Plan Review Notes
Plan Review Notes For Permit 06120139
Permit Number 06120139
Review Stop M
Sequence Number 1
Notes
Date Text
2006-12-26 15:41:38*** DENIED ***
 1) PLEASE SUBMIT COOLING LOAD CALCULATIONS, PER 2004
 FBC 13-407.1.ABC.1.
  
 2) PLEASE SHOW ON MECHANICAL PLANS BATHROOM EXHAUST FAN
 (EF3) CFM'S.
  
 3) ROOF PLAN PAGE 3.2A DOES NOT SHOW AN OSA INLET FOR
 AHU #2, PLEASE CORRECT.
  
 4) PAGE 3.2A SHOWS SF1 AS SF1& EF1, ALSO SHOWS SF2 AS
 SF2 & EF2, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.