2006-12-11 15:33:28*** DENIED ***
 1) THE MECHANICAL PLANS NEEDS THE ARCHITECT'S SEAL ON
 THEM AS HIS INFORMATION IS IN THE TITLE BLOCK, PER FAC
 61G1-16.003.
  
 2) SEE ELECTRICAL REVIEW NOTE #15, PLEASE CORRECT.
  
 3) SEE PAGE M-2 SECOND FLOOR, SHOWER ROOM BETWEEN THE
 TWO BEDROOMS NEEDS AN EXHAUST FAN, SEE 2004 FBC/R
 M1506.1.
  
 4) RETURN AIR DUCT TO AHU #3 NEEDS TO BE SIZED, SEE
 HIGH LIGHT ON PAGE M-2.
  
 5) TWO RETURN AIR DUCTS TO AHU #1 NEED TO BE SIZED
 (PLEASE DO NOT USE PENCIL).
  
 6) 12" RETURN AIR TRANSFER DUCT FROM PLAYROOM TO
 BREAKFAST AREA NEEDS TO BE 14". BALANCED RETURN AIR MAY
 BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.