2007-01-05 17:05:11*****DENIED*****
  
  
  
 1.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE
 PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO THE
 PROPERTY OR VICINITY THEREOF (INCLUDING FIRE LANES).
  
 4.COMBUSTIBLE WASTE MATERIAL, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 5.THE SCOPE OF WORK IS FOR THE ALTERATION TO CONVERT
 A COMMERCIAL STORE (MERCANTILE OCCUPANCY) TO A FOOD
 ESTABLISHMENT (ASSEMBLY OCCUPANCY).PLEASE BE ADVISED
 THAT THIS STRUCTURE SHALL BE CONSIDERED AS A NEW
 ASSEMBLY OCCUPANCY.
  
 6.PANIC HARDWARE OR FIRE EXIT HARDWARE IS REQUIRED ON
 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM AN AREA
 HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS.
  
 7.PROVIDE LIFE SAFETY PLAN SHEET WHICH SHALL SHOW THE
 TRAVEL DISTANCE TO REACH AN EXIT.THE LOCATION OF EXIT
 LIGHTS, EMERGENCY LIGHTS, FIRE EXTINGUISHERS MAY ALSO
 BE INCLUDED.
  
 8.WILL THE BUILDING/STRUCTURE BE EQUIPPED WITH A FIRE
 ALARM AND/OR FIRE SPRINKLER SYSTEM?
  
 9.COMMERCIAL COOKING EQUIPMENT SHALL BE IN ACCORDANCE
 WITH NFPA 96.SEPARATE PLANS AND PERMIT WILL BE
 REQUIRED.
  
 10. PROVIDE INTERIOR FINISH CLASSIFICATION FOR THE
 PROPOSED STRUCTURE.BE ADVISED THAT INTERIOR WALL AND
 CEILING FINISH MATERIALS SHALL BE CLASS A OR CLASS B IN
 EXITS AND EXIT ACCESS CORRIDORS.IN GERNERAL ASSEMBLY
 AREAS HAVING OCCUPANT LOADS OF 300 OR FEWER, INTERIOR
 WALL AND CEILING FINISH SHALL BE CLASS A, B, OR C.
  
 11. SHOW/DISPLAY THE NUMERICAL ADDRESS ONTHE EXTERIOR
 ELEVATION THAT FRONTS NORTH DIXIE HIGHWAY.AS PER WEST
 PALM BEACH CODE, THE ADDRESS NUMBERS SHALL BE NO LESS
 THAN 6" IN HEIGHT AND 1" IN WIDTH.
  
 12. SMOKING IN ASSEMBLY OCCUPANCIES SHALL BE REGULATED
 BY THE AUTHORITY HAVING JURISDICTION.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722