| 2007-01-04 19:14:02 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE BE SURE ALL PLANS STATE THE FOLLOWING |
| | MINIMUM CODES IN WHICH PLANS ARE DESIGNED AND PERMITTED |
| | UNDER. |
| | PLEASE KNOW THE FOLLOWING WILL BE REQUIRED FOR |
| | ELECTRICAL SHEETS. |
| | 2002 NFPA-70 *JUST AS AN FYI AS OF 12/8/06 THE STATE OF |
| | FLORIDA ADOPTED THE NEW 2005 NEC AND ANY PERMIT |
| | APPLICATIONS MADE FROM THAT DATE FORWARD WILL BE UNDER |
| | THE NEW CODE AND THE 2006 REVISIONS TO THE 2004 FBC. |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | ** PLEASE KNOW THIS IS A CHANGE IN OCCUPANCY WHICH |
| | REQUIRES ALL ELECTRICAL TO BE BROUGHT UP TO THE CURRENT |
| | TECHNICAL CODES. |
| | |
| | 2) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1, |
| | .1.2 AND .1.3 |
| | PLEASE INDICATE SCHEDULING, OVER RIDE DEVICES AT |
| | INGRESS/EGRESS, SEPARATE SPACES, TIMES ON ALL OVER RIDE |
| | DEVICES. |
| | PLEASE SEE 13-415.1.AB.1, 13-415.2, AND 13-415.2.ABC.1 |
| | ENERGY CALCULATIONS ARE MISSING AND PERFORMANCE |
| | CALCULATIONS. |
| | |
| | 3) NOTE: PLEASE SEE INFORMATION ON TITLE BLOCKS |
| | REFLECTS METRO DESIGN GROUP WHICH MUST BE LICENSED |
| | THROUGH THE STATE OF FLORIDA FOR PROVIDING ENGINEERING |
| | SERVICES. |
| | PLEASE SEE THAT THIS HAS BEEN NOTED ON PREVIOUS REVIEWS |
| | ON OTHER PROJECTS AND WILL BE DETERMINED FROM THE |
| | FLORIDA BOARD OF ENGINEERS. NO DETERMINATION HAS BEEN |
| | MADE AT THIS POINT IN TIME. |
| | FS 471.023, 481.229, FAC 61G15-23.002 ETC |
| | ONE SET OF PLANS ARE BEING RETAINED BY THIS OFFICE AT |
| | THIS TIME. |
| | |
| | 4) NOTE: PLEASE SEE NFPA-96 AND CLARIFY ANY LIGHTING |
| | AND ELECTRICAL WHICH MAY BE PART OF THE HOOD SYSTEM |
| | WHICH IS REQUIRED TO BE SHUNT TRIP. |
| | |
| | 5) NOTE: PLEASE CLARIFY LOAD FOR AHU, SHOWS 10KW AND |
| | 12KW. PLEASE SEE 424.3B FOR MINIMUM OCP AT 125% IF |
| | 12KW? |
| | |
| | 6) NOTE: PLEASE SEE 220.12A FOR DETERMINING LOAD |
| | CALCULATIONS FOR SERVICE FEEDERS ON WINDOWS. PLEASE SEE |
| | QUOTED COMMENTARY. |
| | ?THE 200-VOLT-AMPERE CALCULATION FOR EACH LINEAR FOOT |
| | OF A SHOW WINDOW IS REQUIRED TO DETERMINE THE FEEDER |
| | LOAD. SEE THE COMMENTARY FOLLOWING 220.3(B)(7) FOR LOAD |
| | CALCULATIONS FOR BRANCH CIRCUITS IN SHOW WINDOWS.? |
| | |
| | 7) NOTE: PLEASE PROVIDE ALL CIRCUITING ON PLANS AND |
| | CORRELATE WITH THE SUBMITTED PANEL SCHEDULE(S). PLEASE |
| | SEE SOME MISSING FOR LIGHTING, RECEPTS AND ROOF TOP |
| | EQUIPMENT. |
| | FBC 106.1.2, 106.3.5.1.2,NEC 408.4, 310.16 ETC |
| | |
| | 8) NOTE: PLEASE SEE 700.12 FOR CIRCUITING OF EMERGENCY |
| | AND EXIT LIGHTS. |
| | |
| | 9) NOTE: PLEASE SEE THE TWO BATHROOMS AS SHOWN DO NOT |
