| Date |
Text |
| 2008-01-03 16:03:01 | 2004 FBC W/2006 REVISIONS |
| | |
| | REVISION TO STRUCTURE AT FACADE IS DENIED BY BUILDING. |
| | |
| | 1) PLEASE CORRECT THE BUILDING DATA SPECIFIED ON SHEET |
| | A-1.1. FBC TABLE 503 SPECIFIES A MAXIMUM HEIGHT OF 40 |
| | FEET, ONE STORY AND 6,000 SQUARE FEET PER FLOOR FOR |
| | GROUP A-2 OCCUPANCIES WITH TYPE V-B CONSTRUCTION. FBC |
| | SECTION 504.2 ALLOWS AN AUTOMATIC SPRINKLER INCREASE |
| | FOR SPRINKLER SYSTEMS COMPLYING WITH FBC 903.3.1.1 OF |
| | 20 FEET IN HEIGHT AND ONE ADDITIONAL STORY. FBC 506.3 |
| | ALLOWS A 200% AREA INCREASE FOR MULTISTORY BUILDINGS |
| | (6000 X 2 = 12,000 + 6000 = 18,000 SQFT PER FLOOR). |
| | |
| | 2) DETAIL 7 ON SHEET A-1.2 IS SHOWN IN THE WRONG |
| | ORIENTATION BASED ON THE INDICATED LOCATION OF THE |
| | PROPERTY LINE. PLEASE CORRECT. |
| | |
| | 3) THE WALL SECTION AND FOOTING DETAILS ON A-1.2 |
| | INDICATE THAT THE NEW FOOTINGS WILL EXTEND PAST THE |
| | PROPERTY LINES. THIS IS NOT ALLOWED BY FBC 3202.1.1. |
| | PLEASE CORRECT. |
| | |
| | 4) THE ECCENTRIC LOADING OF THE NEW BEAM AND COLUMNS |
| | HAS NOT BEEN ADEQUATELY ADDRESSED. SHOW HOW THE NEW |
| | BEAM AND COLUMN ASSEMBLY WILL BE ANCHORED TO THE |
| | EXISTING FLOOR SYSTEM IN ORDER TO RESIST BENDING. FBC |
| | CHAPTER 16. |
| | |
| | 5) SHEET 13 OF THE ENGINEERED DRAWINGS SHOWS THE |
| | BRACING OF THE NEW WALL TO THE EXISTING WALL. INDICATE |
| | THIS ON THE ARCHITECTURAL DRAWINGS. FBC 106.1.1* CITY |
| | AMENDMENTS. |
| | |
| | - ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |