Plan Review Notes
Plan Review Notes For Permit 06120094
Permit Number 06120094
Review Stop B
Sequence Number 2
Notes
Date Text
2007-04-10 18:59:00BUILDING REVIEW SECOND CHECKLIST:
 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTE.
  
 2- PROVIDE COPY OF IMPACT FEES PAID RECEIPT AS
 REQUESTED ON PREVIOUS CHECKLIST.
  
 3- FLAT ROOF NOA #04-0506.03:
 A) SPECIFY ON SHEET 16WHICH FASTENING OPTION IS
 GOING TO BE USED AS REQUIRED BY CITY POLICY FOR ROOFING
 PERMITS. SEE ATTACHED COPY.
  
 B) PROVIDE RAS 117 CALCULATIONS OR NAIL ENHANCING
 FOR PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7. SEE PAGE 19 OF NOA SUBMITTED.
  
 4-DESIGNER OF RECORD NEED TO SPECIFY CONCRETE TILE
 SPECIFIC FASTENING AS REQUIRED BY SEC. 106.1.1.2 OF
 CITY AMENDMENTS TO FBC 2004. PRODUCT APPROVAL IS ONLY
 TO VERIFY THAT PRODUCT MEETS DESIGNER OF RECORDDESIGN
 CRITERIA.
  
 5- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72
 FOR:
 A) POCKET FRENCH SLIDING GLASS DOORS AS SHOWN ON
 PLANS.NOA #02-0306.01 SUBMITTED IS NOT FOR POCKET
 DOORS AND DOOR IS SMALLER THAN SIZE SPECIFIED ON PLANS.
 THEREFORE, IT DOESN'T WORK FOR THIS HOUSE.
  
 B) 3'-6" X 8'-0" INSWING ENTRY DOOR AS SHOWN ON
 PLANS.NOA #02-0129.10 SUBMITTED DOOR IS SMALLER THAN
 SIZE SPECIFIED ON PLANS AND NOA IS EXPIRED ALSO.
  
 C) FIXED WINDOWS. NOA #03-0428.03 SUBMITTED IS
 SUPERSEDED ACCORDING TO DADE COUNTY PRODUCT APPROVAL
 WEBSITE. SEE ATTACHED COPY. NEED CURRENT NOA.
  
 6- DESIGNEROF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALSAS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
 ***NOTE: DESIGNEROF RECORD TO MAKE SURE PRODUCT
 APPROVALS COVERTYPE AND SIZE OF PRODUCT SPECIFIED ON
 PLANS AND IS NOT EXPIRED TO AVOID FURTHER DENIALS AND
 EXPEDITE THE REVIEW PROCESS.
  
 7- PROVIDE COMPLETE SPECIFICATIONS AND UL LISTING FOR
 BBQ DESIGNED TO BE INSTALLED IN THE LOGGIA. OTHERWISE,
 DELETE FROM DRAWINGS AND APPLY FOR SUCH PERMIT AT TIME
 OF INSTALLATION.
  
 8- REVISE ALL SECTIONS/DETAILS THAT SHOW CORRECT RAIN
 DOWNSPOUTS TO COMPLY WITH SEC. R320.7 2004 FLORIDA
 RESIDENTIAL CODE.ILLUSTRATED RAIN LEADERS ARE NOT
 SHOWN CORRECTLY.
  
 9- CONNECTORS P AND O SHOWN ON SHEETS-2DON'T MEET
 THE UPLIFT LOADS SPECIFIED ON PLANS. REVISE/CLARIFY AS
 REQUIRED.
  
 10- SHEET S-4:
 A) CLARIFY GRAVITY LOADS. WHY ATTIC LIVE LOAD FOR
 ATTIC WITHOUT STORAGE IS NONCONCURRENT, WHILE ATTIC
 LIVE LOAD WITH STORAGE IS CONCURRENT. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 11- SOIL TEST REPORTTO HAVE ORIGINALENGINEER'S
 SIGNATURE,DATE AND THE ENGINEERING FIRM'S CERTIFICATE
 OF AUTHORIZATION NUMBER AS REQUIRED BY CHAPTER 471 AND
 FLORIDA ADMINISTRATIVE CODE SEC. 61G15-23.002.
  
 12-A) SURVEY TO HAVE ORIGINAL SIGNATURE, NOT COPY AS
 REQUIRED BY CHAPTER 472 FLORIDA STATUTE.
 B) PROVIDE COMPLETE INFORMATION FOR FLOOD MAP,
 INCLUDING DATE OF MAP (MARCH 1ST. 1979).
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  