| 2007-01-23 17:55:52 | BUILDING REVIEW CHECKLIST: |
| | 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED |
| | BY SEC. 713.13 FLORIDA STATUTES. |
| | |
| | 2- PAY IMPACT FEES TO PALM BEACH COUNTY. NEED TO BRING |
| | BACK STAMPED PLANS AND COPY OF PAID RECEIPT. |
| | |
| | 3- TRUSSES WILL BE REQUIRED FOR REVIEW PRIOR TO |
| | INSTALLATION. SEE SEC. R802.10 OF 2004 FLORIDA |
| | RESIDENTIAL CODE FOR REQUIRED INFORMATION TO BE ON |
| | TRUSS DRAWINGS. DESIGNER OF RECORD TO REVIEW AND |
| | APPROVE THEM PRIOR TO SUBMITTAL. |
| | |
| | 4- PROVIDE DRAINAGE PLANS AS REQUIRED BY SEC. R401.3 |
| | 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | ***NOTE: SEE SURVEY FOR FINISH FLOOR ELEVATIONS ON |
| | ADJACENT PROPERTIES AND PROPOSED FINISH FLOOR ELEVATION |
| | FOR THIS HOUSE TO AVOID DIVERTING WATER TO ADJACENT |
| | PROPERTIES. |
| | |
| | 5- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| | 9B-72 FOR: |
| | A) FLAT ROOF SYSTEM. SEE ATTACHED COPY OF CITY |
| | POLICY FOR ROOFING PERMITS FOR REQUIRED INFORMATION. |
| | FOR FLAT ROOF SYSTEMS NEED TO SELECT SPECIFIC APPROVED |
| | ASSEMBLY AND FASTENING OPTION. IN ADDITION CHECK IF |
| | SYSTEM IS LIMITED BY GENERAL LIMITATION #7 OR #9 |
| | (LIMITATION #9 CAN'T BE INSTALLED IN THIS AREA) AND |
| | PROVIDE REQUIRED INFORMATION ALSO. SEE GENERAL |
| | LIMITATIONS ON PRODUCT APPROVAL SUBMITTED. |
| | |
| | B) POCKET FRENCH SLIDING GLASS DOORS AS SHOWN ON |
| | PLANS. |
| | |
| | C) PARALAM BEAMS AS SHOWN ON PLANS. |
| | |
| | D) PRECAST LINTELS AS SHOWN ON PLANS. |
| | |
| | E) CONCRETE FLAT ROOF TILE.NOA 01-0417.09 EXPIRED |
| | ON 06/07/2006.NEED CURRENT PRODUCT APPROVAL. ALSO, |
| | SPECIFY TILE FASTENING. IF USING POLYFOAM FOR |
| | ATTACHMENT, THEN PROVIDE PRODUCT APPROVAL FOR |
| | POLYFOAM. |
| | |
| | F) GARAGE DOOR. ES LEGACY REPORT #2318 SUBMITTED |
| | STATES THAT THIS REPORT BELONGS TO FLORIDA PRODUCT |
| | APPROVAL FL674. THERE ARE NOT RECORDS FOR FL674.GO TO |
| | WWW.FLORIDABUILDING.ORG TO VERIFY INFORMATION. PROVIDE |
| | CURRENT GARAGE DOOR PRODUCT APPROVAL. |
| | |
| | G) 3'-6" X 8'-0"***INSWING*** MAHOGANY ENTRY DOOR |
| | AS SHOWN ON PLANS. |
| | |
| | H) 3'-0" X 6'-8"***INSWING*** ENTRY DOOR AT GUEST |
| | SUITE AS SHOWN ON PLANS. |
| | |
| | I) ENTRY DOOR SIDELITES. |
| | |
| | J) DOOR AND WINDOW STRUCTURAL MULLIONS AND SPECIFY |
| | FASTENING. |
| | |
| | K) FIXED WINDOWS AS SHOWN ON PLANS. |
| | |
| | 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 7- PROVIDE MANUFACTURER'S SPECS THAT ALLOWS DECORATIVE |
| | CHIMNEY CAPS. THEN, PROVIDE COMPLETE SPECS SUCH AS |
| | CLEARANCES, MATERIALS ETC. SEC. 106.1.2 CITY AMENDMENTS |
| | TO FBC 2004. |
| | |
| | 8- PROVIDE COMPLETE STRUCTURAL SECTION THRU FIREPLACE |
| | AND CHIMNEY. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 9- PROVIDE COMPLETE SPECIFICATIONS AND UL LISTING FOR |
| | BBQDESIGNED TO BE INSTALLED IN THE LOGGIA. SEC. |
| | 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 10- SHEET A-0:A) NAME OF SOIL TEST ENGINEER DOESN'T |
| | MATCH NAME OF COMPANY WHO SUBMITTED THE SOIL TEST |
| | REPORT. REVISE AS REQUIRED. |
| | |
| | B) NAME OF SURVEYOR DOESN'T MATCH NAME OF SURVEYOR |
| | WHO SUBMITTED SURVEY. REVISE AS REQUIRED. |
| | |
| | C) PROPOSED FINISH FLOOR ELEVATIONS DON'T MATCH |
| | PROPOSED FINISH FLOOR ELEVATIONS SHOWN ON SURVEY. |
| | REVISE EITHER ONE TO MATCH. |
| | |
| | 11- SHEET A-1:NOTE BY LOGGIA AREA CALLS FOR CENTER |
| | LINE OF FIREPLACE AND CABANA DOORS. WHERE IS THE |
| | FIREPLACE?. REVISE AS REQUIRED. |
| | |
| | 12-PROVIDE HANDRAIL AND GUARDRAILS DETAILS SHOWING |
| | DESIGN LOADS COMPLIANCE AS REQUIRED BYSEC. 1607.7.1 |
| | FBC 2004 AND SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 13- CONTRACTOR'S WORKER'S COMPENSATION INSURANCE IS |
| | EXPIRED. UPDATE INFORMATION WITH PERMIT CLERK. |
| | |
| | 14- EXTERIOR ELEVATIONS, WALL SECTIONS AND DETAIL CALL |
| | FOR DIFFERENT ROOF SHEATHING SIZE. SOME CALL FOR 3/4" |
| | PLYWOOD AND SOME CALL FOR 5/8" PLYWOOD. REVISE THEM ALL |
| | AS REQUIRED TO MATCH. |
| | |
| | 15- SPECIFY FIREBLOCKING INALL WALL SECTIONS AS |
| | REQUIRED BY SEC. R602.8 OF 2004 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | 16- PROVIDE COMPLETE SPECS AND INSTALLATION FOR |
| | COLONIAL SHUTTERS SHOWN ON ELEVATIONS.SEC. 106.1.2 |
| | CITY AMENDMENTS TO FBC 2004 ANDSEC. R301 FOR WIND |
| | LOADS. AND, CLARIFY IF DECORATIVE SHUTTERS OR |
| | STRUCTURAL SHUTTERS. STRUCTURAL SHUTTERS REQUIRE |
| | PRODUCTAPPROVAL AND COMPLETE INSTALLATION SCHEDULE. |
| | |
| | 17- PROVIDE ATTIC VENTILATION CALCULATIONS AND VENT |
| | SIZES AND LOCATION TO COMPLY WITH SEC. R806 OF 2004 |
| | FLORIDA RESIDENTIAL CODE. |
| | |
| | 18- PROVIDE SPECIFICATIONS FOR GARAGE INTERIOR DOOR TO |
| | COMPLY WITH SEC. R309.1 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 19- PROVIDE SPECIFICATIONS FOR RAIN DOWNSPOUTS TO |
| | COMPLY WITH SEC. R320.7 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 20-MASTER WALK-IN-CLOSET; SPECIFY SIZE OF ATTIC |
| | ACCESS TO COMPLY WITH SEC. R807 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 21- WALL SECTIONS: SPECIFY MINIMUM FOOTING DEPTH BELOW |
| | GRADE AND MINIMUM. HEIGHT ABOVE GRADE AS REQUIRED BY |
| | SEC. R403.1.4ANDSEC. R404.1.6OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 22- WINDOW AND DOOR DETAILS ON SHEET A-12 DON'T APPLY |
| | TO THIS JOB. DELETE AS REQUIRED.PROVIDE ONLY THE |
| | DETAILS THAT APPLY TO THIS JOB. |
| | |
| | 23- SHEET S-2:A) THERE ARE SOME DETAILSTHAT ARE |
| | KEYED FOR SHEET S-6. THERE IS NOT SHEET S-6. REVISE AS |
| | REQUIRED.EG: 3/S-6 AND 4/S-6. |
| | |
| | B) CONNECTORS M AND N ARE FOR WOOD TO WOOD |
| | CONNECTIONS. NEED TO SPECIFY WOOD TO MASONRY CONNECTORS |
| | AS REQUIRED.SEE SIMPSON CATALOGUE FOR PROPER MASONRY |
| | CONNECTOR AND TYPE AND NUMBER OF FASTENERS.OTHERWISE, |
| | PROVIDE COMPLETE ENGINEERING ANALYSIS FOR CONNECTORS |
| | AND FASTENERS THAT ARE DIFFERENT THAN THOSE TESTED AND |
