| Plan Review Notes For Permit 06120074 |
| Permit Number |
06120074 |
|
| Review Stop |
B |
| Sequence Number |
7 |
|
| Notes |
| Date |
Text |
| 2008-03-07 16:08:38 | 2004 FBC W/2006 REVISIONS | | | | | | REVISION TO STRUCTURE AT FACADE IS DENIED BY BUILDING. | | | | | | 1)SPECIFY HOW THE W 8 X 15 STEEL BEAM PROVIDING | | | LATERAL SUPPORT AT THE TWO INTERIOR STEEL COLUMNS WILL | | | BE ATTACHED TO THE NEW AND THE EXISTING STEEL COLUMNS. | | | FBC 106.1.1* CITY AMENDMENTS | | | | | | 2) SPECIFY HOW THE NEW 6 X 12 TS BEAM IS TO BE ATTACHED | | | TO THE EXTERIOR WALLS IN ORDER TO TRANSFER THE TORSION | | | LOADS THE STRUCTURE AT EACH END OF THE BEAM.FBC | | | 106.1.1* CITY AMENDMENTS | | | | | | 3) PLEASE CLARIFY THE WELD LOCATIONS AT THE TOP OF THE | | | TS COLUMN AND THE 6 X 12 STEEL BEAM SHOWN ON DETAIL 7 | | | ON SHEET A-1.2.FBC 106.1.1* CITY AMENDMENTS | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|