Plan Review Notes
Plan Review Notes For Permit 06120139
Permit Number 06120139
Review Stop E
Sequence Number 1
Notes
Date Text
2007-01-04 19:14:02** UNSAT **
  
 1) NOTE: PLEASE BE SURE ALL PLANS STATE THE FOLLOWING
 MINIMUM CODES IN WHICH PLANS ARE DESIGNED AND PERMITTED
 UNDER.
 PLEASE KNOW THE FOLLOWING WILL BE REQUIRED FOR
 ELECTRICAL SHEETS.
 2002 NFPA-70 *JUST AS AN FYI AS OF 12/8/06 THE STATE OF
 FLORIDA ADOPTED THE NEW 2005 NEC AND ANY PERMIT
 APPLICATIONS MADE FROM THAT DATE FORWARD WILL BE UNDER
 THE NEW CODE AND THE 2006 REVISIONS TO THE 2004 FBC.
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE KNOW THIS IS A CHANGE IN OCCUPANCY WHICH
 REQUIRES ALL ELECTRICAL TO BE BROUGHT UP TO THE CURRENT
 TECHNICAL CODES.
  
 2) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1,
 .1.2 AND .1.3
 PLEASE INDICATE SCHEDULING, OVER RIDE DEVICES AT
 INGRESS/EGRESS, SEPARATE SPACES, TIMES ON ALL OVER RIDE
 DEVICES.
 PLEASE SEE 13-415.1.AB.1, 13-415.2, AND 13-415.2.ABC.1
 ENERGY CALCULATIONS ARE MISSING AND PERFORMANCE
 CALCULATIONS.
  
 3) NOTE: PLEASE SEE INFORMATION ON TITLE BLOCKS
 REFLECTS METRO DESIGN GROUP WHICH MUST BE LICENSED
 THROUGH THE STATE OF FLORIDA FOR PROVIDING ENGINEERING
 SERVICES.
 PLEASE SEE THAT THIS HAS BEEN NOTED ON PREVIOUS REVIEWS
 ON OTHER PROJECTS AND WILL BE DETERMINED FROM THE
 FLORIDA BOARD OF ENGINEERS. NO DETERMINATION HAS BEEN
 MADE AT THIS POINT IN TIME.
 FS 471.023, 481.229, FAC 61G15-23.002 ETC
 ONE SET OF PLANS ARE BEING RETAINED BY THIS OFFICE AT
 THIS TIME.
  
 4) NOTE: PLEASE SEE NFPA-96 AND CLARIFY ANY LIGHTING
 AND ELECTRICAL WHICH MAY BE PART OF THE HOOD SYSTEM
 WHICH IS REQUIRED TO BE SHUNT TRIP.
  
 5) NOTE: PLEASE CLARIFY LOAD FOR AHU, SHOWS 10KW AND
 12KW. PLEASE SEE 424.3B FOR MINIMUM OCP AT 125% IF
 12KW?
  
 6) NOTE: PLEASE SEE 220.12A FOR DETERMINING LOAD
 CALCULATIONS FOR SERVICE FEEDERS ON WINDOWS. PLEASE SEE
 QUOTED COMMENTARY.
 ?THE 200-VOLT-AMPERE CALCULATION FOR EACH LINEAR FOOT
 OF A SHOW WINDOW IS REQUIRED TO DETERMINE THE FEEDER
 LOAD. SEE THE COMMENTARY FOLLOWING 220.3(B)(7) FOR LOAD
 CALCULATIONS FOR BRANCH CIRCUITS IN SHOW WINDOWS.?
  
 7) NOTE: PLEASE PROVIDE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE SUBMITTED PANEL SCHEDULE(S). PLEASE
 SEE SOME MISSING FOR LIGHTING, RECEPTS AND ROOF TOP
 EQUIPMENT.
 FBC 106.1.2, 106.3.5.1.2,NEC 408.4, 310.16 ETC
  
 8) NOTE: PLEASE SEE 700.12 FOR CIRCUITING OF EMERGENCY
 AND EXIT LIGHTS.
  
 9) NOTE: PLEASE SEE THE TWO BATHROOMS AS SHOWN DO NOT
 SEEM TO INDICATE ANY ELECTRICAL. PLEASE KNOW THESE
 ROOMS WILL BE REQUIRED TO COMPLY WITH GFI PROTECTION
 FOR RECEPTS IF THEY ARE LOCATED IN THE BATHROOM AND
 ALSO WILL BE REQUIRED TO MEET FBC CHAPTER 13,
 13-415.1.ABC.1.2
  
 10) NOTE: PLEASE PROVIDE MORE INFORMATION FOR THE
 EXISTING SERVICE.PLEASE INDICATE THE EXISTING SERVICE
 ENTRANCE CONDUCTORS. 310.16, 240.4
 MUST MEET LOAD CALCULATIONS WHICH WILL ALSO BE NOTED TO
 BE SUPPLIED.
  
 11) NOTE: PLEASE SEE RISER AS SHOWN WHICH SHOWS THE TWO
 NEW METERS AS MAINS ONE OF TWO AND TWO OF TWO? PLEASE
 SEE THE RISER ALREADY SHOWS A MAIN.
 PLEASE SEE RISER ALSO SHOWS WHAT SOME BROKEN LINES
 WHICH WOULD INDICATE EXISTING APPEAR, YET THE RISER
 SEEMS TO SHOW ALL AS NEW? PLEASE SEE EVEN SERVICE NOTED
 AS EXISTING SEEMS TO BE NEW?
 PLEASE CLARIFY THE ENTIRE RISER FOR NEW AND EXISTING.
 FBC 106.1.2, 106.3.5.1.2
  
 12) NOTE: PLEASE SEE BASED ON THE EXISTING 600A SERVICE
 AS SHOWN, THE EXISTING GROUNDING ELECTRODE SHOULD BE
 VERIFIED FOR SIZE. PLEASE KNOW IN EITHER CASE IS THIS
 IS REALLY A #1 AS SHOWN THEN IT WILL BE REQUIRED TO BE
 BROUGHT UP TO CODE PER 250.66, IF LARGER THEN INDICATE
 THE EXITING SIZE MEETING CODE.
  
 13) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR
 THE EXISTING SERVICE AND THE NEW LOADS BEING ADDED.
 PLEASE SEE NEC 220,
 FBC ADMIN SECTION 106.1.2, 106.3.5.1.2
  
 14) NOTE: PLEASE SEE THE RISER SHOWS THE NEW SUB PANEL
 "B" BEING FED FROM THE NEW PANEL "A", YET THE PANEL "A"
 DOES NOT SHOW ANY BREAKER, OR IS LISTED ON THE PANEL
 SCHEDULE IN ANYWAY.
 408.4, 310.16, 240.4 ETC
 REVIEW CAN NOT BE DONE FOR THIS FOR CODE COMPLIANCE AT
 THIS TIME.
  
 15) NOTE: PLEASE INDICATE A "FLOATING NEUTRAL" FOR ALL
 METERS AFTER THE FIRST MEANS OF DISCONNECT. PLEASE SEE
 250.6, AND 250.24B.
  
 16) NOTE: PLEASE SEE SHOW ALL EQUIPMENT LOCATIONS ON
 PLANS. THE NOTE WHICH MENTIONS TO SEE COVER SHEET FOR
 LOCATIONS, DOES NOT PROVIDE ENOUGH INFORMATION. PLEASE
 SEE 240.24, 110.26, 408.7 ETC.
 NO REVIEW FOR CODE COMPLIANCE CAN BE DONE AT THIS
 TIME.
  
 17) NOTE: PLEASE SEE 210.8B3 FOR GFP PROTECTION FOR ALL
 15/20A 120V RECEPTS IN KITCHEN/ KITCHEN AREAS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-01-04 17:48:482007-01-04 17:48:48
 ELECTRICAL REVIEW IN PROGRESS.
2006-12-28 08:50:53CURRENTLY ON HOLD PER THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS.