| 2007-02-09 16:29:33 | *****DENIED***** |
| | |
| | |
| | 01.THE COMPLETE AND/OR ACTUAL ADDRESS OF THE PROJECT |
| | SITE SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN |
| | SHEET. |
| | |
| | 02.NFPA 101-2003 EDITION AND THE FLORIDA FIRE |
| | PREVENTION CODE SHALL BE REFERENCED. |
| | |
| | 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 04.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL |
| | NOT HINDER OR INTERFERE WITH EMERGENCY ACCESS RESPONSE |
| | TO THE SAID PROPERTY OR VICINITY THEREOF (INCLUDING |
| | FIRE HYDRANTS AND FIRE LANES). |
| | |
| | 05.ALL PAVEMENT ROAD SYSTEMS SHALL BE CAPABLE OF |
| | SUPPORTING 32 TONS FOR FIRE APPARATUS/EQUIPMENT. |
| | |
| | 06. FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN |
| | UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FEET AND AN |
| | UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13 |
| | FEET 6 INCHES. |
| | |
| | 07.LANDSCAPING SHALL NOT OBSTRUCT OR INTERFERE WITH |
| | FIRE PROTECTION EQUIPMENT.PROPER CLEARANCES SHALL BE |
| | MAINTAINED AT ALL TIMES. |
| | |
| | 08.INDICATE THE LOCATION OF THE FIRE HYDRANT(S) IN |
| | THE VICINITY OF THE SITE.BE ADVISED THAT IF THE |
| | HYDRANT(S) IS GREATER THAN 500 FEET, AN ADDITIONAL |
| | HYDRANT SHALL BE REQUIRED. |
| | |
| | 09.ON THE APPROPIATE EXTERIOR ELEVATION, SHOW/DISPLAY |
| | THE NUMERICAL ADDRESS FOR THE BUILDINGS TO BE VISIBLE |
| | FROM BROADWAY AVENUE.ONCE EMERGENCY RESPONDERS ARE |
| | INSIDE OF THE COMPLEX, HOW ARE BUILDINGS DISTINGUISHED |
| | FROM EACH OTHER. |
| | |
| | 10.IN ADDITION TO THE EXTERIOR ELEVATION DETAILS ON |
| | SHEET A5.2 AND A5.2, SPECIFY ELEVATIONS AS NORTH, EAST, |
| | WEST, AND SOUTH. |
| | |
| | 11.PLEASE INDICATE IF THIS BUILDING WILL BE EQUIPPED |
| | WITH A FIRE ALARM SYSTEM.BE ADVISED THAT SMOKE |
| | DETECTORS, AS LEGENDED ON SHEET E-1, ARE TIED INTO A |
| | FIRE ALARM SYSTEM.SMOKE ALARMS ON THE OTHER HAND ARE |
| | NOT TIED INTO A FIRE ALARM SYSTEM. |
| | |
| | 12.ON SHEET FS-6, PLEASE BE ADVISED THAT A 2 1/2" |
| | SINGLE INLET FIRE DEPARTMENT CONNECTION W/CHECK VALVE |
| | WILL BE REQUIRED. |
| | |
| | 13.ON SHEET FS-6, THE FIRE SPRINKLER SYSTEM IS TO BE |
| | MONITORED.IT SHALL BE PROVIDED WITH AN APPROVED ALARM |
| | INITIATION DEVICE THAT OPERATES WHEN THE FLOW OF WATER |
| | IS EQUAL OR GREATER THAN THAT FROM A SINGLE AUTOMATIC |
| | SPRINKLER. |
| | |
| | 14.IN REFERENCE TO THE HYDRAULIC CALCULATIONS THAT |
| | WERE SUBMITTED:3RD FLOOR UNIT-A SYSTEM 4, 3RD FLOOR |
| | UNIT-B SYSTEM 1, 3RD FLOOR UNIT-C SYSTEM 2, ALL SHOW AN |
| | UNACCEPTABLE SAFETY MARGIN.AS PER WPBFR, A SAFETY |
| | MARGIN OF AT LEAST 5.0 PSI IS REQUIRED. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |