| Plan Review Notes For Permit 06120139 |
| Permit Number |
06120139 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-12-26 15:41:38 | *** DENIED *** | | | 1) PLEASE SUBMIT COOLING LOAD CALCULATIONS, PER 2004 | | | FBC 13-407.1.ABC.1. | | | | | | 2) PLEASE SHOW ON MECHANICAL PLANS BATHROOM EXHAUST FAN | | | (EF3) CFM'S. | | | | | | 3) ROOF PLAN PAGE 3.2A DOES NOT SHOW AN OSA INLET FOR | | | AHU #2, PLEASE CORRECT. | | | | | | 4) PAGE 3.2A SHOWS SF1 AS SF1& EF1, ALSO SHOWS SF2 AS | | | SF2 & EF2, PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|