| Date |
Text |
| 2007-02-16 16:59:49 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS AND CITY OF WEST PALM |
| | BEACH GAS PERMIT APPLICATION REQUIREMENTS. |
| | |
| | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN |
| | REVIEW ON THE RESUBMITTED GAS ISOMETRIC ON SHEET 3.OA: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | NOTE: THE SUBMITTED ISOMETRIC DOES NOT INDICATE ALL THE |
| | CORRESPONDING LENGTHS IN RELATION TO THE INDICATED CUT |
| | SECTIONS. PLEASE CORRECT AND RESUBMIT. |
| | |
| | 2. TYPE OF GAS, (LP OR NATURAL) |
| | NOTE: IT IS ASSUMED BY THE INFORMATION ON SHEET 3.0A |
| | GAS ISOMETRIC THAT THE GAS IS NATURAL BUT IT IS NOT |
| | INDICATED. PLEASE INDICATE THE GAS TYPE ON THE |
| | RESUBMITTAL. |
| | |
| | 3. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | NOTE: THE INDICATED DISTANCES OF 59' FOR THE 2 PSI AND |
| | 29' FOR THE 0.5 PSI CAN NOT BE VERIFIED UNTIL COMMENT |
| | NUMBER ONE IS COMPLETED. |
| | |
| | 4. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | NOTE: PLEASE INDICAE ON THE RESUBMITTED MANUFACTURER |
| | SHEETS THE MODEL NUMBER THAT CORRELATES WITH THE GAS |
| | LOAD CALCULATIONS ON SHEET 3.0A. THE FOLLOWING IS A |
| | LIST OF MANUFACTURER SHEETS THAT NEED CLARIFICATION. AN |
| | (OK) BY THE APPLIANCE MEANS THE SUBMITTAL IS |
| | ACCEPTABLE. |
| | |
| | A} WATER HEATER- NO MANUFACTURER SHEET SUBMITTED. |
| | |
| | B} PIZZA- SUBMITTED MAUFACTURER SHEET DOES NOT |
| | CORRELATE. |
| | |
| | C} PIZZA- SUBMITTED MANUFACTURER SHEET DOES NOT |
| | CORRELATE. |
| | |
| | D} RANGE- SUBMITTED MANUFACTURER SHEET DOES NOT |
| | CORRELATE. |
| | |
| | E} RANGE- SUBMITTED MANUFACTURER SHEET DOES NOT |
| | CORRELATE. |
| | |
| | F} CONVECTION OVEN- (OK) |
| | |
| | G} FRYER- (OK) |
| | |
| | H} FRYER- (OK) |
| | |
| | I} GRIDDLE- SUBMITTED MANUFACTURER SHEET DOES NOR |
| | CORRELATE. |
| | |
| | J} MP REGULATOR (PRV)- NO MANUFACTURER SHEET |
| | SUBMITTED. |
| | |
| | K} EMERGENCY HOOD SHUT DOWN VALVE- NO MANUFACTURER |
| | SHEET SUBMITTED. |
| | |
| | |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |