| 2007-04-10 18:59:00 | BUILDING REVIEW SECOND CHECKLIST: |
| | 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED |
| | BY SEC. 713.13 FLORIDA STATUTE. |
| | |
| | 2- PROVIDE COPY OF IMPACT FEES PAID RECEIPT AS |
| | REQUESTED ON PREVIOUS CHECKLIST. |
| | |
| | 3- FLAT ROOF NOA #04-0506.03: |
| | A) SPECIFY ON SHEET 16WHICH FASTENING OPTION IS |
| | GOING TO BE USED AS REQUIRED BY CITY POLICY FOR ROOFING |
| | PERMITS. SEE ATTACHED COPY. |
| | |
| | B) PROVIDE RAS 117 CALCULATIONS OR NAIL ENHANCING |
| | FOR PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL |
| | LIMITATION #7. SEE PAGE 19 OF NOA SUBMITTED. |
| | |
| | 4-DESIGNER OF RECORD NEED TO SPECIFY CONCRETE TILE |
| | SPECIFIC FASTENING AS REQUIRED BY SEC. 106.1.1.2 OF |
| | CITY AMENDMENTS TO FBC 2004. PRODUCT APPROVAL IS ONLY |
| | TO VERIFY THAT PRODUCT MEETS DESIGNER OF RECORDDESIGN |
| | CRITERIA. |
| | |
| | 5- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72 |
| | FOR: |
| | A) POCKET FRENCH SLIDING GLASS DOORS AS SHOWN ON |
| | PLANS.NOA #02-0306.01 SUBMITTED IS NOT FOR POCKET |
| | DOORS AND DOOR IS SMALLER THAN SIZE SPECIFIED ON PLANS. |
| | THEREFORE, IT DOESN'T WORK FOR THIS HOUSE. |
| | |
| | B) 3'-6" X 8'-0" INSWING ENTRY DOOR AS SHOWN ON |
| | PLANS.NOA #02-0129.10 SUBMITTED DOOR IS SMALLER THAN |
| | SIZE SPECIFIED ON PLANS AND NOA IS EXPIRED ALSO. |
| | |
| | C) FIXED WINDOWS. NOA #03-0428.03 SUBMITTED IS |
| | SUPERSEDED ACCORDING TO DADE COUNTY PRODUCT APPROVAL |
| | WEBSITE. SEE ATTACHED COPY. NEED CURRENT NOA. |
| | |
| | 6- DESIGNEROF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ALL PRODUCT APPROVALSAS REQUIRED BY SEC. 106.3.3 CITY |
| | AMENDMENTS TO FBC 2004. |
| | ***NOTE: DESIGNEROF RECORD TO MAKE SURE PRODUCT |
| | APPROVALS COVERTYPE AND SIZE OF PRODUCT SPECIFIED ON |
| | PLANS AND IS NOT EXPIRED TO AVOID FURTHER DENIALS AND |
| | EXPEDITE THE REVIEW PROCESS. |
| | |
| | 7- PROVIDE COMPLETE SPECIFICATIONS AND UL LISTING FOR |
| | BBQ DESIGNED TO BE INSTALLED IN THE LOGGIA. OTHERWISE, |
| | DELETE FROM DRAWINGS AND APPLY FOR SUCH PERMIT AT TIME |
| | OF INSTALLATION. |
| | |
| | 8- REVISE ALL SECTIONS/DETAILS THAT SHOW CORRECT RAIN |
| | DOWNSPOUTS TO COMPLY WITH SEC. R320.7 2004 FLORIDA |
| | RESIDENTIAL CODE.ILLUSTRATED RAIN LEADERS ARE NOT |
| | SHOWN CORRECTLY. |
| | |
| | 9- CONNECTORS P AND O SHOWN ON SHEETS-2DON'T MEET |
| | THE UPLIFT LOADS SPECIFIED ON PLANS. REVISE/CLARIFY AS |
| | REQUIRED. |
| | |
| | 10- SHEET S-4: |
| | A) CLARIFY GRAVITY LOADS. WHY ATTIC LIVE LOAD FOR |
| | ATTIC WITHOUT STORAGE IS NONCONCURRENT, WHILE ATTIC |
| | LIVE LOAD WITH STORAGE IS CONCURRENT. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | 11- SOIL TEST REPORTTO HAVE ORIGINALENGINEER'S |
| | SIGNATURE,DATE AND THE ENGINEERING FIRM'S CERTIFICATE |
| | OF AUTHORIZATION NUMBER AS REQUIRED BY CHAPTER 471 AND |
| | FLORIDA ADMINISTRATIVE CODE SEC. 61G15-23.002. |
| | |
| | 12-A) SURVEY TO HAVE ORIGINAL SIGNATURE, NOT COPY AS |
| | REQUIRED BY CHAPTER 472 FLORIDA STATUTE. |
| | B) PROVIDE COMPLETE INFORMATION FOR FLOOD MAP, |
| | INCLUDING DATE OF MAP (MARCH 1ST. 1979). |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |
| | |