| | SEEM TO INDICATE ANY ELECTRICAL. PLEASE KNOW THESE |
| | ROOMS WILL BE REQUIRED TO COMPLY WITH GFI PROTECTION |
| | FOR RECEPTS IF THEY ARE LOCATED IN THE BATHROOM AND |
| | ALSO WILL BE REQUIRED TO MEET FBC CHAPTER 13, |
| | 13-415.1.ABC.1.2 |
| | |
| | 10) NOTE: PLEASE PROVIDE MORE INFORMATION FOR THE |
| | EXISTING SERVICE.PLEASE INDICATE THE EXISTING SERVICE |
| | ENTRANCE CONDUCTORS. 310.16, 240.4 |
| | MUST MEET LOAD CALCULATIONS WHICH WILL ALSO BE NOTED TO |
| | BE SUPPLIED. |
| | |
| | 11) NOTE: PLEASE SEE RISER AS SHOWN WHICH SHOWS THE TWO |
| | NEW METERS AS MAINS ONE OF TWO AND TWO OF TWO? PLEASE |
| | SEE THE RISER ALREADY SHOWS A MAIN. |
| | PLEASE SEE RISER ALSO SHOWS WHAT SOME BROKEN LINES |
| | WHICH WOULD INDICATE EXISTING APPEAR, YET THE RISER |
| | SEEMS TO SHOW ALL AS NEW? PLEASE SEE EVEN SERVICE NOTED |
| | AS EXISTING SEEMS TO BE NEW? |
| | PLEASE CLARIFY THE ENTIRE RISER FOR NEW AND EXISTING. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 12) NOTE: PLEASE SEE BASED ON THE EXISTING 600A SERVICE |
| | AS SHOWN, THE EXISTING GROUNDING ELECTRODE SHOULD BE |
| | VERIFIED FOR SIZE. PLEASE KNOW IN EITHER CASE IS THIS |
| | IS REALLY A #1 AS SHOWN THEN IT WILL BE REQUIRED TO BE |
| | BROUGHT UP TO CODE PER 250.66, IF LARGER THEN INDICATE |
| | THE EXITING SIZE MEETING CODE. |
| | |
| | 13) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR |
| | THE EXISTING SERVICE AND THE NEW LOADS BEING ADDED. |
| | PLEASE SEE NEC 220, |
| | FBC ADMIN SECTION 106.1.2, 106.3.5.1.2 |
| | |
| | 14) NOTE: PLEASE SEE THE RISER SHOWS THE NEW SUB PANEL |
| | "B" BEING FED FROM THE NEW PANEL "A", YET THE PANEL "A" |
| | DOES NOT SHOW ANY BREAKER, OR IS LISTED ON THE PANEL |
| | SCHEDULE IN ANYWAY. |
| | 408.4, 310.16, 240.4 ETC |
| | REVIEW CAN NOT BE DONE FOR THIS FOR CODE COMPLIANCE AT |
| | THIS TIME. |
| | |
| | 15) NOTE: PLEASE INDICATE A "FLOATING NEUTRAL" FOR ALL |
| | METERS AFTER THE FIRST MEANS OF DISCONNECT. PLEASE SEE |
| | 250.6, AND 250.24B. |
| | |
| | 16) NOTE: PLEASE SEE SHOW ALL EQUIPMENT LOCATIONS ON |
| | PLANS. THE NOTE WHICH MENTIONS TO SEE COVER SHEET FOR |
| | LOCATIONS, DOES NOT PROVIDE ENOUGH INFORMATION. PLEASE |
| | SEE 240.24, 110.26, 408.7 ETC. |
| | NO REVIEW FOR CODE COMPLIANCE CAN BE DONE AT THIS |
| | TIME. |
| | |
| | 17) NOTE: PLEASE SEE 210.8B3 FOR GFP PROTECTION FOR ALL |
| | 15/20A 120V RECEPTS IN KITCHEN/ KITCHEN AREAS. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-01-04 17:48:48 | 2007-01-04 17:48:48 |
| | ELECTRICAL REVIEW IN PROGRESS. |
| 2006-12-28 08:50:53 | CURRENTLY ON HOLD PER THE FLORIDA BOARD OF PROFESSIONAL |
| | ENGINEERS. |