES OF PRINTS NEED TO BE STAMPED AND THE
 TWO PAGE WORK SHEETS NEED TO BE COMPLETED AND ATTACHED
 TO PRINTS BY DPBR HOTEL AND RESTAURANT DIVISION ON THE
 RESUBMITTAL AND PER FBC-2004 CHAPTER 1 SECTION
 102.2.1.
  
 2. SHEET 1.1 OF 9 INDICATES "NO GREASE TRAP- WAIVER
 FROM CITY OF WEST PALM BEACH"
 NOTE: PER WASTE ORDINANCE #3434 FOR THIS WAIVER PLEASE
 CONTACT
 ENVIRONMENTAL COMPLIANCE MANAGER
 LYNN MASSON (561) 822-2271
 FAX (561) 822-2279
 E-MAIL [email protected]
  
 3. SHEET 1.0 OF 9 THE MEN AND WOMENS BATHROOM: NOTE PER
 FBC-2004 PLUMBING SECTION 405.3.1 AND FBC-2004 CHAPTER
 11 SECTION 11-4.16 FIG. 28; BATHROOM IS TO SMALL THE
 MINIMUM FINNISH REQUIRED IS FIVE FEET THREE INCHES
 (5'-3") NOT THE INDICATED FIVE FEET TWO INCHES (5'-2")
 INDICATED. PLEASE CORRECT ON THE RESUBMITTAL.
  
 4. SHEET 3.0A OF 9 SANITARY RISER DIAGRAM: A} PER
 FBC-2004 PLUMBING, SECTION 901.2.1 A VENT IS REQUIRED
 FOR THE MOP SINK. PLEASE CORRECT ON THE RESUBMITTAL. B}
 PER FBC-2004 PLUMBING, SECTION 708.3.5 TWO WAY CLEANOUT
 REQUIRED. PLEASE ADD THESE FOR THE RESUBMITTAL.
  
 5. SHEET 3.0A OF 9 WATER RISER: A} ADD A WATER HAMMER
 ARRESTOR TO THE ICE MACHINE PER FBC-2004 PLUMBING,
 SECTION 604.9. B} DELETE 3/8" C INDICATED BETWEEN THE
 BATHROOM AND ICE MACHINE. C} PLEASE CORRELATE THE
 FIXTURES BEING SUPPLIED ON THE WATER RISER WITH SHEET
 1.1 OF 9, EQUIPMENT PLAN ITEM NUMBERS ON THE
 RESUBMITTAL.
  
 6. SHEET 3.0A OF 9 PLUMBING NOTES: A} NOTE #8 DELETE
 1/8" FT. MIN. AND ADD IN ITS PLACE TABLE 704.1. B} NOTE
 #12 DELETE AIR CHAMBER PER FBC-2004 PLUMBING SECTION
 604.9.
  
 7. SHEET 1.1 OF 9 ITEM #22 WAREWASHER DRAIN NEEDS TO BE
 INDICATED ON SHEET 3.0A SANITARY AND WATER RISER
 DIAGRAMS AND PLUMBING PLAN. PER WEST PALM BEACH CODE
 SECTION 90-124 (7) B. GREASE INTERCEPTERS (SEPERATORS,
 GREASE TRAPS) ARE TO BE INSTALLED OUTSIDE OF THE FOOD
 PREPERATION AREAWITH THE DISHWASHER DISCHARGING VIA A
 SEPERATE LINE.
 NOTE: THERE IS NO INDICATION ON THE PRINTS ON HOW THIS
 UNIT IS TO DRAIN, OR HOW ITIS SUPPLIED WITH WATER.
 THE UNIT MUST DRAIN INTO THE SANITARY SYSTEM SEPERATE
 FROM THE GREASE WASTE. PLEASE CLARIFY THIS ON THE
 RESUBMITTAL.
  
 8. SHEET 3.0A OF 9 WATER HEATER DETAIL SAFEY PAN:
 PLEASE INDICATE THE FOLLOWING PER FBC-2004 SECTION
 504.7.1 PAN DRAIN SIZE AND PER SECTION 504.7.2 DRAIN
 TERMINATION ON THE RESUBMITTAL.
  
 9. PLEASE NOTE ELECTRICAL COMMENT #3 ON TITLE BLOCK
 REFLECTING METRO DESIGN GROUP PER FS 471.023, 481.229,
 FAC 61G15-23.002 AND CORRECT ON THE RESUBMITTAL.
  
 10. PRINTS INDICATE GAS APPLIANCES, THE FOLLOWING
 INFORMATION IS REQUIRED FOR GAS PLAN REVIEW TO MEET
 CODE COMPLIANCE:
 A} SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 B} SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 C} TYPE OF GAS, (LP OR NATURAL)
 D} BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 E} SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 F} SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 G} INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 H} SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
 I} SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 J} CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 K} CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 L} EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 **********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721