Review Stop M
Sequence Number 2
Notes
Date Text
2007-03-26 12:21:18*** DENIED ***
 1) AS NOTED IN LAST REVIEW 12-16-07 NOTE #6. SEE
 MECHANICAL PLANS PAGE M-1. THE 12" RETURN AIR TRANSFER
 DUCT FROM THE PLAYROOM TO THE BREAKFAST AREA NEEDS TO
 BE 14".
 BALANCED RETURN AIR MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING TO ACHIEVE
 PROPER RETURN AIR BALANCE. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.