| 2007-01-12 15:09:50 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING, FBC-2004 CHAPTER 1, AND |
| | FBC-2004 CHAPTER 11 |
| | |
| | NOTE: SEPERATE PLUMBING AND GAS PERMITS REQUIRED FOR |
| | THIS JOB |
| | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING |
| | PLAN REVIEW: |
| | |
| | 1. THE TWO COPIES OF PRINTS NEED TO BE STAMPED AND THE |
| | TWO PAGE WORK SHEETS NEED TO BE COMPLETED AND ATTACHED |
| | TO PRINTS BY DPBR HOTEL AND RESTAURANT DIVISION ON THE |
| | RESUBMITTAL AND PER FBC-2004 CHAPTER 1 SECTION |
| | 102.2.1. |
| | |
| | 2. SHEET 1.1 OF 9 INDICATES "NO GREASE TRAP- WAIVER |
| | FROM CITY OF WEST PALM BEACH" |
| | NOTE: PER WASTE ORDINANCE #3434 FOR THIS WAIVER PLEASE |
| | CONTACT |
| | ENVIRONMENTAL COMPLIANCE MANAGER |
| | LYNN MASSON (561) 822-2271 |
| | FAX (561) 822-2279 |
| | E-MAIL [email protected] |
| | |
| | 3. SHEET 1.0 OF 9 THE MEN AND WOMENS BATHROOM: NOTE PER |
| | FBC-2004 PLUMBING SECTION 405.3.1 AND FBC-2004 CHAPTER |
| | 11 SECTION 11-4.16 FIG. 28; BATHROOM IS TO SMALL THE |
| | MINIMUM FINNISH REQUIRED IS FIVE FEET THREE INCHES |
| | (5'-3") NOT THE INDICATED FIVE FEET TWO INCHES (5'-2") |
| | INDICATED. PLEASE CORRECT ON THE RESUBMITTAL. |
| | |
| | 4. SHEET 3.0A OF 9 SANITARY RISER DIAGRAM: A} PER |
| | FBC-2004 PLUMBING, SECTION 901.2.1 A VENT IS REQUIRED |
| | FOR THE MOP SINK. PLEASE CORRECT ON THE RESUBMITTAL. B} |
| | PER FBC-2004 PLUMBING, SECTION 708.3.5 TWO WAY CLEANOUT |
| | REQUIRED. PLEASE ADD THESE FOR THE RESUBMITTAL. |
| | |
| | 5. SHEET 3.0A OF 9 WATER RISER: A} ADD A WATER HAMMER |
| | ARRESTOR TO THE ICE MACHINE PER FBC-2004 PLUMBING, |
| | SECTION 604.9. B} DELETE 3/8" C INDICATED BETWEEN THE |
| | BATHROOM AND ICE MACHINE. C} PLEASE CORRELATE THE |
| | FIXTURES BEING SUPPLIED ON THE WATER RISER WITH SHEET |
| | 1.1 OF 9, EQUIPMENT PLAN ITEM NUMBERS ON THE |
| | RESUBMITTAL. |
| | |
| | 6. SHEET 3.0A OF 9 PLUMBING NOTES: A} NOTE #8 DELETE |
| | 1/8" FT. MIN. AND ADD IN ITS PLACE TABLE 704.1. B} NOTE |
| | #12 DELETE AIR CHAMBER PER FBC-2004 PLUMBING SECTION |
| | 604.9. |
| | |
| | 7. SHEET 1.1 OF 9 ITEM #22 WAREWASHER DRAIN NEEDS TO BE |
| | INDICATED ON SHEET 3.0A SANITARY AND WATER RISER |
| | DIAGRAMS AND PLUMBING PLAN. PER WEST PALM BEACH CODE |
| | SECTION 90-124 (7) B. GREASE INTERCEPTERS (SEPERATORS, |
| | GREASE TRAPS) ARE TO BE INSTALLED OUTSIDE OF THE FOOD |
| | PREPERATION AREAWITH THE DISHWASHER DISCHARGING VIA A |
| | SEPERATE LINE. |
| | NOTE: THERE IS NO INDICATION ON THE PRINTS ON HOW THIS |
| | UNIT IS TO DRAIN, OR HOW ITIS SUPPLIED WITH WATER. |
| | THE UNIT MUST DRAIN INTO THE SANITARY SYSTEM SEPERATE |
| | FROM THE GREASE WASTE. PLEASE CLARIFY THIS ON THE |
| | RESUBMITTAL. |
| | |
| | 8. SHEET 3.0A OF 9 WATER HEATER DETAIL SAFEY PAN: |
| | PLEASE INDICATE THE FOLLOWING PER FBC-2004 SECTION |
| | 504.7.1 PAN DRAIN SIZE AND PER SECTION 504.7.2 DRAIN |
| | TERMINATION ON THE RESUBMITTAL. |
| | |
| | 9. PLEASE NOTE ELECTRICAL COMMENT #3 ON TITLE BLOCK |
| | REFLECTING METRO DESIGN GROUP PER FS 471.023, 481.229, |
| | FAC 61G15-23.002 AND CORRECT ON THE RESUBMITTAL. |
| | |
| | 10. PRINTS INDICATE GAS APPLIANCES, THE FOLLOWING |
| | INFORMATION IS REQUIRED FOR GAS PLAN REVIEW TO MEET |
| | CODE COMPLIANCE: |
| | A} SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | B} SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | C} TYPE OF GAS, (LP OR NATURAL) |
| | D} BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | E} SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | F} SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. |
| | G} INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | H} SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. |
| | I} SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2 |
| | J} CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | K} CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| | PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | L} EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | |
| | **********IMPORTANT INFORMATION |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |