Plan Review Notes
Plan Review Notes For Permit 06120094
Permit Number 06120094
Review Stop E
Sequence Number 1
Notes
Date Text
2006-12-06 09:16:04**** UNSAT ****
  
 1) NOTE: PLEASE SEE THAT PLANS SHALL STATE THE
 FOLLOWING MINIMUM CODES.
 2002 NFPA-70 (NEC), 2002 NFPA-72.
  
 2) NOTE: PLEASE INDICATE THE MINIMUM AIC RATINGS FOR
 ALL SERVICE EQUIPMENT. IT IS NOTED THAT THE SUB PANELS
 INDICATE 10K , HOWEVER MAINS SHOULD CONTAIN THE MINIMUM
 RATINGS ALSO.
 PLEASE SEE 110.9 FBC 106.1.2 ADMIN SECTION.
  
 3) NOTE: PLEASE SEE PLANS INDICATE A/F PROTECTION AS
 EACH RECEPTACLE, HOWEVER BASED ON THE CODE AS STATED ON
 E-3 AND IN 210.12B, THE PROTECTION IS FOR THE BRANCH
 CIRCUIT. PLEASE KNOW IT IS NOT KNOWN TO THIS OFFICE AT
 THIS TIME THAT A AF TYPE RECEPT IS MANUFACTURED.
  
 4) NOTE: PLEASE INDICATE THE GFI PROTECTION FOR THE
 JACUZZI/WHIRLPOOL TUB. 680.71
  
 5) NOTE: PLEASE SEE MISSING RECEPTS PER 210.52. (2FT OF
 WALL IN BEDROOM #2 REDLINED).
 PLEASE CHECK OTHER LOCATIONS, HOWEVER PLANS SEEM TO
 INDICATE ALL REQUIRED.
  
 6) NOTE: PLEASE SEE 210.52C3 FOR MISSING PENINSULAR GFI
 RECEPTACLE REQUIRED. (REDLINED)
  
 7) NOTE: PLEASE SEE NFPA-72 FOR DEFINITIONS OF SMOKE
 DEVICES IN A DWELLING. PLEASE KNOW IN A RECENT SECTION
 MEETING WITH NFPA, THE DESIGNATION OF THESE DEVICES
 SHOULD BE AS FOLLOWS. PLEASE KNOW IF THE DEVICE IS 120V
 WHICH DETECTS AND SOUNDS AND ALARM, THEN THIS DEVICE
 WOULD ACTUALLY NOW BE SHOWN A "SA" FOR SMOKE ALARM. IF
 THE DEVICE IS LOW VOLTAGE AND PART OF ALV SECURITY OR
 LV FIRE ALARM SYSTEM , THEN DEVICE WOULD BE ONLY A "SD"
 FOR SMOKE DETECTOR AS IT ONLY DETECTS AND WILL CAUSE
 AND ALARM THROUGH OTHER SOUNDING DEVICES. PLEASE KNOW
 THAT SD HAS BEEN THE ACCEPTED PRACTICE FOR MANY YEARS
 THROUGH THIS AHJ, HOWEVER AS OF RECENT INFORMATION IF
 INDEED THESE DEVICES ARE 120V SMOKE ALARMS, PLEASE
 CHANGE THE DESIGNATIONS ON PLANS, NOTES AND SYMBOL
 LEGEND.
  
 8) NOTE: PLEASE ADJUST NOTES PERTAINING TO THE RELEVANT
 CODES. PLEASE SEE NFPA-72 11.5.1.1 AND 11.8.3 DICTATES
 THE PLACEMENT.
 PLEASE SEE THAT THE SA DEVICE SHALL BE LOCATED WITHIN
 12INCHES OF THE HIGHEST POINT ON A FLAT/TRAY CEILING
 AND WITHIN 3FT ON SLOPED ONLY CEILING. PLEASE KNOW, IF
 THE TRAY IS 12INCHES OR MORE IN DEPTH, THE SA DEVICE
 SHALL BE RELOCATED.
  
 9) NOTE: PLEASE SEE AREA AT THE TOP OF THE STAIRS WHICH
 SHOWS ONLY ONE SMOKE DEVICE. PLEASE KNOW DUE TO THE
 DISTANCE AND LOCATION SHOWN, PLEASE EITHER ADD ONE UNIT
 OR MOVE THE EXISTING TO BE CLOSER AND IN MORE OF THE
 IMMEDIATE VICINITY OUTSIDE BEDROOMS #3 AND MASTER
 BEDROOM.
 NFPA-72 11.5.1.1
  
 10) NOTE: PLEASE SEE ANY POSSIBLE ZONING COMMENTS FOR
 ANY CHANGES OR ACCESS REQUIREMENTS FOR THE GUEST SUITE
 LOCATED IN THE REAR. PLEASE KNOW THESE COMMENTS MAY OR
 MAY NOT AFFECT THE ELECTRICAL PLANS GREATLY.
  
 11) NOTE: PLEASE INDICATE THE ACTUAL RATING OF THE
 METER MAIN COMBO. PLEASE ALSO SHOW THIS E-1 PLAN
 LAYOUT.
 PLEASE SEE MISSING PANEL A-1 ON PLANS. THIS SUB PANEL
 COULD NOT LOCATED ON LOWER OR UPPER FLOORS. PLEASE SEE
 110.26,240.24 ETC
 FBC 106.1.2 ADMIN SECTION.
  
 12) NOTE: PLEASE SEE PANEL SCHEDULES FOR BRANCH
 CIRCUITING SHOULD BE MORE SPECIFIC TO AREAS IN WHICH
 THEY FEED. IE: B-23 MASTER BRM LTS, A-1 KITCHEN LTS.
 ETC
 PLEASE KNOW IT IS KNOW THAT DURING THE CONSTRUCTION
 THESE WILL MOST LIKELY CHANGE HOWEVER MINIMUMS SHALL BE
 SHOWN AT THIS TIME.
 PLEASE SEE 210.52B1 FOR DINING ROOMS AND AREAS OF THE
 LIKE.
 PLEASE SEE 240.4,310.16, 408.4.
 FBC ADMIN SECTION, 106.1.2, 106.3.5.4 PAR(8).
  
 13) NOTE: PLEASE INDICATE RECESSED LIGHTING IN LOAD
 CALCULATIONS PER 220.3B4, PLEASE KNOW THIS MANY
 FIXTURES CAN NOT BE CONSIDERED AS PART OF THE GENERAL
 LIGHTING LOADS.
  
 14) NOTE: PLEASE INDICATE THE REQUIREMENTS FOR AIR
 TIGHT RATED FIXTURES AS REQUIRED PER FBC
 13-606.1.ABC1.2.4
  
 15) NOTE: PLEASE CORRELATE THE A/C'S. PLEASE SEE PANEL
 SCHEDULES SHOW 3-10KW AHU'S AND LOAD CALCULATIONS
 INDICATE 4-10KW SYSTEMS?
 PLEASE SEE MECHANICAL PLANS WHICH INDICATE 2-15KW
 SYSTEMS AND ONE 5KW.PLEASE KNOW BASED ON THE MAXIMUM
 PERMITTED OVER CURRENT PROTECTION REQUIRED AND THE
 AMOUNT OF LOADS ETC AS SHOWN ON THE M-SHEETS, IF THESE
 UNITS ARE INSTALLED, THIS WILL GREATLY AFFECT THE
 ELECTRICAL BRANCH CIRCUIT RATINGS. PLEASE CORRELATE AND
 ADJUST AS THE EXACT SIZES CAN NOT BE VERIFIED AT THIS
 TIME.
 310.16, 240.4, 424.3B, 424.22(A) AND (B).
  
 16) NOTE:PLEASE INDICATE POOL PUMP AS FUTURE AS IT IS
 NOT BEING INSTALLED AT THIS TIME. THIS CAN BE REVISED
 AT A LATER DATE, OR IF POOL IS NOT BUILT DURING HOUSE
 CONSTRUCTION THIS WILL NOT HAVE TO BE REVISED LATER.
  
 17) NOTE: PLEASE SEE PANEL "A" WHICH SHOWS TWO
 DEDICATED CIRCUITS FOR GARAGE DOOR OPENERS, YET PLANS
 ONLY INDICATE ONE GDO RECEPT ON PLANS?
 PLEASE CORRELATE.
 FBC 106.1.2 ADMIN SECTION
 408.4. NEC.
  
 18) NOTE: PLEASE CLARIFY THE LOCATION OF THE
 DISCONNECTSSHOWN ON THE CU'S ETC. PLEASE SEE IN ORDER
 TO CHANGE OUT THE EQUIPMENT, THE DISCONNECTBEING
 MOUNTED DIRECTLY ON THE EQUIPMENT WOULD CREATE SOME
 INTERFERENCE WIHT THIS.
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-12-06 07:02:23REVIEW COMMENCED
2006-12-05 19:12:18IN ELEC FOR REVIEW