2008-10-31 16:03:55PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLANS
 *** DENIED ***
  
 1) THE ZONES FOR SYSTEM 1 AND 2 HAVE CHANGED, ALSO THE
 SIZE OF SYSTEM 2 IS LARGER. THE COOLING LOAD
 CALCULATIONS FOR ZONES 1 AND 2 NEED TO BE REVISED, PER
 2004 FBC 13-607.1.ABC.1.
  
 2) THE SUPPLY AIR DUCT FROM AHU #3 TO THE MIXING BOX
 AND FROM THAT MIXING BOX TO THE NEXT MIXING BOX, NEEDS
 TO BE SIZED (SEE YELLOW HIGH LIGHT ON PLAN) PER 2004
 FBC/M 603.1 AND 603.2.
  
 MECHANICAL PLAN REVIEW BY;