| Plan Review Notes For Permit 06120107 |
| Permit Number |
06120107 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-12-27 10:50:33 | *****DENIED***** | | | | | | | | | | | | 1.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE | | | PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED. | | | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT | | | INTERFERE OR HINDER ACCESS TO OR EGRESS FROM OTHER | | | SUITES ON THE FLOOR OR THE BUILDING. | | | | | | 4.WILL THERE BE ADEQUATE VISIBILITY TOWARDS THE EXIT | | | SIGN LIGHT FROM THE FRONT DOOR OF THE #3 OFFICE?IF | | | NOT, AN ADDITIONAL EXIT LIGHT WILL BE REQUIRED. | | | | | | 5.IT IS STATED IN THE REFLECTED CEILING /LIGHTING | | | NOTE #9 THAT THE ENTIRE SPACE WILL BE FIRE SPRINKLED, | | | WHEREAS IN THE POWER PLAN NOTE #8 IT STATES "NO FIRE | | | ALARM AT THIS SPACE" ;HOW WILL THE FIRE SPRINKLER | | | SYSTEM BE MONITORED? | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|