2007-03-20 17:55:23****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBEXISTING BUILDING
 FBC R RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 FROM PREVIOUS REVIEW:
  
 _XX_5.FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG.NOT
 PROVIDED FOR THE INNOVATIVE PRODUCT.IF A FL APPROVAL
 IS NOT AVAILABLE, PLEASE ADVISE AND A LOCAL PRODUCT
 APPROVAL WILL BE ISSUED USING THE NOA.
  
 _XX_6.PROVIDE A FLOOR PLAN SHOWING ROOM
 DESIGNATIONS.NOTE EXISTING CONDITIONS (TYPE OF
 WINDOW) AND OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB
 505.1.TWO SETS REQUIRED.ONE FLOOR PLAN SUBMITTED AS
 WELL AS A LETTER AND A LIST OF BEDROOM WINDOWS; PLEASE
 SUBMIT TWO COMPLETE COLLATED SETS OF PERMIT DOCUMENTS.
 THE FLOOR PLAN IS WITH INNOVATIVE PRODUCT APPROVALS, NO
 FL PRODUCT APPROVAL, AND THE LETTERS REGARDING BEDROOM
 WINDOWS ARE SEPARATE.IT IS NOT CLEAR WHAT IS TO BE
 INCLUDED IN THE PERMIT PACKAGE.
  
 NEW COMMENTS:
  
 A.IF THE BEDROOM WINDOW #5 IS A HORIZONTAL ROLLER,
 37X39 ON THE FLOOR PLAN, HOW IS THE CLEAR OPENING
 50X17?#6 HAS A CLEAR OPENING OF 34X17, FLOOR PLAN IS
 53X51.ALL SIZES SHOULD BE WXH, OPENING SIZES DO NOT
 CORRELATE WITH WINDOW SIZES.
  
 B.ONE OF THE PAGES STATES THAT MULL BAR IS REQUIRED,
 BUT NO DOUBLE WINDOWS ARE SHOWN ON THE PLAN.SHOW THE
 DOUBLE WINDOW ON THE PLAN AND SUBMIT MULLION PRODUCT
 APPROVALS.
  
  