| 2006-12-06 09:16:04 | **** UNSAT **** |
| | |
| | 1) NOTE: PLEASE SEE THAT PLANS SHALL STATE THE |
| | FOLLOWING MINIMUM CODES. |
| | 2002 NFPA-70 (NEC), 2002 NFPA-72. |
| | |
| | 2) NOTE: PLEASE INDICATE THE MINIMUM AIC RATINGS FOR |
| | ALL SERVICE EQUIPMENT. IT IS NOTED THAT THE SUB PANELS |
| | INDICATE 10K , HOWEVER MAINS SHOULD CONTAIN THE MINIMUM |
| | RATINGS ALSO. |
| | PLEASE SEE 110.9 FBC 106.1.2 ADMIN SECTION. |
| | |
| | 3) NOTE: PLEASE SEE PLANS INDICATE A/F PROTECTION AS |
| | EACH RECEPTACLE, HOWEVER BASED ON THE CODE AS STATED ON |
| | E-3 AND IN 210.12B, THE PROTECTION IS FOR THE BRANCH |
| | CIRCUIT. PLEASE KNOW IT IS NOT KNOWN TO THIS OFFICE AT |
| | THIS TIME THAT A AF TYPE RECEPT IS MANUFACTURED. |
| | |
| | 4) NOTE: PLEASE INDICATE THE GFI PROTECTION FOR THE |
| | JACUZZI/WHIRLPOOL TUB. 680.71 |
| | |
| | 5) NOTE: PLEASE SEE MISSING RECEPTS PER 210.52. (2FT OF |
| | WALL IN BEDROOM #2 REDLINED). |
| | PLEASE CHECK OTHER LOCATIONS, HOWEVER PLANS SEEM TO |
| | INDICATE ALL REQUIRED. |
| | |
| | 6) NOTE: PLEASE SEE 210.52C3 FOR MISSING PENINSULAR GFI |
| | RECEPTACLE REQUIRED. (REDLINED) |
| | |
| | 7) NOTE: PLEASE SEE NFPA-72 FOR DEFINITIONS OF SMOKE |
| | DEVICES IN A DWELLING. PLEASE KNOW IN A RECENT SECTION |
| | MEETING WITH NFPA, THE DESIGNATION OF THESE DEVICES |
| | SHOULD BE AS FOLLOWS. PLEASE KNOW IF THE DEVICE IS 120V |
| | WHICH DETECTS AND SOUNDS AND ALARM, THEN THIS DEVICE |
| | WOULD ACTUALLY NOW BE SHOWN A "SA" FOR SMOKE ALARM. IF |
| | THE DEVICE IS LOW VOLTAGE AND PART OF ALV SECURITY OR |
| | LV FIRE ALARM SYSTEM , THEN DEVICE WOULD BE ONLY A "SD" |
| | FOR SMOKE DETECTOR AS IT ONLY DETECTS AND WILL CAUSE |
| | AND ALARM THROUGH OTHER SOUNDING DEVICES. PLEASE KNOW |
| | THAT SD HAS BEEN THE ACCEPTED PRACTICE FOR MANY YEARS |
| | THROUGH THIS AHJ, HOWEVER AS OF RECENT INFORMATION IF |
| | INDEED THESE DEVICES ARE 120V SMOKE ALARMS, PLEASE |
| | CHANGE THE DESIGNATIONS ON PLANS, NOTES AND SYMBOL |
| | LEGEND. |
| | |
| | 8) NOTE: PLEASE ADJUST NOTES PERTAINING TO THE RELEVANT |
| | CODES. PLEASE SEE NFPA-72 11.5.1.1 AND 11.8.3 DICTATES |
| | THE PLACEMENT. |
| | PLEASE SEE THAT THE SA DEVICE SHALL BE LOCATED WITHIN |
| | 12INCHES OF THE HIGHEST POINT ON A FLAT/TRAY CEILING |
| | AND WITHIN 3FT ON SLOPED ONLY CEILING. PLEASE KNOW, IF |
| | THE TRAY IS 12INCHES OR MORE IN DEPTH, THE SA DEVICE |
| | SHALL BE RELOCATED. |
| | |
| | 9) NOTE: PLEASE SEE AREA AT THE TOP OF THE STAIRS WHICH |
| | SHOWS ONLY ONE SMOKE DEVICE. PLEASE KNOW DUE TO THE |
| | DISTANCE AND LOCATION SHOWN, PLEASE EITHER ADD ONE UNIT |
| | OR MOVE THE EXISTING TO BE CLOSER AND IN MORE OF THE |
| | IMMEDIATE VICINITY OUTSIDE BEDROOMS #3 AND MASTER |
| | BEDROOM. |
| | NFPA-72 11.5.1.1 |
| | |
| | 10) NOTE: PLEASE SEE ANY POSSIBLE ZONING COMMENTS FOR |
| | ANY CHANGES OR ACCESS REQUIREMENTS FOR THE GUEST SUITE |
| | LOCATED IN THE REAR. PLEASE KNOW THESE COMMENTS MAY OR |
| | MAY NOT AFFECT THE ELECTRICAL PLANS GREATLY. |
| | |
| | 11) NOTE: PLEASE INDICATE THE ACTUAL RATING OF THE |
| | METER MAIN COMBO. PLEASE ALSO SHOW THIS E-1 PLAN |
| | LAYOUT. |
| | PLEASE SEE MISSING PANEL A-1 ON PLANS. THIS SUB PANEL |
| | COULD NOT LOCATED ON LOWER OR UPPER FLOORS. PLEASE SEE |
| | 110.26,240.24 ETC |
| | FBC 106.1.2 ADMIN SECTION. |
| | |
| | 12) NOTE: PLEASE SEE PANEL SCHEDULES FOR BRANCH |
| | CIRCUITING SHOULD BE MORE SPECIFIC TO AREAS IN WHICH |
| | THEY FEED. IE: B-23 MASTER BRM LTS, A-1 KITCHEN LTS. |
| | ETC |
| | PLEASE KNOW IT IS KNOW THAT DURING THE CONSTRUCTION |
| | THESE WILL MOST LIKELY CHANGE HOWEVER MINIMUMS SHALL BE |
| | SHOWN AT THIS TIME. |
| | PLEASE SEE 210.52B1 FOR DINING ROOMS AND AREAS OF THE |
| | LIKE. |
| | PLEASE SEE 240.4,310.16, 408.4. |
| | FBC ADMIN SECTION, 106.1.2, 106.3.5.4 PAR(8). |
| | |
| | 13) NOTE: PLEASE INDICATE RECESSED LIGHTING IN LOAD |
| | CALCULATIONS PER 220.3B4, PLEASE KNOW THIS MANY |
| | FIXTURES CAN NOT BE CONSIDERED AS PART OF THE GENERAL |
| | LIGHTING LOADS. |
| | |
| | 14) NOTE: PLEASE INDICATE THE REQUIREMENTS FOR AIR |
| | TIGHT RATED FIXTURES AS REQUIRED PER FBC |
| | 13-606.1.ABC1.2.4 |
| | |
| | 15) NOTE: PLEASE CORRELATE THE A/C'S. PLEASE SEE PANEL |
| | SCHEDULES SHOW 3-10KW AHU'S AND LOAD CALCULATIONS |
| | INDICATE 4-10KW SYSTEMS? |
| | PLEASE SEE MECHANICAL PLANS WHICH INDICATE 2-15KW |
| | SYSTEMS AND ONE 5KW.PLEASE KNOW BASED ON THE MAXIMUM |
| | PERMITTED OVER CURRENT PROTECTION REQUIRED AND THE |
| | AMOUNT OF LOADS ETC AS SHOWN ON THE M-SHEETS, IF THESE |
| | UNITS ARE INSTALLED, THIS WILL GREATLY AFFECT THE |
| | ELECTRICAL BRANCH CIRCUIT RATINGS. PLEASE CORRELATE AND |
| | ADJUST AS THE EXACT SIZES CAN NOT BE VERIFIED AT THIS |
| | TIME. |
| | 310.16, 240.4, 424.3B, 424.22(A) AND (B). |
| | |
| | 16) NOTE:PLEASE INDICATE POOL PUMP AS FUTURE AS IT IS |
| | NOT BEING INSTALLED AT THIS TIME. THIS CAN BE REVISED |
| | AT A LATER DATE, OR IF POOL IS NOT BUILT DURING HOUSE |
| | CONSTRUCTION THIS WILL NOT HAVE TO BE REVISED LATER. |
| | |
| | 17) NOTE: PLEASE SEE PANEL "A" WHICH SHOWS TWO |
| | DEDICATED CIRCUITS FOR GARAGE DOOR OPENERS, YET PLANS |
| | ONLY INDICATE ONE GDO RECEPT ON PLANS? |
| | PLEASE CORRELATE. |
| | FBC 106.1.2 ADMIN SECTION |
| | 408.4. NEC. |
| | |
| | 18) NOTE: PLEASE CLARIFY THE LOCATION OF THE |
| | DISCONNECTSSHOWN ON THE CU'S ETC. PLEASE SEE IN ORDER |
| | TO CHANGE OUT THE EQUIPMENT, THE DISCONNECTBEING |
| | MOUNTED DIRECTLY ON THE EQUIPMENT WOULD CREATE SOME |
| | INTERFERENCE WIHT THIS. |
| | |
| | ** ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |