| 2007-01-08 08:25:29 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB |
| | FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO |
| | PERMIT PICKUP, FS713.13. |
| | |
| | 1.)INCLUDE FBC 2004 EXISTING BUILDING CODE IN THE |
| | GOVERNING CODE. |
| | |
| | 2.)DECLARE LEVEL OF ALTERATION, FBC EB CHAPTER 3. |
| | |
| | 3.)PROJECT IS TO COMPLY WITH FBC EB CHAPTER 8, CHANGE |
| | OF OCCUPANCY. |
| | |
| | 4.)DECLARE THE OCCUPANCY OF THE ADJACENT TENANT. |
| | CORRECT OCCUPANCY SEPARATION FBC TABLE 302.3.2 CANNOT |
| | BE DETERMINED WITHOUT THIS INFORMATION. |
| | |
| | 5.)BUILDING TYPE IIIB WAS DECLARED.SEE FBC TABLE |
| | 601, 2 HOUR MINIMUM FOR EXTERIOR WALLS REQUIRED. |
| | PROVIDE A SITE PLAN, SHOWING DISTANCE FROM THE PROPERTY |
| | LINE.SEE FBC TABLE 602 AND INDICATE MINIMUM EXTERIOR |
| | WALL FIRE RATING REQUIRED, FBC 704.8 REGARDING |
| | OPENINGS.PROVIDE DETAILS FOR FIRE RATED WALLS. |
| | |
| | 6.)AS THIS IS A CHANGE OF OCCUPANCY, COMPLIANCE WITH |
| | FBC TABLE 503.PROVIDE TOTAL AREA OF THE BUILDING. |
| | |
| | 7.)DECLARE OCCUPANT LOAD, FBC 3.PLANS STATE "NUMBER |
| | OF SEATS".SEE FBC 1004, KITCHEN AREA IS TO ALSO BE |
| | INCLUDED IN OCCUPANT LOAD. |
| | |
| | 8.)SHEET 1.0 SHOWS REFERENCE TO DETAILS ON SHEETS |
| | 1.2, THIS SHEET IS NOT IN THE PLAN. |
| | |
| | 9.)SHEET 1.0 SHOWS REFERENCE TO A DETAIL ON SHEET |
| | 1.1, THE DETAIL IS NOT ON THE PLAN. |
| | |
| | 10.)INTERIOR PARTITION DETAIL, 1.0, SHOWS FIRESTOP |
| | TYP IN THE TEXT, NOTHING SHOWN GRAPHICALLY. |
| | |
| | 11.)SHEET 1.0 STATES EXISTING BRICK 2 HR DEMISING |
| | WALL, STATES ONLY "13" BRICK 2 HR".PROVIDE MORE |
| | INFORMATION IN REGARDS TO THE WALL FBC TABLE 720.1(2). |
| | |
| | 12.)THERE APPEARS TO BE A WALL FROM THE ADJACENT |
| | TENANT WHICH PENETRATES THE EXISTING DEMISING WALL. |
| | PROVIDE INFORMATION IN REGARDS TO THIS WALL; SEPARATION |
| | TO BE MAINTAINED.IS THE SAME DETAIL TO BE USED?WALL |
| | GRAPHICALLY DOES NOT APPEAR TO BE THE SAME WALL AS THE |
| | EXISTING DEMISING WALL, CAN UL U408 STILL BE USED?IF |
| | NOT, PROVIDE A DETAIL FOR THIS WALL. |
| | |
| | 13.)PROVIDE ALL INFORMATION REQUIRED FOR UL U408 ON |
| | SHEET 1.THE DETAIL PROVIDED IS INCOMPLETE. |
| | |
| | 14.)SHOW ACCESSIBLE ROUTE FBC11-4.1.2(1), ACCESSIBLE |
| | PARKING. |
| | |
| | 15.)SHOW ACCESSIBLE ROUTE AT GLASS PIZZA DISPLAY. |
| | WHEN SCALED, THE SPACE BETWEEN THE BACK OF THE CHAIRS |
| | WHEN PUSHED UNDER THE TABLE TO THE DISPLAY CASE IS 12". |
| | SEE ALSO FBC1013. |
| | |
| | 16.)SHEET 3.1 REFERS TO THE WRONG BUILDING CODE |
| | (FBC2001). |
| | |
| | 17.)PROVIDE ROOF LOADING INFORMATION; DESIGN LOAD, |
| | NEW LOAD FOR MECHANICAL EQUIPMENT.THREE DIFFERENT |
| | CONDITIONS ARE SHOWN (STEEL, WOOD, CONCRETE), WHICH |
| | APPLIES TO THIS JOB? |
| | |
| | 18.)SHOW WORST CASE EXIT ACCESS TRAVEL DISTANCE, FBC |
| | TABLE 1015.1.NOTE THAT THERE ARE NO OVERALL |
| | DIMENSIONS ON THE FLOOR PLAN AND INCOMPLETE INTERIOR |
| | DIMENSIONS.INCLUDE OVERALL DIMENSIONS. |
| | |
| | 19.)SHOW DISTANCE BETWEEN THE TWO EXITS FBC |
| | 1014.2.1. |
| | |
| | 20.)SEE FBC 11-4.1(3), WORK AREAS SHALL BE DESIGNED |
| | SO THAT INDIVIDUALS CAN APPROACH, ENTER, AND EXIT THE |
| | AREAS.THE DOORS TO THE KITCHEN DO NOT COMPLY WITH |
| | FBC11-4.13. |
| | |
| | 21.)COUNTER LENGTH TO BE A MINIMUM OF 36", |
| | FBC11-7.2(1), 2'6" SHOWN 1.2A. |
| | |
| | 22.)SHOW ACCESSIBLE SEATING, FBC11-4.32. |
| | |
| | 23.)THE NOTE REGARDING THE SPECIFICATIONS BEING A |
| | GUIDE ONLY IS TOO VAGUE.SOME OF THE SPECIFICATIONS |
| | ARE REQUIRED BY CODE (COUNTER LENGTH/HEIGHT, WALL |
| | FINISH IN THE RESTROOMS, DETAILS REGARDING ACCESSIBLE |
| | SEATING, ETC.).THE NOTE STATES "MAY CHANGE WHERE CODE |
| | PERMITS"; HOW WILL THE CONTRACTOR IN THE FIELD KNOW |
| | WHERE CODE PERMITS?EITHER NOTE WHICH DETAILS MAY NOT |
| | BE CHANGED (OR REQUIRE A REVISION TO DETERMINE CODE |
| | COMPLIANCE) OR REMOVE THE NOTE FROM THE PLAN. |
| | |
| | 24.)MINIMUM INTERIOR FINISH CLASSIFICATION NOTE ON |
| | THE COVER SHEET IS CONFUSING.IN ONE PLACE ASSEMBLY IS |
| | HIGHLIGHTED WITH REQUIREMENTS FOR BOTH SPRINKLED AND |
| | UNSPRINKLED, INCLUDING INTERIOR FINISH A THROUGH C, BUT |
| | FLAME SPREAD GROUP A IS CHECKED.NOTE REQUIREMENTS FOR |
| | THIS PARTICULAR JOB, NOT GENERAL NOTES OUT OF THE CODE |
| | BOOK. |
| | |
| | 25.)IF THIS IS A SPRINKLED BUILDING, FIRE SPRINKLER |
| | PLANS REQUIRED PRIOR TO PERMITTING. |
| | |