| 2007-03-19 11:00:57 | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| | MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) SUBMIT THE INSTALLATION INSTRUCTIONS WITH THE DESIGN |
| | PRESSURES FOR THE IMPACT WINDOWS. PROVIDE DOCUMENTATION |
| | THAT THE WINDOWS HAVE BEEN TESTED FOR LARGE MISSLE |
| | IMPACT. (ITEM #6 FROM FIRST REVIEW.) |
| | |
| | 3)SUBMIT PRODUCT APPROVALS FOR THE STRUCTURAL |
| | MULLIONS BETWEEN THE CASEMENT AND FIXED GLASS ARCHED |
| | WINDOWS. (ITEM #7 FROM FIRST REVIEW.) |
| | |
| | 4) THE DEMOLITION PLAN ON SHEET D-1.1 IS STILL |
| | INDICATING SIX WINDOW OPENINGS AND THE NEW ELEVATION ON |
| | A-1.1 SHOWS FIVE NEW WINDOWS. PLEASE CLARIFY. |
| | |
| | 5)ON SHEETS A-1.1 AND A-1.2 THE FLORIDA PRODUCT |
| | APPROVAL NUMBERS FOR THE WINDOWS ARE LISTED ON THE |
| | PLANS PRECEDED BY FBC. THIS IS INCORRECT. THE NUMERALS |
| | SHOULD BE PRECEDED BY FL #. PLEASE CORRECT. |
| | |
| | 6)HAVE A FLORIDA REGISTERED STRUCTURAL ENGINEER |
| | PERFORM A STRUCTURAL ANALYSIS OF THE EXISTING AND |
| | PROPOSED SOUTH WALL OF THE BUILDING AND EXISTING STUCCO |
| | AND WIRE LATH ATTACHMENT TO THE WOOD FRAME WALL. SUBMIT |
| | A SIGNED AND SEALED LETTER STATING THAT THE EXISTING |
| | WOOD FRAME STUCCO WALLS AND PARAPET ARE CAPABLE OF |
| | SAFELY SUPPORTING THE ADDITIONAL DEAD LOADS THAT WILL |
| | BE IMPOSED BY THE ADDITION OF THE CULTURED BRICK AND |
| | TRIM TO THE EXISTING FACADE AND RESIST THE LIVE LOADS |
| | OF A 140 MPH WINDLOAD. |
| | |
| | 7) SPECIFY HOW THE CULTURED VENEER WILL BE ATTACHED TO |
| | THE EXISTING WALL. SEE THE ENCLOSED INSTALLATION |
| | INSTRUCTIONS. |
| | |
| | NOTE: INSTALLATION INSTRUCTIONS AND MSDS FOR THE |
| | CULTURED BRICK HAVE BEEN DOWNLOADED AND INSERTED INTO |
| | YOUR SUBMITTAL PACKAGE. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |