| 2007-03-21 12:59:37 | |
| | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH REQUESTED THE |
| | AIC RATINGS FOR THE SERVICE EQUIPMENT AND PLANS NOW |
| | INDICATE THE RATINGS FOR THE PANELS ONLY. PLEASE |
| | INDICATE THE RATINGS FOR MAINS ALSO. |
| | 110.9 |
| | FBC 106.1.2 |
| | |
| | 2) NOTE: PLEASE SEE RISER WHICH SHOWS PANEL A-1 AS 100A |
| | AND PANEL A-1 WHICH IS SHOWN AS 150AMP. |
| | PLEASE CORRELATE. |
| | FBC 106.1.2 |
| | |
| | 3) NOTE: PLEASE SEE THAT THE IDENTIFICATION OF THE |
| | RECESSED LIGHTS WAS ADDED HOWEVER ONLY FOR THE IC |
| | RATING. PLEASE SEE THE SECTION AS STATED ALSO REQUIRES |
| | FIXTURES TO BE AIR TIGHT. |
| | FBC 13-606.1.ABC.1.2.4 |
| | |
| | 4) NOTE: PLEASE CLARIFY WHERE THE RECESSED LIGHTING IS |
| | FIGURED INTO THE LOAD CALCULATIONS AT THE MAXIMUM |
| | NUMBER OF FIXTURES TIME THE NUMBER OF FIXTURES? |
| | 220.3B4 |
| | |
| | 5) NOTE: PLEASE SEE THE PANEL SCHEDULE WHICH STILL LIST |
| | MANY CIRCUITS AS *GENERAL*. |
| | PLEASE SEE THE FOLLOWING TEXT WHICH IS EXTRACTED FROM |
| | THE NEC COMMENTARY FOR 408.4. |
| | |
| | *CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY |
| | CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE |
| | LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR |
| | WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME |
| | PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR |
| | EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY |
| | OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN |
| | COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL |
| | APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD, |
| | THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL |
| | RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR |
| | ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.'' |
| | CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH |
| | ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE |
| | SUFFICIENT DETAIL REQUIRED BY THIS SECTION.* |
| | PLEASE KNOW IF THIS WAS THE ONLY COMMENT THIS COULD |
| | HAVE BEEN REVISED, HOWEVER PLEASE INDICATE THE |
| | ESTIMATED LOCATIONS AT THIS TIME PER DESIGNER. IT IS |
| | KNOWN THAT THESE WILL MOST LIKELY BE INSTALLED |
| | DIFFERENTLY AND MAY BE REVISED AT A LATER DATE. |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.3.5.4 |
| | |
| | |
| | ** PLEASE KNOW THAT SOME OF THESE COMMENTSWERE MADE |
| | FROM THE PREVIOUS REVIEW AND SOME MAY HAVE BEEN |
| | REDLINED OR SET UP AS A PROVISO, HOWEVER SOME CAN NOT. |
| | PLEASE ADDRESS ALL AT THIS TIME AND IF THERE ARE ANY |
| | COMMENTS, QUESTIONS, PLEASE CALL TO GO OVER. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |