| 2006-12-11 15:33:28 | *** DENIED *** |
| | 1) THE MECHANICAL PLANS NEEDS THE ARCHITECT'S SEAL ON |
| | THEM AS HIS INFORMATION IS IN THE TITLE BLOCK, PER FAC |
| | 61G1-16.003. |
| | |
| | 2) SEE ELECTRICAL REVIEW NOTE #15, PLEASE CORRECT. |
| | |
| | 3) SEE PAGE M-2 SECOND FLOOR, SHOWER ROOM BETWEEN THE |
| | TWO BEDROOMS NEEDS AN EXHAUST FAN, SEE 2004 FBC/R |
| | M1506.1. |
| | |
| | 4) RETURN AIR DUCT TO AHU #3 NEEDS TO BE SIZED, SEE |
| | HIGH LIGHT ON PAGE M-2. |
| | |
| | 5) TWO RETURN AIR DUCTS TO AHU #1 NEED TO BE SIZED |
| | (PLEASE DO NOT USE PENCIL). |
| | |
| | 6) 12" RETURN AIR TRANSFER DUCT FROM PLAYROOM TO |
| | BREAKFAST AREA NEEDS TO BE 14". BALANCED RETURN AIR MAY |
| | BE ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| | INCREASING THE RETURN TRANSFER ONE AND |
| | ONE HALF TIMES THE CROSS SECTIONAL AREA |
| | (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING |
| | AND THE DOOR HAVING AT LEAST AN |
| | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| | PROPER RETURN AIR BALANCE. |
| | (B)TRANSFER GRILLES SHALL USE 50 |
| | SQUARE INCHES (OF GRILLE AREA) TO 100 |
| | CFM (OF SUPPLY AIR) FOR SIZING |
| | THROUGH-THE-WALL TRANSFER GRILLES AND |
| | USING AN UNRESTRICTED 1-INCH |
| | UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| | RETURN AIR BALANCE |
| | (C)HABITABLE ROOMS ONLY SHALL BE |
| | REQUIRED TO MEET THESE REQUIREMENTS FOR |
| | PROPER BALANCED RETURN AIR EXCLUDING |
| | BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| | AIR INTO THE MASTER SUITE SHALL BE |
| | INCLUDED. PER 2004 FBC/R M1602.4 . |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |