Plan Review Notes
Plan Review Notes For Permit 06120094
Permit Number 06120094
Review Stop E
Sequence Number 2
Notes
Date Text
2007-03-21 12:59:37 
 ** UNSAT **
  
 1) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH REQUESTED THE
 AIC RATINGS FOR THE SERVICE EQUIPMENT AND PLANS NOW
 INDICATE THE RATINGS FOR THE PANELS ONLY. PLEASE
 INDICATE THE RATINGS FOR MAINS ALSO.
 110.9
 FBC 106.1.2
  
 2) NOTE: PLEASE SEE RISER WHICH SHOWS PANEL A-1 AS 100A
 AND PANEL A-1 WHICH IS SHOWN AS 150AMP.
 PLEASE CORRELATE.
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE THAT THE IDENTIFICATION OF THE
 RECESSED LIGHTS WAS ADDED HOWEVER ONLY FOR THE IC
 RATING. PLEASE SEE THE SECTION AS STATED ALSO REQUIRES
 FIXTURES TO BE AIR TIGHT.
 FBC 13-606.1.ABC.1.2.4
  
 4) NOTE: PLEASE CLARIFY WHERE THE RECESSED LIGHTING IS
 FIGURED INTO THE LOAD CALCULATIONS AT THE MAXIMUM
 NUMBER OF FIXTURES TIME THE NUMBER OF FIXTURES?
 220.3B4
  
 5) NOTE: PLEASE SEE THE PANEL SCHEDULE WHICH STILL LIST
 MANY CIRCUITS AS *GENERAL*.
 PLEASE SEE THE FOLLOWING TEXT WHICH IS EXTRACTED FROM
 THE NEC COMMENTARY FOR 408.4.
  
 *CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.*
 PLEASE KNOW IF THIS WAS THE ONLY COMMENT THIS COULD
 HAVE BEEN REVISED, HOWEVER PLEASE INDICATE THE
 ESTIMATED LOCATIONS AT THIS TIME PER DESIGNER. IT IS
 KNOWN THAT THESE WILL MOST LIKELY BE INSTALLED
 DIFFERENTLY AND MAY BE REVISED AT A LATER DATE.
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
  
 ** PLEASE KNOW THAT SOME OF THESE COMMENTSWERE MADE
 FROM THE PREVIOUS REVIEW AND SOME MAY HAVE BEEN
 REDLINED OR SET UP AS A PROVISO, HOWEVER SOME CAN NOT.
 PLEASE ADDRESS ALL AT THIS TIME AND IF THERE ARE ANY
 COMMENTS, QUESTIONS, PLEASE CALL TO GO OVER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]