2007-01-08 08:25:29****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB
 FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 1.)INCLUDE FBC 2004 EXISTING BUILDING CODE IN THE
 GOVERNING CODE.
  
 2.)DECLARE LEVEL OF ALTERATION, FBC EB CHAPTER 3.
  
 3.)PROJECT IS TO COMPLY WITH FBC EB CHAPTER 8, CHANGE
 OF OCCUPANCY.
  
 4.)DECLARE THE OCCUPANCY OF THE ADJACENT TENANT.
 CORRECT OCCUPANCY SEPARATION FBC TABLE 302.3.2 CANNOT
 BE DETERMINED WITHOUT THIS INFORMATION.
  
 5.)BUILDING TYPE IIIB WAS DECLARED.SEE FBC TABLE
 601, 2 HOUR MINIMUM FOR EXTERIOR WALLS REQUIRED.
 PROVIDE A SITE PLAN, SHOWING DISTANCE FROM THE PROPERTY
 LINE.SEE FBC TABLE 602 AND INDICATE MINIMUM EXTERIOR
 WALL FIRE RATING REQUIRED, FBC 704.8 REGARDING
 OPENINGS.PROVIDE DETAILS FOR FIRE RATED WALLS.
  
 6.)AS THIS IS A CHANGE OF OCCUPANCY, COMPLIANCE WITH
 FBC TABLE 503.PROVIDE TOTAL AREA OF THE BUILDING.
  
 7.)DECLARE OCCUPANT LOAD, FBC 3.PLANS STATE "NUMBER
 OF SEATS".SEE FBC 1004, KITCHEN AREA IS TO ALSO BE
 INCLUDED IN OCCUPANT LOAD.
  
 8.)SHEET 1.0 SHOWS REFERENCE TO DETAILS ON SHEETS
 1.2, THIS SHEET IS NOT IN THE PLAN.
  
 9.)SHEET 1.0 SHOWS REFERENCE TO A DETAIL ON SHEET
 1.1, THE DETAIL IS NOT ON THE PLAN.
  
 10.)INTERIOR PARTITION DETAIL, 1.0, SHOWS FIRESTOP
 TYP IN THE TEXT, NOTHING SHOWN GRAPHICALLY.
  
 11.)SHEET 1.0 STATES EXISTING BRICK 2 HR DEMISING
 WALL, STATES ONLY "13" BRICK 2 HR".PROVIDE MORE
 INFORMATION IN REGARDS TO THE WALL FBC TABLE 720.1(2).
  
 12.)THERE APPEARS TO BE A WALL FROM THE ADJACENT
 TENANT WHICH PENETRATES THE EXISTING DEMISING WALL.
 PROVIDE INFORMATION IN REGARDS TO THIS WALL; SEPARATION
 TO BE MAINTAINED.IS THE SAME DETAIL TO BE USED?WALL
 GRAPHICALLY DOES NOT APPEAR TO BE THE SAME WALL AS THE
 EXISTING DEMISING WALL, CAN UL U408 STILL BE USED?IF
 NOT, PROVIDE A DETAIL FOR THIS WALL.
  
 13.)PROVIDE ALL INFORMATION REQUIRED FOR UL U408 ON
 SHEET 1.THE DETAIL PROVIDED IS INCOMPLETE.
  
 14.)SHOW ACCESSIBLE ROUTE FBC11-4.1.2(1), ACCESSIBLE
 PARKING.
  
 15.)SHOW ACCESSIBLE ROUTE AT GLASS PIZZA DISPLAY.
 WHEN SCALED, THE SPACE BETWEEN THE BACK OF THE CHAIRS
 WHEN PUSHED UNDER THE TABLE TO THE DISPLAY CASE IS 12".
 SEE ALSO FBC1013.
  
 16.)SHEET 3.1 REFERS TO THE WRONG BUILDING CODE
 (FBC2001).
  
 17.)PROVIDE ROOF LOADING INFORMATION; DESIGN LOAD,
 NEW LOAD FOR MECHANICAL EQUIPMENT.THREE DIFFERENT
 CONDITIONS ARE SHOWN (STEEL, WOOD, CONCRETE), WHICH
 APPLIES TO THIS JOB?
  
 18.)SHOW WORST CASE EXIT ACCESS TRAVEL DISTANCE, FBC
 TABLE 1015.1.NOTE THAT THERE ARE NO OVERALL
 DIMENSIONS ON THE FLOOR PLAN AND INCOMPLETE INTERIOR
 DIMENSIONS.INCLUDE OVERALL DIMENSIONS.
  
 19.)SHOW DISTANCE BETWEEN THE TWO EXITS FBC
 1014.2.1.
  
 20.)SEE FBC 11-4.1(3), WORK AREAS SHALL BE DESIGNED
 SO THAT INDIVIDUALS CAN APPROACH, ENTER, AND EXIT THE
 AREAS.THE DOORS TO THE KITCHEN DO NOT COMPLY WITH
 FBC11-4.13.
  
 21.)COUNTER LENGTH TO BE A MINIMUM OF 36",
 FBC11-7.2(1), 2'6" SHOWN 1.2A.
  
 22.)SHOW ACCESSIBLE SEATING, FBC11-4.32.
  
 23.)THE NOTE REGARDING THE SPECIFICATIONS BEING A
 GUIDE ONLY IS TOO VAGUE.SOME OF THE SPECIFICATIONS
 ARE REQUIRED BY CODE (COUNTER LENGTH/HEIGHT, WALL
 FINISH IN THE RESTROOMS, DETAILS REGARDING ACCESSIBLE
 SEATING, ETC.).THE NOTE STATES "MAY CHANGE WHERE CODE
 PERMITS"; HOW WILL THE CONTRACTOR IN THE FIELD KNOW
 WHERE CODE PERMITS?EITHER NOTE WHICH DETAILS MAY NOT
 BE CHANGED (OR REQUIRE A REVISION TO DETERMINE CODE
 COMPLIANCE) OR REMOVE THE NOTE FROM THE PLAN.
  
 24.)MINIMUM INTERIOR FINISH CLASSIFICATION NOTE ON
 THE COVER SHEET IS CONFUSING.IN ONE PLACE ASSEMBLY IS
 HIGHLIGHTED WITH REQUIREMENTS FOR BOTH SPRINKLED AND
 UNSPRINKLED, INCLUDING INTERIOR FINISH A THROUGH C, BUT
 FLAME SPREAD GROUP A IS CHECKED.NOTE REQUIREMENTS FOR
 THIS PARTICULAR JOB, NOT GENERAL NOTES OUT OF THE CODE
 BOOK.
  
 25.)IF THIS IS A SPRINKLED BUILDING, FIRE SPRINKLER
 PLANS REQUIRED PRIOR TO PERMITTING.
  