| | PUBLISHED BY THE MANUFACTURER. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | C) SPECIFY SPECIFIC SIMPSON HANGER FOR STAIRS 2X12 |
| | CARRIAGES. |
| | |
| | D) SPECIFY CONNECTORS FOR GIRDER TRUSSES ENDS BY |
| | STAIRWAY AND GIRDER TRUSS END BYFAMILY ROOM AREA. SEE |
| | PLANS FOR COMMENTS. |
| | |
| | 24- SHEET S-3:A) COORDINATE LOCATION OF ATTIC ACCESS |
| | BY MASTER BEDROOM WITH ARCHITECTURAL DRAWINGS. |
| | |
| | B) WHERE ARE DETAILS 2/S-6. THEREIS NOT SHEET |
| | S-6. |
| | |
| | C) SPECIFY UPLIFT LOAD AND CONNECTOR FOR GIRDER |
| | TRUSS RESTING ON CHIMNEY SIDE. SEE PLANS FOR COMMENTS. |
| | |
| | D) CLARIFY DETAIL 4/S-5 KEYED ON LEFT BOTTOM CORNER |
| | OF GUEST SUITE ROOF.DETAIL 4/S-5 IS FOR A BUCKET |
| | DETAIL. CLARIFY/REVISE AS REQUIRED. |
| | |
| | E) SPECIFY LEDGER SIZE AND FASTENERS AROUND CHIMNEY |
| | TO RECEIVE ROOF TRUSSES. SEE PLANS. |
| | |
| | 25- SHEET S-4:A) REVISE STRUCTURAL NOTES. CLEARLY |
| | INDICATE DESIGN CRITERIA AS REQUIRED BY SEC. R301 OF |
| | 2004 FLORIDA RESIDENTIAL CODE. INCLUDE ALL LOADS |
| | INCLUDING LIVE AND DEAD LOADS. AND, ATTIC LIVE LOADS |
| | FOR ATTIC WITH STORAGE AND ATTICS WITHOUT STORAGE AS |
| | REQUIRED BY TABLE R301.5 2004 FLORIDA RESIDENTIAL CODE. |
| | SPECIFY ALL LOADS. EG:ALL DEAD LOADS PLUS 30PSF LIVE |
| | LOAD FOR ROOF IS NOT PROVIDING ALL NECESSARY |
| | INFORMATION. REVISE ALL INFORMATION AS REQUIRED. |
| | |
| | B) INCLUDE 2004 FLORIDA RESIDENTIAL CODE WHICH IS |
| | THE CODE THAT APPLIES TO ONE AND TWO FAMILY DWELLINGS. |
| | |
| | C) NOTE I REFERS TO SOIL TEST REPORT BY ARDAMAN AND |
| | ASSOCIATES. THIS IS NOT THE SOIL TEST REPORT SUBMITTED |
| | WITH PLANS. REVISE/COORDINATE AS REQUIRED. SEE PROVIDED |
| | SOIL TEST REPORT. |
| | |
| | 26- ENERGY CALCULATIONS:A) REVISE CONDITIONED AREA TO |
| | MATCH ARCHITECTURAL DRAWINGS. |
| | |
| | B) REVISE UNDER ATTIC AREA. SEE ARCHITECTURAL |
| | PLANS. |
| | |
| | C) CLARIFY WHERE ARE THE SINGLE ASSEMBLY AREAS. |
| | |
| | D) REVISE INFORMATION ON TOP OF FORM.THE |
| | PERMITTING OFFICE IS WEST PALM BEACH NOT PALM BEACH |
| | COUNTY AND THE CORRECT JURISDICTION # IS 604700 NOT |
| | 601000. |
| | |
| | 27- SURVEY SUBMITTED;A) SURVEY TO HAVE ORIGINAL |
| | SIGNATURE (NOT COPY) AS REQUIRED BY CHAPTER 472 FLORIDA |
| | STATUTES. |
| | |
| | B) PROPERTY IS LOCATED ON FLOOD ZONE "B" NOT "A5". |
| | SEE MAP DATED MARCH 1, 1979.REVISE AS REQUIRED. |
| | |
| | C) PROVIDE COMPLETE INFORMATION FOR FLOOD MAP. |
| | INCLUDE SUFFIX AND DATE OF MAP . |
| | |
| | D) SURVEY IS MISSING THE DIMENSIONS FOR THE COVERED |
| | REAR PORCH. |
| | |
| | 28- SOIL TEST REPORT SUBMITTED: A) ENGINEER TO PROVIDE |
| | ORIGINAL SIGNATURE, NOT COPY AS REQUIRED BY CHAPTER 471 |
| | FLORIDA STATUTES AND FLORIDAADMINISTRATIVE CODE. |
| | |
| | B) NEED THE FIRM'S CERTIFICATE OF AUTHORIZATION |
| | NUMBER IN THE LETTERHEAD AS REQUIRED BY SEC. |
| | 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE. |
| | |
| | |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |