| 2007-01-05 17:05:11 | *****DENIED***** |
| | |
| | |
| | |
| | 1.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE |
| | PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED |
| | |
| | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT |
| | INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO THE |
| | PROPERTY OR VICINITY THEREOF (INCLUDING FIRE LANES). |
| | |
| | 4.COMBUSTIBLE WASTE MATERIAL, DUST, AND DEBRIS SHALL |
| | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR |
| | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| | |
| | 5.THE SCOPE OF WORK IS FOR THE ALTERATION TO CONVERT |
| | A COMMERCIAL STORE (MERCANTILE OCCUPANCY) TO A FOOD |
| | ESTABLISHMENT (ASSEMBLY OCCUPANCY).PLEASE BE ADVISED |
| | THAT THIS STRUCTURE SHALL BE CONSIDERED AS A NEW |
| | ASSEMBLY OCCUPANCY. |
| | |
| | 6.PANIC HARDWARE OR FIRE EXIT HARDWARE IS REQUIRED ON |
| | ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM AN AREA |
| | HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS. |
| | |
| | 7.PROVIDE LIFE SAFETY PLAN SHEET WHICH SHALL SHOW THE |
| | TRAVEL DISTANCE TO REACH AN EXIT.THE LOCATION OF EXIT |
| | LIGHTS, EMERGENCY LIGHTS, FIRE EXTINGUISHERS MAY ALSO |
| | BE INCLUDED. |
| | |
| | 8.WILL THE BUILDING/STRUCTURE BE EQUIPPED WITH A FIRE |
| | ALARM AND/OR FIRE SPRINKLER SYSTEM? |
| | |
| | 9.COMMERCIAL COOKING EQUIPMENT SHALL BE IN ACCORDANCE |
| | WITH NFPA 96.SEPARATE PLANS AND PERMIT WILL BE |
| | REQUIRED. |
| | |
| | 10. PROVIDE INTERIOR FINISH CLASSIFICATION FOR THE |
| | PROPOSED STRUCTURE.BE ADVISED THAT INTERIOR WALL AND |
| | CEILING FINISH MATERIALS SHALL BE CLASS A OR CLASS B IN |
| | EXITS AND EXIT ACCESS CORRIDORS.IN GERNERAL ASSEMBLY |
| | AREAS HAVING OCCUPANT LOADS OF 300 OR FEWER, INTERIOR |
| | WALL AND CEILING FINISH SHALL BE CLASS A, B, OR C. |
| | |
| | 11. SHOW/DISPLAY THE NUMERICAL ADDRESS ONTHE EXTERIOR |
| | ELEVATION THAT FRONTS NORTH DIXIE HIGHWAY.AS PER WEST |
| | PALM BEACH CODE, THE ADDRESS NUMBERS SHALL BE NO LESS |
| | THAN 6" IN HEIGHT AND 1" IN WIDTH. |
| | |
| | 12. SMOKING IN ASSEMBLY OCCUPANCIES SHALL BE REGULATED |
| | BY THE AUTHORITY HAVING JURISDICTION. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, |
| | INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH |
| | ITEM WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |