| 2007-03-26 12:21:18 | *** DENIED *** | | | 1) AS NOTED IN LAST REVIEW 12-16-07 NOTE #6. SEE | | | MECHANICAL PLANS PAGE M-1. THE 12" RETURN AIR TRANSFER | | | DUCT FROM THE PLAYROOM TO THE BREAKFAST AREA NEEDS TO | | | BE 14". | | | BALANCED RETURN AIR MAY BE ACHIEVED BY. | | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE | | | RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS | | | SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM OR SPACE IT'S SERVING TO ACHIEVE | | | PROPER RETURN AIR BALANCE. PER 2004 FBC/R M1602.4 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|