| Plan Review Notes For Permit 06120094 |
| Permit Number |
06120094 |
|
| Review Stop |
M |
| Sequence Number |
8 |
|
| Notes |
| Date |
Text |
| 2008-10-31 16:03:55 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | REVISION TO MECHANICAL PLANS | | | *** DENIED *** | | | | | | 1) THE ZONES FOR SYSTEM 1 AND 2 HAVE CHANGED, ALSO THE | | | SIZE OF SYSTEM 2 IS LARGER. THE COOLING LOAD | | | CALCULATIONS FOR ZONES 1 AND 2 NEED TO BE REVISED, PER | | | 2004 FBC 13-607.1.ABC.1. | | | | | | 2) THE SUPPLY AIR DUCT FROM AHU #3 TO THE MIXING BOX | | | AND FROM THAT MIXING BOX TO THE NEXT MIXING BOX, NEEDS | | | TO BE SIZED (SEE YELLOW HIGH LIGHT ON PLAN) PER 2004 | | | FBC/M 603.1 AND 603.2. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|